2006-06-25 00:00:00 | REVIEW BACK IN PROGRESS |
| |
| *** SEE NOTES BELOW.*** |
| |
| PLEASE KNOW, PLANS ARE IN GOOD SHAPE. |
| THE ELECTRICAL DESIGN TEAM HAS ADDRESSED |
| COMMENTS WITH ONLY VERY MINOR ITEMS |
| REDLINED. |
| REVIEW PASSED. STAMPED ALL THREE SETS OF |
| ELECTRICAL PLANS, GENERATOR, ATS, FIRE |
| PUMP, AND FIRE PUMP CONTROLLER |
| SUBMITTIALS ALONG WITH REVISED SPEC |
| SHEETS. |
| |
| ** PLEASE SEE ONLY NOTE #1 BELOW SHOULD |
| BE VERIFIED WITH THIS OFFICE BEFORE |
| FINAL ELEVATION OF THE EPSS EQUIPMENT |
| AND BEFORE INSTALLATION OF FORMS FOR THE |
| LOCATION OFGEN RM, AND MAIN ELECTRICAL |
| RM. AND THE FIRE PUMP ROOM. |
| |
| 1) NOTE:PLEASE KNOW, THE ELEVATION OF |
| EPSS "SHALL"MEET NFPA-110 2002. |
| 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE |
| BUILDINGS HOUSING LEVEL 1 OR LEVEL 2 |
| EPSS EQUIPMENT SHALL BE DESIGNED AND |
| LOCATED TO MINIMIZE THE DAMAGE FROM |
| FLOODING, INCLUDING THAT CAUSED BY THE |
| FOLLOWING: |
| (1) FLOODING RESULTING FROM FIRE |
| FIGHTING |
| (2) SEWER WATER BACKUP |
| (3) SIMILAR DISASTERS OR OCCURRENCES BE |
| |
| ** PLEASE SEE COMMENTARY MENTIONS |
| CONSIDERATIONS, HOWEVER 110, 7.1.3(3) |
| ALSO STATES DETERMINATIONS SHALL BEPER |
| AHJ. |
| PLEASE SEE THE FOLLOWING IS TAKEN |
| DIRECTLY OUT OF NFPA-110 |
| |
| **A.7.2.3 EPSS EQUIPMENT SHOULD BE |
| LOCATED ABOVE KNOWN PREVIOUS FLOODING |
| ELEVATIONS WHERE POSSIBLE. |
| |
| **A.7.2.4(3)EPSS DESIGN SHOULD CONSIDER |
| THE "100-YEAR STORM" FLOODING LEVEL OR |
| THE FLOODING LEVEL PREDICTED BY THE |
| SLOSH MODELS FOR A CLASS 4 HURRICANE. |
| |
| |
| ** PLEASE SEE THE FOLLOWING ITEMS WERE |
| REDLINED ON PLANS AND THERE IS NO NEED |
| FOR CORRECTIONS.THESE ARE MINOR ITEMS |
| MISSING AS PREVIOUSLY NOTED AND CAN BE |
| REVISED AT LATER DATE AS PLANS WILL MOST |
| LIKELY HAVE SOME SORT OF REVISIONS. |
| |
| PLEASE SEE E-24 PANEL SYMBOL REMOVED, |
| HOWEVER STILL SHOWS "ELEC-PANEL". |
| |
| PLEASE SEE E-25 WHAT APPEARS TO BE |
| DINING AREA, RECEPT CIRCUITED TO |
| LIGHTING CIRCUIT. VIF. |
| PLEASE ALSO SEE ON SAME SHEET THE LV |
| PANEL STILL SHOWN IN CLOSET WHERE THE |
| LOCATION HAD BEEN REVISED TO NEW |
| LOCATION. |
| |
| PLEASE SEE E-36A MISSING CIRCUIT # FOR |
| RECEPT IN GRAND SALON. |
| |
| PLEASE SEE E-39 AS LV PANEL STILL SHOWN |
| IN CLOSET WHERE LOCATION HAS BEEN |
| REVISED. |
| |
| PLEASE SEE NOTE REGARDING "BUS-DUCT' |
| CURBING AS RESPONSE MENTIONS THE CLOSET |
| SHALL HAVE THIS CURBING AS WAS REVISED |
| ON "A" SHEET. PLANS WERE NOTED AND |
| REDLINED ON BOTH RISER SHEETS FOR 368.6 |
| |
| |
| ************************************** |
| THE FOLLOWING WAS ONLY NOTED ON PLANS |
| FOR REQ'D INFORMATION. |
| |
| 1) A LAYOUT/MAPPING SHALL BE LOCATED IN |
| THE FIRE COMMAND ROOM INDICATING ALL |
| LOCATIONS OFMAINS/SERVICES, GENERATOR, |
| FIRE PUMP. THIS MAPPING SHALL BE COVERED |
| AND PROTECTED FROM ANY DAMAGE RO |
| DETERIORATING CONDITIONS. |
| SIGNAGE REQUIRED AT FCRM, AND AT EACH |
| OTHER LOCATION OF MAINS AND SERVICES |
| DENOTING ALL OTHER LOCATIONS OF MAINS |
| ETC. |
| 230.2E,700.8,701.9 ETC. |
| |
| |
| *********************************** |
| |
| |
| |
| PLEASE SUBMIT THE INFORMATION AS |
| SET-FORTH IN NOTE ONE BEFORE |
| CONSTRUCTION AS NOTED ABOVE. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-06-24 00:00:00 | REVIEW IN PROGRESS/COMMENCED. |