Plan Review Notes
Plan Review Notes For Permit 05071035
Permit Number 05071035
Review Stop B
Sequence Number 3
Notes
Date Text
2005-09-07 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- STILL UNABLE TO PERFORM PLAN REVIEW
 TO VERIFY COMPLIANCE OF PRODUCT USE IF
 COMPLETE INSTALLATION INFORMATION IS NOT
 PROVIDED.
 CONTRACTOR WAS ASKED TO MARK ON DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE,
 CONCRETE BLOCK OR WOOD). SECTION
 104.2.1.2 CITY AMENDMENTS TO THE FBC
 2001 AND THE CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION. IN ADDITION ANCHOR NOTE #2
 ON PAGE 5 OF 5 OF THE ACCORDION DRAWINGS
 CALLS FOR THE SAME INFORMATION I
 REQUESTED ON THE FIRST CHECKLIST.
  
 BY PROVIDING THIS SIMPLE INFORMATION
 PLAN REVIEWER CAN VERIFY THAT PROPER
 ANCHOR TYPE AND SPACING IS USED.
  
 INSTALLATION SCHEDULE CALLS FOR TAPCON
 AS THE ANCHOR TO BE USED. THE ANCHOR
 SCHEDULE IN PAGE 5 OF 5 SHOWS THREE
 DIFFERENT TYPES OF TAPCONS. SOME WORK
 FOR THE SPACING SPECIFIED IN THE
 INSTALLATION SCHEDULE AND SOME DON'T.
 THAT'S WHY IS IMPORTANT TO BE SPECIFIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.