2005-08-31 00:00:00 | ******* UNSAT ******* |
| |
| 1)NOTE:PLEASE SEE MECH NOTES, SITE |
| PLANS, PLANS ARE TO INDICATE 10' |
| CLEARENCE FROM ANY OPENINGS IN HOUSE, |
| ATTIC VENTILATION, OPERABLE WINDOWS, |
| DOORS. ETC. |
| PLEASE SEE SITE PLANS DO NOT INDICATE |
| DIMENTIONS FROM DWELLINGS. |
| |
| 2)NOTE: PLEASE SUBMIT SPECS FOR TRANSFER |
| SWITCH WHICHINDICATE BEING "SERVICE |
| EQUIPMENT RATED" AS REQUIRED UNDER |
| 225.36 |
| PLEASE ALSO SEE THE ATS AS SHOWN DOES |
| NOT MEET 230.76, 230.79, 110.27 |
| MUST CONTAIN AN MANUAL MEANS OF |
| DISCONNECT LOCATED ON THE OUTSIDE OF THE |
| EQUIPMENT. |
| PLEASE SEE THIS MAN MEANS OF DISCONNECT |
| MUST BE RATED FOR THE LOAD SERVED. |
| 110.27 |
| |
| 3)NOTE: PLEASE SEE RISER INDICATES AN |
| "EQUIPMENT GROUNDING CONDUCTOR" BEING |
| INSTALLED FROM METER TO MAIN/FIRST MEANS |
| OF DISCONNNECT. |
| PLEASE SEE EQUIPMENT GRNDS ARE ONLY |
| INSTALLED AFTER THE FIRST MEANS OF DISC. |
| 250.6 |
| |
| 4)NOTE: PLEASE SEE MISSING COLD WATER |
| PIPE AS PART OF THE GROUNDING ELECTRODE |
| SYSTEM. |
| 250.50 |
| |
| 5)NOTE: PLEASE SEE RISER INDICATES THE |
| ENTIRE SERVICE WILL BE FED FROM THIS NEW |
| GENERATOR, HOWEVER PLEASE SEE THE |
| CIRCUITS AS SHOWN ON LOAD CALCULATIONS, |
| DO NOT SEEM TO INDICATE ALL CIRCUITS IN |
| THIS HOUSE. |
| PUMPS, SPECIFIC APPLIANCES, MOTOR LOADS |
| ETC, ETC. |
| PLEASE SUPPLY COMPLETE PANEL SCHEDULES |
| INDICATING ALL CIRCUITS AND LOADS. |
| PLEASE SEE MIN KW RATING FOR RANGES.8KW. |
| PLEASE ADJUST AND SUBMIT REVISED LOAD |
| CALCULATIONS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |