Notes
Date Text
2006-10-06 00:00:00***PROVISO***
  
 PLEASE NOTE THAT ALL PREVIOUS FIRE
 REVIEW COMMENTS HAVE BEEN ADDRESSED,
 HOWEVER PLEASE SEE THE FOLLOWING FOR
 CLARIFICATION OR INFORMATION REQUIRED:
  
 2ND FIRE REVIEW COMMENTS
  
 COMMENT
 7) OK- PLANS SHOW A #3 REVISION HOWEVER
 NO DETAILS ARE FOUND IN TITLE BLOCK TO
 CORRULATE.
  
 9) OK- EXPLANATION UNDERSTOOD HOWEVER
 PLEASE ADD DIMENSION NOTE TO DRAWINGS.
  
 33) IN ADDITION TO CIRCUIT NUMBERS
 INDICATED, PLEASE ILLUSTRATE DEVICE
 LOCATIONS ON DRAWINGS.
  
 35) PLEASE NOTE THAT THE SEQUENCE OF
 OPERATIONS STILL INDICATE A SUPERVISORY
 SIGNAL. PLEASE CHANGE THAT NOTE TO READ,
 DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 44) OK- IT IS PRESUMED THAT YOUR
 RESPONSE TO #43 AND #44 IS BASED ON NFPA
 101, SECTION 7.3.3.1 REFERENCING 0.2"
 PER PERSON. PLEASE VERIFY.
  
 48) PLEASE ADD NOTE TO SHT LS0.01 AND
 LS0.02 AS INDICATED IN YOUR RESPONSE
 LETTER.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722