 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1 THE LOADS, EXISTING AND ADDED, EXCEED
 THE RATING OF THE SERVICE. SEE ARTICLE
 230.42.
  
 2} A SMOE DETECTOR IS REQUIRED OIUTSIDE
 THE ADDED BEDROOM PER 313.1.1 FBC
 (RESIDENTIAL).
  
 3} THE RECEPTACLE ADDED IN THE POOL AREA
 AT THE EXISTING PATR OF THE RESIDENCE
 MUST BE GFI PROTECTED PER 210.8(A)(3).
  
 4} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  