Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-25 00:00:00REVIEW BACK IN PROGRESS
  
 *** SEE NOTES BELOW.***
  
 PLEASE KNOW, PLANS ARE IN GOOD SHAPE.
 THE ELECTRICAL DESIGN TEAM HAS ADDRESSED
 COMMENTS WITH ONLY VERY MINOR ITEMS
 REDLINED.
 REVIEW PASSED. STAMPED ALL THREE SETS OF
 ELECTRICAL PLANS, GENERATOR, ATS, FIRE
 PUMP, AND FIRE PUMP CONTROLLER
 SUBMITTIALS ALONG WITH REVISED SPEC
 SHEETS.
  
 ** PLEASE SEE ONLY NOTE #1 BELOW SHOULD
 BE VERIFIED WITH THIS OFFICE BEFORE
 FINAL ELEVATION OF THE EPSS EQUIPMENT
 AND BEFORE INSTALLATION OF FORMS FOR THE
 LOCATION OFGEN RM, AND MAIN ELECTRICAL
 RM. AND THE FIRE PUMP ROOM.
  
 1) NOTE:PLEASE KNOW, THE ELEVATION OF
 EPSS "SHALL"MEET NFPA-110 2002.
 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE
 BUILDINGS HOUSING LEVEL 1 OR LEVEL 2
 EPSS EQUIPMENT SHALL BE DESIGNED AND
 LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE
 FOLLOWING:
 (1) FLOODING RESULTING FROM FIRE
 FIGHTING
 (2) SEWER WATER BACKUP
 (3) SIMILAR DISASTERS OR OCCURRENCES BE
  
 ** PLEASE SEE COMMENTARY MENTIONS
 CONSIDERATIONS, HOWEVER 110, 7.1.3(3)
 ALSO STATES DETERMINATIONS SHALL BEPER
 AHJ.
 PLEASE SEE THE FOLLOWING IS TAKEN
 DIRECTLY OUT OF NFPA-110
  
 **A.7.2.3 EPSS EQUIPMENT SHOULD BE
 LOCATED ABOVE KNOWN PREVIOUS FLOODING
 ELEVATIONS WHERE POSSIBLE.
  
 **A.7.2.4(3)EPSS DESIGN SHOULD CONSIDER
 THE "100-YEAR STORM" FLOODING LEVEL OR
 THE FLOODING LEVEL PREDICTED BY THE
 SLOSH MODELS FOR A CLASS 4 HURRICANE.
  
  
 ** PLEASE SEE THE FOLLOWING ITEMS WERE
 REDLINED ON PLANS AND THERE IS NO NEED
 FOR CORRECTIONS.THESE ARE MINOR ITEMS
 MISSING AS PREVIOUSLY NOTED AND CAN BE
 REVISED AT LATER DATE AS PLANS WILL MOST
 LIKELY HAVE SOME SORT OF REVISIONS.
  
 PLEASE SEE E-24 PANEL SYMBOL REMOVED,
 HOWEVER STILL SHOWS "ELEC-PANEL".
  
 PLEASE SEE E-25 WHAT APPEARS TO BE
 DINING AREA, RECEPT CIRCUITED TO
 LIGHTING CIRCUIT. VIF.
 PLEASE ALSO SEE ON SAME SHEET THE LV
 PANEL STILL SHOWN IN CLOSET WHERE THE
 LOCATION HAD BEEN REVISED TO NEW
 LOCATION.
  
 PLEASE SEE E-36A MISSING CIRCUIT # FOR
 RECEPT IN GRAND SALON.
  
 PLEASE SEE E-39 AS LV PANEL STILL SHOWN
 IN CLOSET WHERE LOCATION HAS BEEN
 REVISED.
  
 PLEASE SEE NOTE REGARDING "BUS-DUCT'
 CURBING AS RESPONSE MENTIONS THE CLOSET
 SHALL HAVE THIS CURBING AS WAS REVISED
 ON "A" SHEET. PLANS WERE NOTED AND
 REDLINED ON BOTH RISER SHEETS FOR 368.6
  
  
 **************************************
 THE FOLLOWING WAS ONLY NOTED ON PLANS
 FOR REQ'D INFORMATION.
  
 1) A LAYOUT/MAPPING SHALL BE LOCATED IN
 THE FIRE COMMAND ROOM INDICATING ALL
 LOCATIONS OFMAINS/SERVICES, GENERATOR,
 FIRE PUMP. THIS MAPPING SHALL BE COVERED
 AND PROTECTED FROM ANY DAMAGE RO
 DETERIORATING CONDITIONS.
 SIGNAGE REQUIRED AT FCRM, AND AT EACH
 OTHER LOCATION OF MAINS AND SERVICES
 DENOTING ALL OTHER LOCATIONS OF MAINS
 ETC.
 230.2E,700.8,701.9 ETC.
  
  
 ***********************************
  
  
  
 PLEASE SUBMIT THE INFORMATION AS
 SET-FORTH IN NOTE ONE BEFORE
 CONSTRUCTION AS NOTED ABOVE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-24 00:00:00REVIEW IN PROGRESS/COMMENCED.
 REVIEW STOPPED, REVIEW TO CONTINUE ON
 SUNDAY 6/25
2006-06-21 00:00:00MEP ROLLS IN ELEC.