Plan Review Notes
Plan Review Notes For Permit 05071213
Permit Number 05071213
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-16 00:00:00REDLINED.
  
  
 RISER SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR METER TO MAIN/FIRST MEASN OF
 DISCONNECT.
 PLEASE SEE 250.6,250.24, AN "EQUIPMENT
 GROUNDING" CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  