Date |
Text |
2005-07-27 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. NOTICE OF COMMENCEMENT REQUIRED. |
| 2. CHANGE OF OCCUPANCY - SPACE SHALL |
| COMPLY WITH ALL FBC-2001 CODE |
| REQUIREMENTS. SECTION 34. |
| 3. APPLICATION REQUIRES A DETAILED |
| DISCRIPTION OF WORK. |
| 4. IF THE DESIGN PROFESSIONAL IS AN |
| ARCHITECT OR ENGINEER, THEN HE/SHE SHALL |
| AFFIX HIS/HER OFFICIAL SEAL.SECTION |
| 104.2.12. |
| 5. PLANS FOR REVIEW SHALL BE ROUTED TO |
| DBPR HOTEL AND RESTURANT DIVISION FOR |
| REVIEW PRIOR TO BEING SUBMITTED TO THE |
| CITY WPB FOR PLAN REVIEW. MINIMUM OF TWO |
| SETS OF PLANS STAMPED BY DBPR WITH THE |
| TWO PAGE "WORKSHEETS" ATTACHED TO BE |
| SUBMITTED. SECTION 101.4.7. |
| 6. GREASE INTERCEPTOR SHALL BE SIZED BY |
| THE UTILITY DEPT. PLEASE CONTACT LYNN |
| MASSON ENVIRONMENTAL COMPLIANCE. (561) |
| 822-2271, FAX (561) 822-2279 OR E-MAIL |
| [email protected]. WASTE ORD #3434. |
| 7. SUBMIT CALCULATIONS FOR MINIMUM |
| FACILITIES. SHOW ALL SEATING AND |
| INDICATE IF SEATING IS FIXED OR NOT PER |
| TABLE 1003.1 AND 403.1 - FOR THE |
| PURPOSES OF CALCULATING THE MINIMUM |
| NUMBER OF REQUIRED PLUMBING FACILITIES, |
| THE REQUIREMENTS OF TABLE 403.1 SHALL |
| APPLY TO ANY AREAS OUTSIDE OF THE |
| BUILDING THAT ARE USED AS PART OF THE |
| BUILDING'S DESIGNATED OCCUPANCY. SECTION |
| 403.1 WHERE ADDITIONAL SEATING IS ALSO |
| UTILIZED IN THESE AREAS, THE ACTUAL |
| NUMBER OF SEATS SHALL BE ADDED TO THE |
| NUMBER OF PERSONS CALCULATED BY TABLE |
| 403.1 TO OBTAIN THE TOTAL ADDITIONAL |
| FACILITIES REQUIRED. |
| 8. SHT 3.0P NOTES PLUMBING SCOPE OF WORK |
| NOTE NUMBER #4 CUT OFF AND CAN NOT BE |
| READ. SECTION 104.2.1. |
| 9. SHT 3.0P GREASE TRAP UNDER SINK IN |
| FOOD PREP AREA IS NOT APPROVED. DELETE |
| FROM PLANS. |
| 10. SHT 3.0P TOILET ROOMS REQUIRE A LOCK |
| ON THE DOOR PER SECTION 426.3.2.2. |
| 11. SHT 3.0P WATER RISER DIAGRAM FULL |
| OPEN VALVES ARE REQUIRED ON ALL WATER |
| DOWN FEED PIPES. SECTION 606.1(4)- |
| KITCHEN FIXTURES AND ONE W/C AND THE |
| URINAL ARE NOT SHOWN ON THE RISER |
| DIAGRAM. SHOW ALL PIPE SIZES, VALVES, |
| WATER HAMMER ARRESTORS AS REQUIRED ON |
| RISER. - WATER HAMMER ARRESTORS SHALL BE |
| LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| SHOWN. - THERMAL EXPANSION CONTROL |
| REQUIRED PER SECTION 607.3.2. |
| 12. SHT 3.0P SANITARY RISER DIAGRAM |
| MISSING ONE HAND SINK AND THE SCULLARY |
| SINK. SECTION 104.3.1.1. |
| 13 SHT 3.0P EQUIPMENT SCHEDULE DOES NOT |
| REFLECT THE FLOOR PLAN. SEE ITEM #1. |
| SECTION 104.2.1. |
| 14. SHT 3.0PPLUMBING NOTES #8, DOES |
| NOT COMPLY WITH TABLE 704.1. 2-1/2"AND |
| SMALLER PIPE SHALL BE PITCHED AT |
| 1/4"/FT. - NOTE #11 "L" COPPER REQUIRED |
| UNDER THE SLAB. M SOFT ROLL NOT |
| MANUFACTURED AND NO JOINTS FOR COPPER |
| ARE APPROVED UNDER THE SLAB. - NOTE #12 |
| AIR CHAMBERS ARE NOT APPROVED. DELETE |
| REFERENCE FROM NOTE. SECTION 604.9 |
| 15. SHOW THE FOLLOWING INFORMATION TO |
| INDICATE COMPLIANCE: |
| FOR THE URINAL: |
| A. 11-4.18.4 CONTROLS |
| FOR THE LAVS: |
| B. 11-4.19.5 FAUCETS |
| 16. THE FOLLOWING INFORMATION IS |
| REQUIRED FOR THE GAS PERMIT AS INDICATED |
| ON THE EQUIPMENT SCHEDULE: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| QUESTONS CONTACT 561-805-6692 |