2005-08-19 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- MINIMUM DESIGN PRESSURES SHALL BE |
| 10PSF AS REQUIRED BY SEC. 2002.4 FBC |
| 2001. SHEET #2 OF ENGINEERED DRAWINGS IS |
| USING 6 PSF FOR ROOF BEAM. REVISE |
| CALCULATIONS AND WIND LOADS CHART AND |
| GENERAL NOTE #10. |
| |
| 2- ENGINEERED DRAWINGS TO CLEARLY |
| SPECIFY CONNECTION OF ALUMINUM POSTS TO |
| THE FOOTER. SPECIFY SIZE, NUMBER AND HOW |
| MUCH EMBEDMENT IS REQUIRED FOR THE |
| ANCHORS. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| 3- ENGINEERED DRAWINGS TO SPECIFY SIZE |
| OF STRUCTURAL GUTTER. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 4- SHEET 3-B: MANSARD CHART CALLS FOR |
| 2X10 BEAM SIZE TO SPAN 33"-9". PLANS |
| CALL FOR 37'-0" TOTAL SPAN OF SCREEN |
| ENCLOSURE. BEAM DOESN'T WORK. REVISE AS |
| REQUIRED. |
| |
| 5- SCREEN ENCLOSURE LAYOUT TO INCLUDE |
| ENGINEER'S TITLE BLOCK AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTES. |
| |
| 6- PROVIDE RECORDED NOTICE OF |
| COMMENCEMENT. INFORMATION SUBMITTED WAS |
| A COPY OF THE DEED, NOT THE NOC. |
| |