Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop M
Sequence Number 3
Notes
Date Text
2006-09-23 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 104.2.1.3
 CHAPTER ONE AMENDMENTS 2001 QUALITY OF
 PLANS PAGES AC-1 - AC-9.
 2) GARAGE VENTLATION MUST BE TIED IN TO
 EMERGENCY POWER,SO FANS CAN RUN WHEN
 POWER FAILS.
 3) PAGE AC-12 NEED RETURN AIR FOR
 ELEVATOR LOBBY TOWER # 7.
 4) PAGE AC-12 ALL TRASH ROOM A/C MARKED
 # 10,0N HEAT PUMP SCHEDULE A/C ARE
 MARKED 33 - 40 PAGE AC-36.
 5) PAGE AC-01 PLEASE REMOVE EF-38 FRON
 PLANS IF NOT BEING USED.
 6) PAGE AC-12 PLEASE PROVIDE DUCT SIZE
 FOR A/C # 9 BEFOR 6X6 DUCT.
 7) PAGE AC-10 CAN NOT FIND DUCT
 CONTINUATION ON PAGE AC-01.
 8) PAGE AC-2 PLANS AND DRAWING NOTES DO
 NOT MATCH.
 9) PAGE AC-13 AND A LOT OF THE PLANS
 HAVE PRINT ON TOP OF PRINT CAN NOT READ
 PLANS.
 10) PAGE AC-13 SMOKE EVAC.?
 11) PAGE AC-13 PLEASE REFER TO DASHED
 LINES FOR RETURN AIR PLENUM.
 12) PAGE AC-14 PLEASE INDECATE SIZE OF
 RETURN AIR DUCT FOR A/C # 15
 13) PAGE AC-14 PLEASE INDECATE DUCT SIZE
 OF FLEX OFF SUPLY PLENUM ON A/C # 15.
 CAN WE PLEASE SET UP A MEETING AFTER
 OCTOBER 2 TO GO OVER THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732