Plan Review Notes For Permit 05071027 |
Permit Number |
05071027 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-10-06 00:00:00 | ***PROVISO*** | | | | PLEASE NOTE THAT ALL PREVIOUS FIRE | | REVIEW COMMENTS HAVE BEEN ADDRESSED, | | HOWEVER PLEASE SEE THE FOLLOWING FOR | | CLARIFICATION OR INFORMATION REQUIRED: | | | | 2ND FIRE REVIEW COMMENTS | | | | COMMENT | | 7) OK- PLANS SHOW A #3 REVISION HOWEVER | | NO DETAILS ARE FOUND IN TITLE BLOCK TO | | CORRULATE. | | | | 9) OK- EXPLANATION UNDERSTOOD HOWEVER | | PLEASE ADD DIMENSION NOTE TO DRAWINGS. | | | | 33) IN ADDITION TO CIRCUIT NUMBERS | | INDICATED, PLEASE ILLUSTRATE DEVICE | | LOCATIONS ON DRAWINGS. | | | | 35) PLEASE NOTE THAT THE SEQUENCE OF | | OPERATIONS STILL INDICATE A SUPERVISORY | | SIGNAL. PLEASE CHANGE THAT NOTE TO READ, | | DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | LOCAL REQUIREMENTS. | | | | 44) OK- IT IS PRESUMED THAT YOUR | | RESPONSE TO #43 AND #44 IS BASED ON NFPA | | 101, SECTION 7.3.3.1 REFERENCING 0.2" | | PER PERSON. PLEASE VERIFY. | | | | 48) PLEASE ADD NOTE TO SHT LS0.01 AND | | LS0.02 AS INDICATED IN YOUR RESPONSE | | LETTER. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW (561) 805-6722 |
|