2005-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2B)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SLIDING DOORS - REPORT SUBMITTED
 MISSING FL COVERSHEET
 B) HORIZONTAL SLIDING WINDOWS NO REPORT
  
 NOR STATE FL NUMBER SUBMITTED.
 C) EFIS SYSTEMS- STO MISSING REPORT AND
 FL COVER SHEET.
 D) PLANS DO NOT INDICATE LOUVERS, IF
 THE HAS LOUVERS REPORTS ARE
 REQUIRED.
 NOTE, MOST EFIS REPORTS INDICATE THAT
 THIS SYSTEM IS NOT TO BE USED ON
 HORIZONTAL SURFACES.
  
 3) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, PLANS
 DO NOT INDICATE IF NEGATIVE PRESSURES
 TAKEN ARE END ZONE PRESSUES AND WHAT
 TRIUTARY AREA (WINDOWS AND DOORS) WORST
 CASE 20 SQ FT.
  
 4) ENGINEERING SHEETS 007 AND 010 BOTH
 INDICATE A 2X WOOD BUCK BUT NO
 INFORMATION IS PROVIDED FOR THE
 ATTACHMENT OF BUCK TO STRUCTURE?
 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 5) STO DETAIL SHEET INDICATES A
 SUPPORTING SUBSTRATE OR SUBSHEATHING,
 PLANS DO NOT PROVIDE WHAT THIS WILL BE,
 PLEASE IDENTIFY , SECTION 604 TYPE II
 CONSTRUCTION.
 TYPE II CONSTRUCTION
 TYPE II IS CONSTRUCTION IN WHICH THE
 STRUCTURAL MEMBERS INCLUDING EXTERIOR
 WALLS, INTERIOR BEARI5) STO DETAIL SHEET
 INDICATES A
 SUPPORTING SUBSTRATE OR SUBSHEATHING,
 PLANS DO NOT PROVIDE WHAT THIS WILL BE,
 PLEASE IDENTIFY.SECTION 604NG WALLS,
 COLUMNS,
 BEAMS, GIRDERS, TRUSSES, ARCHES,
 FLOORS AND ROOFS ARE OF NONCOMBUSTIBLE
 MATERIALS AND ARE PROTECTED SO AS TO
 HAVE FIRE RESISTANCE NOT LESS THAN THAT
 SPECIFIED FOR THE STRUCTURAL
 ELEMENTS AS SPECIFIED IN TABLE 600.
 **** CHECK NOA TESTING TO SEE WHAT
 SUBSTRATE WAS USED TO ACHIEVE PRESSURES
 OF NOA!
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  