Plan Review Notes
Plan Review Notes For Permit 05071213
Permit Number 05071213
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-29 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE 240.6, 310.16 600MCM
 ALUM IS NOT RATED FOR 400A'S.
 MAX 350A'S.
  
 2)NOTE: PLEASE SEE NO MORE THAN 8' OF
 UNPROTECTED CONDUCTOR ARE PERMITTED
 INSIDE BLDG WITH OUT OCP . 230.70
 PLEASE ALSO SEE NO MAIN SHOWN. 230.70
  
 3)NOTE: PLEASE SEE 250.6, AN EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.24.
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]