2005-07-30 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561)###-#### |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2A) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 2B)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) SLIDING DOORS - REPORT SUBMITTED |
| MISSING FL COVERSHEET |
| B) HORIZONTAL SLIDING WINDOWS NO REPORT |
| |
| NOR STATE FL NUMBER SUBMITTED. |
| C) EFIS SYSTEMS- STO MISSING REPORT AND |
| FL COVER SHEET. |
| D) PLANS DO NOT INDICATE LOUVERS, IF |
| THE HAS LOUVERS REPORTS ARE |
| REQUIRED. |
| NOTE, MOST EFIS REPORTS INDICATE THAT |
| THIS SYSTEM IS NOT TO BE USED ON |
| HORIZONTAL SURFACES. |
| |
| 3) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, PLANS |
| DO NOT INDICATE IF NEGATIVE PRESSURES |
| TAKEN ARE END ZONE PRESSUES AND WHAT |
| TRIUTARY AREA (WINDOWS AND DOORS) WORST |
| CASE 20 SQ FT. |
| |
| 4) ENGINEERING SHEETS 007 AND 010 BOTH |
| INDICATE A 2X WOOD BUCK BUT NO |
| INFORMATION IS PROVIDED FOR THE |
| ATTACHMENT OF BUCK TO STRUCTURE? |
| 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 5) STO DETAIL SHEET INDICATES A |
| SUPPORTING SUBSTRATE OR SUBSHEATHING, |
| PLANS DO NOT PROVIDE WHAT THIS WILL BE, |
| PLEASE IDENTIFY , SECTION 604 TYPE II |
| CONSTRUCTION. |
| TYPE II CONSTRUCTION |
| TYPE II IS CONSTRUCTION IN WHICH THE |
| STRUCTURAL MEMBERS INCLUDING EXTERIOR |
| WALLS, INTERIOR BEARI5) STO DETAIL SHEET |
| INDICATES A |
| SUPPORTING SUBSTRATE OR SUBSHEATHING, |
| PLANS DO NOT PROVIDE WHAT THIS WILL BE, |
| PLEASE IDENTIFY.SECTION 604NG WALLS, |
| COLUMNS, |
| BEAMS, GIRDERS, TRUSSES, ARCHES, |
| FLOORS AND ROOFS ARE OF NONCOMBUSTIBLE |
| MATERIALS AND ARE PROTECTED SO AS TO |
| HAVE FIRE RESISTANCE NOT LESS THAN THAT |
| SPECIFIED FOR THE STRUCTURAL |
| ELEMENTS AS SPECIFIED IN TABLE 600. |
| **** CHECK NOA TESTING TO SEE WHAT |
| SUBSTRATE WAS USED TO ACHIEVE PRESSURES |
| OF NOA! |