2005-08-04 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED FLORIDA PRODUCT APPROVAL OR |
| APPLY FOR LOCAL PRODUCT APPROVAL FOR THE |
| ACCORDION SHUTTERS. DADE COUNTY NOA |
| ALONE IS NOT AUTOMATICALLY AN STATE WIDE |
| FLORIDA PRODUCT APPROVAL. IF |
| MANUFACTURER DOESN'T HAVE A FLORIDA |
| PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| APPLY FOR LOCAL PRODUCT APPROVAL USING |
| THE DADE COUNTY NOA BY COMPLETING THE |
| LOCAL PRODUCT APPROVAL FORM DOWNLOADED |
| FROM WWW.FLORIDABUILDING.ORG. |
| |
| 2- KEY SUBMITTED INDICATES THAT EGRESS |
| OPENINGS ARE GOING TO HAVE SHUTTERS. |
| NEED TO HAVE AT LEAST ONE MEANS OF |
| EMERGENCY ESCAPE AS REQUIRED BY SEC. |
| 1005.4.5 FBC 2001. SPECIFY WHICH ONE. |
| |
| 3- A) ENGINEER DRAWINGS FOR STRUCTURAL |
| MODIFICATION ARE NOT CLEAR IF STRUCTURAL |
| TUBE IS FOR OPENING #1 ONLY OR IF IT |
| APPLIES TO OTHER OPENINGS AS WELL. IF |
| SO, SPECIFY WHICH ONES. |
| *NOTE THAT DWG SHOW SHUTTER SPAN OF 57". |
| |
| B) CLARIFY WHY STRUCTURAL MULLION IS |
| SHOWN AT BOTTOM ONLY. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001 |
| |
| 4- NOTICE OF COMMENCEMENT IS EXPIRED IF |
| WORK IS NOT STARTED AFTER 90 DAYS OF |
| RECORDING. NEED TO RE-RECORD IT. |
| |
| 5- REVISE INSTALLATION SCHEDULE. IT |
| CALLS FOR TAPCONS AT ALL OPENINGS. BUT, |
| SOME SHUTTERS ARE TO BE INSTALLED INTO |
| THE STRUCTURAL TUBE. REVISE AS REQUIRED. |
| |