Plan Review Notes
Plan Review Notes For Permit 05071132
Permit Number 05071132
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. NOTICE OF COMMENCEMENT REQUIRED.
 2. CHANGE OF OCCUPANCY - SPACE SHALL
 COMPLY WITH ALL FBC-2001 CODE
 REQUIREMENTS. SECTION 34.
 3. APPLICATION REQUIRES A DETAILED
 DISCRIPTION OF WORK.
 4. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER, THEN HE/SHE SHALL
 AFFIX HIS/HER OFFICIAL SEAL.SECTION
 104.2.12.
 5. PLANS FOR REVIEW SHALL BE ROUTED TO
 DBPR HOTEL AND RESTURANT DIVISION FOR
 REVIEW PRIOR TO BEING SUBMITTED TO THE
 CITY WPB FOR PLAN REVIEW. MINIMUM OF TWO
 SETS OF PLANS STAMPED BY DBPR WITH THE
 TWO PAGE "WORKSHEETS" ATTACHED TO BE
 SUBMITTED. SECTION 101.4.7.
 6. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE UTILITY DEPT. PLEASE CONTACT LYNN
 MASSON ENVIRONMENTAL COMPLIANCE. (561)
 822-2271, FAX (561) 822-2279 OR E-MAIL
 [email protected]. WASTE ORD #3434.
 7. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES. SHOW ALL SEATING AND
 INDICATE IF SEATING IS FIXED OR NOT PER
 TABLE 1003.1 AND 403.1 - FOR THE
 PURPOSES OF CALCULATING THE MINIMUM
 NUMBER OF REQUIRED PLUMBING FACILITIES,
 THE REQUIREMENTS OF TABLE 403.1 SHALL
 APPLY TO ANY AREAS OUTSIDE OF THE
 BUILDING THAT ARE USED AS PART OF THE
 BUILDING'S DESIGNATED OCCUPANCY. SECTION
 403.1 WHERE ADDITIONAL SEATING IS ALSO
 UTILIZED IN THESE AREAS, THE ACTUAL
 NUMBER OF SEATS SHALL BE ADDED TO THE
 NUMBER OF PERSONS CALCULATED BY TABLE
 403.1 TO OBTAIN THE TOTAL ADDITIONAL
 FACILITIES REQUIRED.
 8. SHT 3.0P NOTES PLUMBING SCOPE OF WORK
 NOTE NUMBER #4 CUT OFF AND CAN NOT BE
 READ. SECTION 104.2.1.
 9. SHT 3.0P GREASE TRAP UNDER SINK IN
 FOOD PREP AREA IS NOT APPROVED. DELETE
 FROM PLANS.
 10. SHT 3.0P TOILET ROOMS REQUIRE A LOCK
 ON THE DOOR PER SECTION 426.3.2.2.
 11. SHT 3.0P WATER RISER DIAGRAM FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN FEED PIPES. SECTION 606.1(4)-
 KITCHEN FIXTURES AND ONE W/C AND THE
 URINAL ARE NOT SHOWN ON THE RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS AS REQUIRED ON
 RISER. - WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. - THERMAL EXPANSION CONTROL
 REQUIRED PER SECTION 607.3.2.
 12. SHT 3.0P SANITARY RISER DIAGRAM
 MISSING ONE HAND SINK AND THE SCULLARY
 SINK. SECTION 104.3.1.1.
 13 SHT 3.0P EQUIPMENT SCHEDULE DOES NOT
 REFLECT THE FLOOR PLAN. SEE ITEM #1.
 SECTION 104.2.1.
 14. SHT 3.0PPLUMBING NOTES #8, DOES
 NOT COMPLY WITH TABLE 704.1. 2-1/2"AND
 SMALLER PIPE SHALL BE PITCHED AT
 1/4"/FT. - NOTE #11 "L" COPPER REQUIRED
 UNDER THE SLAB. M SOFT ROLL NOT
 MANUFACTURED AND NO JOINTS FOR COPPER
 ARE APPROVED UNDER THE SLAB. - NOTE #12
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE FROM NOTE. SECTION 604.9
 15. SHOW THE FOLLOWING INFORMATION TO
 INDICATE COMPLIANCE:
 FOR THE URINAL:
 A. 11-4.18.4 CONTROLS
 FOR THE LAVS:
 B. 11-4.19.5 FAUCETS
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT AS INDICATED
 ON THE EQUIPMENT SCHEDULE:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 QUESTONS CONTACT 561-805-6692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved