Plan Review Notes For Permit 05071080 |
Permit Number |
05071080 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-08-25 00:00:00 | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1 THE LOADS, EXISTING AND ADDED, EXCEED | | THE RATING OF THE SERVICE. SEE ARTICLE | | 230.42. | | | | 2} A SMOE DETECTOR IS REQUIRED OIUTSIDE | | THE ADDED BEDROOM PER 313.1.1 FBC | | (RESIDENTIAL). | | | | 3} THE RECEPTACLE ADDED IN THE POOL AREA | | AT THE EXISTING PATR OF THE RESIDENCE | | MUST BE GFI PROTECTED PER 210.8(A)(3). | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | |
|