2005-08-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- MINIMUM DESIGN PRESSURES SHALL BE
 10PSF AS REQUIRED BY SEC. 2002.4 FBC
 2001. SHEET #2 OF ENGINEERED DRAWINGS IS
 USING 6 PSF FOR ROOF BEAM. REVISE
 CALCULATIONS AND WIND LOADS CHART AND
 GENERAL NOTE #10.
  
 2- ENGINEERED DRAWINGS TO CLEARLY
 SPECIFY CONNECTION OF ALUMINUM POSTS TO
 THE FOOTER. SPECIFY SIZE, NUMBER AND HOW
 MUCH EMBEDMENT IS REQUIRED FOR THE
 ANCHORS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 3- ENGINEERED DRAWINGS TO SPECIFY SIZE
 OF STRUCTURAL GUTTER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 4- SHEET 3-B: MANSARD CHART CALLS FOR
 2X10 BEAM SIZE TO SPAN 33"-9". PLANS
 CALL FOR 37'-0" TOTAL SPAN OF SCREEN
 ENCLOSURE. BEAM DOESN'T WORK. REVISE AS
 REQUIRED.
  
 5- SCREEN ENCLOSURE LAYOUT TO INCLUDE
 ENGINEER'S TITLE BLOCK AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 6- PROVIDE RECORDED NOTICE OF
 COMMENCEMENT. INFORMATION SUBMITTED WAS
 A COPY OF THE DEED, NOT THE NOC.
  