2005-08-05 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| 1- WINDOW MULLIONS: A) PROVIDE FLORIDA |
| PRODUCT APPROVAL FOR MULLIONS USED OR |
| APPLY FOR LOCAL PRODUCT APPROVAL BY |
| USING THE DADE COUNTY NOA AND COMPLETING |
| THE LOCAL PRODUCT APPROVAL FORM |
| DOWNLOADED FROM WWW.FLORIDABUILDING.ORG. |
| |
| B) SPECIFY MULLION SIZE AND ANCHORS TO |
| BE USED TO VERIFY COMPLIANCE WITH |
| ENGINEER CALCULATED DESIGN PRESSURES. |
| |
| 2- CUSTOMER QUOTE LIST AND CUSTOMER |
| AGREEMENT SUBMITTED CALLSFOR SINGLE |
| HUNG WINDOWS AND SLIDING GLASS DOORS |
| WITH TEMPERED GLASS. PRODUCT APPROVALS |
| SUBMITTED ARE FOR LARGE MISSILE IMPACT |
| GLASS. CLARIFY AND REVISE AS REQUIRED. |
| *NOTE: ENGINEER IS TAKING INTO |
| CONSIDERATION THE BUILDING TO BE |
| DESIGNED AS ENCLOSED, THEREFORE, IMPACT |
| GLASS IS REQUIRED. |
| REVISE VALUATION OF JOB ACCORDINGLY TO |
| THE IMPACT GLASS DOORS/WINDOWS FEES. |
| |
| 3- SINGLE HUNG WINDOWS SUBMITTED DON'T |
| RESIST THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER. NEED WINDOWS THAT MEET |
| THE CALCULATED DESIGN PRESSURES. SEE |
| PAGE 1 OF 5 OF DADE COUNTY NOA SINGLE |
| HUNG WINDOWS |
| |
| 4- CLEARLY IDENTIFY WHICH GLAZING OPTION |
| IS GOINT TO BE INSTALLED FOR SLIDING |
| GLASS DOORS TO VERIFY COMPLIANCE WITH |
| THE DESIGN PRESSURES CALCULATED BY THE |
| ENGINEER. SEE PAGE 2 OF 8 OF DADE COUNTY |
| NOA FOR SLIDING GLASS DOORS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |