Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop P
Sequence Number 3
Notes
Date Text
2006-07-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEWS:
  
 ****************************************
 A. COMMENTS FROM PREVIOUS REVIEW: NO
 COMMENT RESPONSES TO REVIEW WERE NOT
 SUBMITTED. COMMENT NUMBERS SHALL REMAIN
 THE SAME AS FIRST REVIEW UNTIL ADDRESSED
 ****************************************
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO
 INFORMATION ON THE SEAL HAS BEEN
 IMPRESSED ON THE SHEETS AS REQUIRED BY
 FAC 61G1-16.001. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 SHALL APPEAR ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) & (6) AND FS 481.219,
 481.2055.(NO RESPONSE, SHEETS NOT
 RESUBMITTED. PLEASE CLARIFY)
 ****RESPONSE NOTED, BUT PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT AND CA#
 STILL NOT INDICATED. SEE ATTACHED SHEET
 FROM DBPR WEBSITE.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW
 BACKING & OPENING DIMENSIONS FOR THE W/C
 OPENINGS FOR ADDITIONAL BATHROOMS PER
 BATHROOM REQUIREMENTS PAGE 7.35. THIS
 WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS'
 SHT A4.03 UNIT 'BS', SHT A4.04 UNIT
 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06
 UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15
 UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20
 UNIT 'KN', SHT A4.22 UNIT 'LS', SHT
 A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2',
 SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT
 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28
 UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT
 A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT
 'QN', SHT A4.32 UNIT 'RN', SHT A4.33
 UNIT 'RS', SHT A4.34 UNIT 'SN', SHT
 A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS',
 SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT
 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT
 A4.31.1 UNIT 'STSM'. (NO RESPONSE, NOT
 ADDRESSED. ADDITIONAL BATHROOMS IN THE
 UNIT ARE EXEMPT -ONLY- FROM MANEUVERING
 AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES)
 ****RESPONSE NOTED, BUT DIMENSIONS SHALL
 BE SHOWN IN EACH UNIT, OR INDICATE IN
 EACH UNIT WHERE THE DIMENSIONS SHALL BE
 LOCATED.
  
 13.OK
 14. NOT USED
 15. NOT USED
  
 16. SHTS A4.38, A4.39, & A4.40 ENTRY
 LEVEL TO BE COVERED PER FHA. SUBMIT
 DETAILS FOR BATHROOMS. (RESPONSE NOTED,
 BUT THE FIRST FLOOR SHALL HAVE A
 ACCESSIBLE PATH TO THE ELEVATORS).
  
 17. GROUND FLOOR CONFERENCE ROOM SINKS
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION SHALL BE SHOWN:
 A. 11-4.24.5 CLEAR FLOOR SPACE, CABINET
 DOORS SHALL BE REMOVED, NO DOORS IN THE
 CLEAR FLOOR SPACE.
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
 18. OK
 19. OK
 20. NOT USED
 21. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT INDICATE WHERE
 THE DETAIL CAN BE LOCATED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE POOL/SPA
 HEATER SHEETS HAVE NOT BEEN FOUND.
  
 E. (NEW COMMENT) PIPE SIZE INCORRECT AT
 LAST SPA HEATER. 1-1/4" REQUIRED. 1-1/2"
 REQUIRED FOR 2 SPA HEATERS. 2" REQUIRED
 FOR 3 SPA HEATERS.
  
 22.(INFORMATIONAL)
  
 23. ALL FLOOR PLAN SHEETS, SHOW THE
 LOCATION & NUMBER OF EACH RISER THRU THE
 BUILDING ON EACH FLOOR PLAN AND EACH
 LEVEL. SECTION 104.2.1. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE RISERS ARE
 ONLY SHOWN ON THE GROUND FLOOR. WHERE IS
 LEVEL 3?
  
 24.OK
  
 25. SHT P-2 SHOW THE PIPING FOR ALL
 TRENCH DRAINS WITH PIPE SIZES. THIS
 SHALL BE REFLECTED ON THE STORM RISER
 DIAGRAM. SECTION 104.3.1.1. (NO
 RESPONSE, NOT ADDRESSED FOR TRENCH DRAIN
 AT COL. LINE G/01).
 ****RESPONSE NOTED, BUT PIPING NOT SHOWN
 ON P-2 OR P-68
  
 26. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD. #3434. PLEASE CONTACT LYNN
 MASSON AT (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT APPROVAL
 REQUIRED BY LYNN MASSON FOR LOCATION AND
 MAINTENANCE.
  
 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL
 PIPE SIZES. RECALCULATE ADDITION ON SOME
 RWL'S, INDICATE RWL RISER NUMBERS, 3"
 OVERFLOW SHOWN CONNECTING TO PRIMARY
 SYSTEM AT COL. 24 BETWEEN COLS, A&B.
 PLEASE CLARIFY. SECTION 104.2.1. -(SHOW
 ALL SECONDARY ROOF DRAINS, WITH PIPE
 SIZES, SF, ETC.). (NO RESPONSE NOT
 ADDRESSED).
 ****RESPONSE NOTED, ADDITION STILL NOT
 CORRECT IN SOME PLACES. RECHECK ALL
 ADDITION OF THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. - RWL'S ARE
 NOT NUMBERED. THIS IS REQUIRED TO TRACK
 THE RISERS THRU THE BUILDING. -
 SECONDARY DRAINS ON THE 5TH FLOOR ARE
 SHOWN IN THE PLANTERS FOR SOME, AND IN
 OPEN AREAS FOR OTHERS. PLEASE CLARIFY.
  
 28. OK
 29. OK
 30. OK
  
 31. SHT P-7 SANT. PIPING NOT ALLOWED IN
 THE EGRESS STAIRWAY. NFPA-101 SECTION
 7.1.3.2.1(6). (NO RESPONSE, NOT
 ADDRESSED).RESPONSE NOTED, BUT THE
 PIPING SHALL BE POURED IN SOLID
 CONCRETE, OR DRAIN SHALL BE DESIGNED FOR
 THE VOID.
  
 32. OK
 33. OK
 34. OK
 35. SHT P-9 THE FOLLOWINGPIPING
 LAYOUTS DO NOT REFLECT RISER DIAGRAMS
 44, 47, 42, 40, 39, 20, & 4. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER #4 STILL
 DOES NOT REFLECT THE FLOOR PLAN.
  
 36. SHT P-13 PIPING FOR THE DWV AND
 STORM SYSTEMS NOT APPROVED IN EGRESS
 STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6)
 AND SECTION 1006.1.3.1. (METHOD OF
 ADDRESSING NOT APPROVED. SEE BUILDING
 PLAN REVIEW COMMENT #38).
 ****RESPONSE NOTED, BUT THE PIPING WILL
 HAVE TO BE IN A SOLID POUR, OR A DRAIN
 FOR THE VOID WILL BE REQUIRED.
  
 37. P-14. CONDENSATE IS INDICATED AS 5'
 SEPARATION FOR THE SUPPORTS. INDICATE
 MATERIAL FOR CONDENSATE PIPING. IF PVC,
 MAXIMUM 4' SEPARATION OF SUPPORTS PER
 TABLE 305.5. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 140 MPH WIND LOAD FOR
 SUPPORTS. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT S RESIDENTIAL
 TOWER ROOF LEVEL, NO DETAIL INDICATED.
  
 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON
 RISER DIAGRAM 56, 59A, 92, 93, 94, 95,
 96, 97, 98, 99, & 100. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 94 DOES
 NOT REFLECT THE FIXTURE/WALL LAYOUT.
 (SEE SHT P-17 ALSO).
  
 39. SHT P-15 PIPING NOT APPROVED IN
 EGRESS STAIRWAYS. NFPA-101 SECTION
 7.1.3.2.1(6). (METHOD OF ADDRESSING NOT
 APPROVED. SEE BUILDING PLAN REVIEW #38).
 ****RESPONSE NOTED, BUT THE PIPING SHALL
 BE IN SOLID POUR OR A DRAIN SHALL BE
 INSTALLED FOR THE VOID.
  
 41. OK
 42. OK
 43. OK
  
 44. SHT P-17 THE FOLLOWING RISERS DO NOT
 REFLECT PIPING LAYOUT: 50, 51, 52, & 55.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT 50 & 52 DOES NOT
 REFLECT THE FLOOR PLAN AND 52 SHOWS AN
 OFFSET ON SHT P-16.
  
 46. OK
  
 48. SHT P-22 CONDENSATE LINE SHOWN AS 5'
 SEPARATION BETWEEN SUPPORTS. INDICATE
 TYPE OF MATERIAL. IF PVC PER TABLE 305.5
 MAXIMUM 4' SEPARATION BETWEEN SUPPORTS.
 SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW
 THEY ARE ATTACHED TO THE ROOF AND SHOW
 COMPLIANCE WITH 140 MPH WIND LOAD. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT NO DETAIL
 LOCATED.
 49. OK
  
 50. SHT P-23 RECREATION AT LEVEL 4
 PIPING DOES NOT REFLECT THE FIXTURE
 LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT
 WITH PIPING LAYOUT. SECTION 104.2.1.
 (RISER DIAGRAM DOES NOT REFLECT FIXTURE
 LAYOUT EITHER).(W/C MISSING ON RISER
 DIAGRAM).
 ****RESPONSE NOTED, BUT THE W/C IS STILL
 MISSING AT LEVEL 4 RECREATION.
  
 51. OK
 52. OK
 53. OK
 54. OK
 55. OK
 56. OK
 57. SHT P-53 RISER 8 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RELIEF VENT
 STILL SHOWN AFTER 11 BRANCH INTERVALS.
 58. OK
 59. OK
  
 60. SHT P-54 RISER 14 LOWER OFFSET VENT
 REQUIRED. SEC. 915.3 - MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET &
 THE NEXT LOWER HORIZONTAL BRANCH. 915.3
  
 62. SHT P-55 RISER 20 BATHROOM SHOWN ON
 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON
 5TH FLOOR ON RISER. CORRELATE RISER AND
 FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH
 FLOOR NOT SHOWN ON RISER. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE BATHROOM IS
 STILL SHOWN ON THE 5TH FLOOR.
  
 63. OK
  
 64. SHT P-55 RISER 23 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 LOWER OFFSET VENT REQD. SEC. 915.3. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. SECTION
 915.3.
  
 65. OK
  
 66. SHT P-56 RISER 26 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO BRANCH CONNECTIONS ON HORIZONTAL
 OFFSET. SEC. 711.2. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. SECTION
 915.3.
  
 67. SHT P-56 RISER 28 NO HORIZONTAL DRY
 VENTS. SEC. 905.3/905.4 (16TH FLOOR).
 ****NOT ADDRESSED.
  
 68. SHT P-56 RISER 29 LOWER OFFSET VENT
 REQD. SEC 915.3. - NO CONNECTION TO
 HORIZONTAL OFFSET. SEC. 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. 915.3.
  
 69. SHT P-56 RISER 30 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. (NO RESP0NSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT OFFSETS IN THE
 STACK VENT SHALL BE ABOVE THE FLOOD
 LEVEL OF THE HIGHEST FIXTURE. 905.4.
  
 70. SHT P-56 RISER 32 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. - UPPER OFFSET VENT REQD.
 SEC. 915.2. - SEPARATE RISER SECTION AT
 BASE OF STACK FOR POWDER ROOM, INDICATE
 RISERS CONNECTING FROM UPSTREAM. (33,
 37, 37A) SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. 915.3.
  
 71. SHT P-56 RISER 33 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENT. SEC. 905.3/905.4
 - DOES NOT REFLECT FLOOR PLAN @ 4TH
 LEVEL. (BASE OF STACK) SEC. 104.2.1. -
 VENT FROM 1ST FLOOR FLOOR DRAIN NOT
 SHOWN ON RISER. (SEE P-3, P-4, P-67).
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT SHALL
 OFFSET ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
 72. OK
 73. OK
 74. OK
  
 75. SHT P-59 RISER 50 DOES NOT REFLECT
 THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER STILL DOES
 NOT REFLECT THE FLOOR PLAN.
  
 76. OK
  
 77. SHT P-59 RISER 52 DOES NOT REFLECT
 FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT
 REQUIRED. SEC. 915.2. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT OFFSET IS SHOWN
 ON P-15, BUT NOT ON THE RISER.
  
 78. OK
  
 79. SHT P-60 RISER 56 DOES NOT REFLECT
 THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS
 REQD. SECS. 915.2/915.3. - MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. - NO CONNECTIONS TO HORIZONTAL
 OFFSET. SEC. 711.2.- NO HORIZONTAL DRY
 VENTS. SECS. 905.3/905.4. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT VENT OFFSET
 SHALL BE ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
  
 85. SHT P-61 RISERS 63, 64 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CLARIFY
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISERS STILL DO
 NOT REFLECT THE FLOOR PLAN.
  
 86. SHT P-61 RISER 67 MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT SHALL
 OFFSET ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 87. OK
 89. OK
  
 90. SHT P-62 RISER 71 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO DRY HORIZONTAL VENT. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT OFFSET
 SHALL BE ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 91. OK
  
 92. SHT P-62 RISER 73 & 74 MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 73 SHOWS
 THE RELIEF VENT AFTER 11 BRANCH
 INTERVALS.
  
 94. OK
 95. OK
 96. OK
  
 97. SHT P-64 RISERS 89,94,95,99,101,102
 & 103 DO NOT REFLECT THE FLOOR PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 94 STILL
 DOES NOT REFLECT THE FLOOR PLAN.
  
 98. OK
  
 99. SHT P-67 FOLLOWING ARE CORRECTIONS
 TO BE MADE TO SANT.
 - RISERS 23 & 23A MISLABELED.
 - 2" VENT UP TO RISER
 67 TO READ "TO RISER 67A". (SEE RISER
 67A). - "2" VENT FOR CONT. SEE P-53"
 INDICATE RISER VENT WILL CONNECT TO. -
 - THIS SHEET SHOWS LEVELS AS PARK,
 PARK 2, PARK 3 ECT., BUT SHEETS P-15,
 P-16. & P-17 SHOWS LEVELS AS GROUND
 FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS
 MEZZ. ECT. PLEASE CLARIFY & CORRELATE
 SHEET LEVELS. - RECHECK ADDITION OF
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SOME FIXTURES UNITS ARE NOT
 SHOWN AND ADDED TO THE SYSTEM. INDICATE
 THE SLOPE OF THE PIPE WHERE THE FIXTURES
 UNITS ARE MORE THAN ALLOWED FOR MINIMUM
 SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE
 INSTALLED IN A UNIFORM SLOPE AS REQUIRED
 IN SECTION 704.1. INDICATE ON PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISERS 23 & 23A
 ARE STILL MISLABELED. (SHOULD NOW BE 23,
 23A, 21, NOT 23, 234. - RISER NOT
 INDICATED FOR VENT. - LEVELS STILL
 DIFFERENT FROM SHEET TO SHEET. CLARIFY.
 - STILL MISSING PIPE SIZE, AND NEED TO
 SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. ADDITION TO BE CHECKED AS IT IS
 NOT CORRECT IN SOME AREAS. - CHECK
 PROPER APPLICATION TO THE FIXTURE UNIT
 TABLES 709.1, 709.2, (FOR TRAPS LARGER
 THAN INDICATED IN 709.1), 710.1(1),
 710.1(2). - CONFLICTS IN SLOPE, SHOWS
 1/16"/FT IN SOME AREAS, BUT NOTE STATES
 "1/8"/FT FOR ALL PIPE 3" & LARGER.
 PLEASE CORRELATE.
  
 100. SHT P-68 HORIZONTAL STORM RISER
 DOES NOT REFLECT STORM PIPING IN
 BUILDING. STRUCTURES S1 THRU S9 NOT
 SHOWN. - NO ROOF DRAINS 2650SF, 2350SF,
 2450SF ECT. FOUND. - NO EXFILTRATION
 TRENCHES FOUND. - NO TRENCH DRAINS
 FOUND, RISERS SHOWS 25TH, 26TH, 27TH
 FLOORS ECT. - NO POINT OF REFERENCE TO
 FLOOR PLAN CAN BE FOUND. - RISER HARD TO
 READ, PLEASE INCREASE THE SIZE OF THE
 STORM RISER DIAGRAM AND POSSIBLY SPLIT
 UP TO TWO PAGES TO MAKE RISER EASIER TO
 READ. SECTION 104.2.1.3. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT ADDITION ON
 RISER DIAGRAM AND FLOOR NEEDS TO BE
 RECHECKED. SOME INCONSISTANCIES. ALSO
 SOME AREAS OF THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CHECK
 ENTIRE RISER DIAGRAM.
  
 101. OK
 102. OK
 103. OK
  
 104. BACKFLOW PROTECTION REQUIRED FOR
 IRRIGATION, POOLS, TRASH CHUTE WASH
 DOWNS, AND COOLING TOWER MAKE UP WATER.
 SECTION 608. INDICATE METHOD OF
 PROTECTION FOR EACH SYSTEM. (NO
 RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT NO PROTECTION
 INDICATED FOR THE IRRIGATION, NOR FOR
 THE POOL MAKE UP WATER.
  
 105. PLANS ARE INCOMPLETE AT THIS TIME
 AND MORE COMMENTS MAY BE FORTHCOMING
 WITH THE NEXT REVIEW.
 ****PLANS STILL DO NOT SEEM TO BE 100%
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 (NO RESPONSE)
 ****RESPONSE NOTED, BUT ON SOME COMMENTS
 WITH MULTIPLE COMMENTS, NOT ALL SECTIONS
 OF THE COMMENT WERE ADDRESSED IN
 RESPONSE. ALSO RSPONSES WERE NOT
 DETAILED AS TO WHERE THE CORRECTION
 COULD BE FOUND.
 ****************************************
 ****************************************
  
 NEW COMMENTS: (2ND REVIEW)
  
 1B. OK
  
 2B. SHOW PIPING FOR FIXTURES IN THE
 SHEET WITH FIXTURES, NOT ON THE FLOOR
 BELOW. THIS IS CONFUSING AND IS HARD TO
 FOLLOW THE PIPING, FIXTURES, AND RISER
 DIAGRAM ISOMETRICS. SECTION 104.2.1.
 ****RESPONSE NOTED, BUT THIS IS NOT
 ACCEPTABLE. THE PIPING AS SHOWN IS STILL
 CONFUSING. SOME PIPING THAT SHOULD BE ON
 THE SAME FLOOR AS THE FIXTURES, (SUCH AS
 WASH MACHINE PIPING, LAV AND KITCHEN ARM
 PIPING, ETC.), IS SHOWN ON THE FLOOR
 BELOW ALSO. ALL PIPING SHALL BE SHOWN ON
 THE SAME FLOOR AS THE FIXTURES.
  
 3B. BUILDING PLANS SHALL BE DRAWN TO
 MINIMUM OF 1/8" SCALE. SECTION
 104.2.1.3. ( SEE SHEETS P-2 THRU P-6.
 PLEASE SUBMIT 1/8" SCALE FOR THESE
 SHEETS FOR REVIEW).
 ****RESPONSE NOTED, BUT SHT P-6 HAS NOT
 BEEN CHANGED.
  
 4B. OK
  
 5B. SHT P-1A LOCATED BETWEEN P-19 &
 P-20. INDEX CALLS FOR IT TO BE PRIOR TO
 SHT P-1. PLEASE CORRELATE SHEETS &
 INDEX. SHT 104.2.1.
 ****RESPONSE NOTED, BUT SHT P-1A IS
 INSERTED AFTER P-1. CORRELATE THE INDEX
 AND SHEETS.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 NEW COMMENTS: (3RD REVIEW)
  
 1C. SHT P-1 PIPE SIZES FOR THE SPA
 HEATERS ARE INCORRECT. 2" REQUIRED FOR 3
 HEATERS, 1-1/2" REQUIRED FOR 2 HEATERS,
 AHD 1-1/4" REQUIRED FOR THE LAST HEATER.
 TABLE 402.2
  
 2C. SHTS P-2, P-2A, P-2B, P-2C, P-2D AND
 RISER DIAGRAM P-68, P-68A, P-68B, P-68C.
 CHECK THE ADDITION OF SQUARE FOOTAGE IN
 SYSTEM. ALSO MAKE SURE THE RISER DIAGRAM
 REFLECT THE FLOOR PLAN THROUGHOUT.
 SECTION 104.2.1, TABLE 1106.2, 1106.3
  
 3C. SHT P-7 DOWNSTREAM OF RISER 24, 24A
 DOES NOT REFLECT THE FLOOR PLAN. SECTION
 104.2.1.
  
 4C. ALL FLOOR PLAN SHEETS. NO PIPING IS
 SHOWN FOR WASH MACHINE DRAINS. (SEE
 RISER 32 FOR EXAMPLE). SECTION 104.2.1.
  
 5C. SHT P-9 UNITS 'LT2' EITHER SIDE OF
 COL. LINE S.06 SHOW NO LAV FIXTURES.
 SECTION 104.2.1.
  
 6C. SHT P-9 RISERS 16 & 22 OFFSETS SHOWN
 ARE NOT SHOWN ON THE RISER DIAGRAMS. -
 SHOW PIPING TO W/C'S AND LAVS. SECTION
 104.2.1.
  
 7C. SHT P-15 RISER 73,75,76,77,78,79
 DFU'S DO NOT REFLECT DFU'F INDICATED ON
 THE RISER DIAGRAM. CORRELATE DFU'S.
 SECTION 104.2.1.
  
 8C. SHT P-16 RISER 52 OFFSET NOT SHOWN
 ON THE RISER. CORRELATE FLOOR PLAN AND
 RISER DIAGRAM. SECTION 104.2.1.
  
 9C. SHT P-17 RISERS 62 & 94 FLOOR PLANS
 DO NOT REFLECT THE RISER DIAGRAMS.
  
 10C. SHT P-17 FLOOR PLAN INDICATED
 PARTIAL SOUTH NORTH RESIDENTIAL LOFTS
 2ND LEVEL, BUT SHEET TITLE SHOWS NORTH
 RESIDENTIAL LOFTS 2ND LEVEL. PLEASE
 CORRELATE SHEET INFORMATION. 104.2.1.
  
 11C. SHT P-19 FLOOR PLAN INDICATES NORTH
 RESIDENTIAL, BUT SHEET TITLE INDICATES
 SOUTH RESIDENTIAL. CORRELATE. 104.2.1.
  
 12C. SHT P-23 RECREATION AT LEVEL 2
 SHOWS TWO WASTE ARMS FOR ONE LAV. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 13C. SHT P-37 MISLABELED AS P-39.
 104.2.1.
  
 14C. SHT P-52 RISER DIAGRAM FOR 1W UNIT,
 W/C FOR POWDER NOT VENTED. SECTION
 901.2.1.
  
 15C. SHT P-53 STACK DIAGRAM #4 DOES NOT
 REFLECT THE FLOOR PLAN AT LEVEL 4.
 PLEASE CORRELATE. 104.2.1.
  
 16C. SHT P-54 STACK RISER #12 SHOWS A
 SHOWER, BUT FLOOR PLAN SHOWS A TUB.
 PLEASE CORRELATE. 104.2.1.
  
 17C.SHT P-54 STACK RISER #16 CHECK
 VENTING LEVEL 2. SECTION 104.2.1.
  
 18C. SHT P-54 STACK RISER #18 INDICATES
 AN EXTRA BRANCH LINE BETWEEN LEVELS 3 &
 4. MORE INFORMATION REQUIRED. PLEASE
 EXPLAIN WHAT THIS CONNECTS TO. SECTION
 104.2.1.
  
 19C. SHT P-55 STACK RISER #24 HORIZONTAL
 BRANCH LINE SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. 711.2 (2
 INSTANCES).
  
 20C. SHT P-55 STACK RISER #23 HORIZONTAL
 BRANCH LINE SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. 711.2 (2
 INSTANCES LEVEL 3 & LEVEL 4).
  
 21C. SHT P-56 STACK RISER #29 DOES NOT
 REFLECT THE FLOOR PLAN LEVEL 2.
 CORRELATE. SECTION 104.2.1.
  
 22C. SHT P-59 STACK RISER #50 DOES NOT
 REFLECT THE FLOOR PLAN LEVEL 4.
 CORRELATE. SECTION 104.2.1.
  
 23C. SHT P-60 STACKS 56 & 58 HORIZONTAL
 BRANCH LINES SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. SECTION 711.2
 (2 PLACES EACH STACK).
  
