2005-08-16 00:00:00GAS PERMIT FOR THE GENERATOR 05080022
  
 SITE PLAN INDICATES GENERATOR 3 FT FROM
 THE BUILDING.PER 2001 FBC(M)804.3.5
 ITEM #6, EXHAUST TERMINATION SHALL BE A
 MINIMUM OF 3 FT HORIZONTALLY FROM ANY
 PORTION OF THE ROOF STRUCTURE.SHOW
 COMPLIANCE WITH 2001 FBC(M)804.3.3
 THROUGH 804.3.5.
  