 24C. SHT P-61 STACK RISER #62 HORIZONTAL
 BRANCH CONNECTIONS TO THE HORIZONTAL
 STACK OFFSETS NOT APPROVED. 711.2 (2
 PLACES).
  
 25C. SHT P-61 STACK RISER #63 FIXTURES
 NOT SHOWN ON THE FLOOR PLAN TO REFLECT
 THE RISER AT THE BOTTOM OF THE STACK.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 26C. SHT P-61 STACK RISER #64 LEVEL 4
 OFFSET NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 104.2.1.
  
 27C. ALL RISERS & FLOOR PLANS WHERE
 THERE ARE HORIZONTAL OFFSETS. HORIZONTAL
 BRANCH CONNECTIONS SHALL NOT CONNECT
 WITH IN 2FT OF OFFSETS. SECTION 711.2.
  
 28C. SHT P-64 STACK RISER #94 DOES NOT
 REFLECT THE FLOOR PLAN AT THE BASE OF
 THE STACK. CORRELATE. 104.2.1.
  
 29C. SHT P-67 MAXIMUM 2900 DFU'S ON 12"
 PIPE AT 1/16"/FT SLOPE. 3538 DFU'S
 SHOWN. NOTE INDICATED 3" OR MORE PIPE
 SIZE SHALL SLOPE 1/8"/FT. SOUTH BLDG.
 DRAIN SHOWS 1/16TH/FT SLOPE IN VARIOUS
 PLACES. CORRELATE. SECTION 104.2.1 AND
 TABLE 710.1(1)
  
 30C. SHT P-67 5" MINIMUM REQUIRED
 UPSTREAM OF RISER 102. TABLE 710.1(1).
 PLEASE INDICATE ON RISER.
  
 31C. SHT P-67 CLEANOUT MISSING UPSTREAM
 OF THE BASE OF RISER 26/27 ETC. DOES NOT
 REFLECT THE FLOOR PLAN. CORRELATE.
 104.2.1.
  
 32C. SHT P-67 SHOWS RISER 23, 234.
 SHOULD BE 23, 23A, 21. SECTION 104.2.1.
  
 33C. SHT P-67 UPSTREAM OF RISER 39, 40
 ETC., SHOWS VENT FOR FLOOR DRAINS.
 INDICATE WHERE VENT CONNECTS. SECTION
 104.2.1.
  
 34. THE FOLLOWING STACKS HAVE HORIZONTAL
 DRY VENTS AT THE TOP OF THE STACKS.
 THESE VENTS SHALL BE OFFSET ABOVE THE
 FLOOD LEVEL OF THE HIGHEST FIXTURES.
 THESE STACKS ARE ON SHEETS P-53, P-54K,
 P-55, P-56, P-59, P-60, AND P-62. -
 STACK NUMBERS 1, 2, 13, 15, 10, 12, 14,
 16, 18, 20, 22, 23, 26, 28, 30, 32, 33,
 48, 48A, 53, 55, 56, 57, 60, 67, 71, 73,
 74. SECTION 905.4.
  
 35C. SHT P-39 NO PIPING SHOWN ON THE
 FLOOR PLAN 2ND FLOOR LOFT UNITS. SHOW
 PIPING. SECTION 104.2.1.
  
 36C. ALL RISERS WITH OFFSET VENTS. LOWER
 OFFSET VENTS SHALL CONNECT BETWEEN THE
 OFFSET AND THE NEXT LOWER HORIZONTAL
 BRANCH CONNECTION. SECTION 915.3.
  
 37C. SHT P-62 RISER 72 NO LAV ARM SHOWN
 ON LEVEL 4. CLARIFY. SECTION 104.2.1.
  
 38C. SHT P-62 RISER 79 SHOWS WASH
 MACHINE PIPING FOR 2ND LEVEL, BUT NO
 WASH MACHINE SHOWN. CLARIFY. 104.2.1.
  
 39C. INDICATE THE LOCATION FOR THE VENTS
 FOR THE CONDENSATE RISERS. VENTS ARE NOT
 ALLOWED IN THE WALLS, OR IN THE A/C ROOM
 IF THE ROOM IS A PLENUM. SECTION
 104.2.1.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 REVIEW BY KEN STEVENS