2006-06-28 00:00:00PERMIT: 05071027
 ADD: 2211 N FLAGLER DR
 CONT: PLAN REVIEW
 OWNER: MERCO GROUP
 TEL: (561)296-3300
 ARCH: SONG & ASSOC/ JOHN STRNDBERG
  
 TEL: (561) 655-2423
  
 -PALADIO TERRACE-
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 3RD REVIEW
 ACTION: DENIED
  
 1)LS 0.00 SHEET:
 A) OCCUPANCY CALCULATION AT THE BOTTOM
 OF SHEET, THE OCCUPANCY LOADS FOR THE
 VARIOUS FLOORS DO NOT TOTAL WHAT THE
 PLAN CALLS FOR, INDICATED 6316 ACTUAL
 COUNT IS 6186, CORRECT.
  
 B) TOP CENTER THE TABLE FOR TRAVEL
 DISTANCE AND DEAD ENDS TOTAL THE
 OCCUPANT LOAD BY FLOOR AND THE TOTAL IS
 100 LESS THAN THE OCCUPANT LOAD TABLE.
  
 C) ON THE RIGHT SIDE OF THE PAGE THERE
 IS A THIRD AREA WHICH PROVIDES THE
 OCCUPANT LOAD AND THE FIGURE STATED
 THERE (6081) DOESN'T MATCH EITHER OF THE
 OTHERS QUOTED.
  
 2)COMMENT2A FROM THE PREVIOUS REVIEW.ATRIUM.WE
 WILL BE REVIEWING FOR CODE
 COMPLIANCE UNDER SECTION 412.5 (HIGH
 RISE SMOKE CONTROL) AND SECTION 414.1-10 (ATRIUM).
  
 THE NEW LIFE SAFETY PLANS DATED 07-07-06 INDICATE THE
 NEW
 RATED WALL AND OPENING PROTECTIVES FOR TTHE ATRIUM
 AREA. THE ARCHITECTURAL PLANS NEED TO BE UPDATED TO
 REFLECT
 THE FIRE RATINGS AS WELL AS THE DOOR SCHEDULE.
 CURRENTLY THTHE A SHEETS DO NOT INDICATE ANY RATINGS AT
 ALL.
 2ND FLOOR: C207B, C205A, C206A,
 DOUBLE DOORS TO GARAGE NOT IDENTIFIED,
 C203A INDICATES 45MIN RATED, PIVOT
 DELUGE PROTECTION FRAMELESS, SEE NFPA 80
 DELUGE SYSTEM IS FOR WINDOWS NOT DOORS,
 THE SECOND ISSUE IS THE 45 MIN RATING ON
 A FRAMELESS GLASS DOOR, HOW DO YOU SEAL
 FOR SMOKE AND FIRE?
 3RD FLOOR: AREA WITH ISSUES, STILL
 UNDER CONSIDERATION IN COMMUNICATING
 WITH DESIGN TEAM.C301 PIVOT, FRAMELESS,
  
  
  
 SHEET LS1-02C HAS A 8 1/2X11 SHEET STAPLED TO THE PLAN
 INDICATING THE SEQUENCE OF OPERATION FOR THE MECHANICAL
 AND ELECTRICAL DEVISES.
 THE MECHANICAL AND ELECTRICAL SHEETS WILL NEED TO BE
 FURTHER DEVELOPED TO INCORPORATETHE SEQUENCE OF
 OPERATION ALSO.
  
 PLEASE PROVIDE COMPUTER MODELING FOR
 THE ATRIUM THERE HAS BEEN NO STUDY
 COMPLETED EITHER FOR SMOKE / FIRE PLUME.
  
 3) A SHEETS ARE RED LINED WHERE MISSING FIRE RATINGS ON
 WALLSOR DOORS ARE MISSING IDENTIFICATION.
  
 4)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) R.C. HORIZONTAL ROLLING WINDOWS LOW
 PRESSURE.
  
 B) R.C. FX100 ALUMINUM FIXED WINDOWS
 LOW PRESSURES.
  
 C) GAF MODIFIED BITAMEN ROOF FOR
 CONCRETE DECKS, THE CONTRACTOR
 DIDN'T HIGHLIGHT WHICH SUBSYSTEM
 WILL BE USED. MAY HAVE LOW PRESSURE
 DEPENDING ON THE TYPE OF SYSTEM.
 D) EXTERIOR GUARDRAIL- NO REPORT
 SUBMITTED.
 E) PANEL WALL SYSTEMS: SOFFITS, EFIS
 SYSTEMS, DENSEGLASS
  
 5)SHEET A6.01 DETAIL# 1, INDICATES THE USE OF AN
 EMERGENCY OVERFLOW DRAIN 4 INCHES ABOVE THE ROOF DECK.
 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 6 COMMENT#37 FROM THE PREVIOUS REVIEW,
 50) A6.06 MAIN GLASS CANOPY, PROVIDE
 INFORMATION ON THE CANOPY SYSTEM. ALSO
 PROVIDE INFORMATION ON THE GLAZING
 SYSTEM INDICATING COMPLIANCE WITH
 2407.2.1 ALLOWABLE GLAZING MATERIALS.
 THIS SYSTEM SHALL ALSO BE AN ENGINEERED
 SYSTEM. IT DOESN,T FIT THE PARAMETERS OF
 THE PRODUCT APPROVAL UNDER RULE 9-B, THE
 CANOPY DESIGN WILL BE SITE SPECIFIC. SEE
 "FLORIDA.BUILDING.ORG" FOR REQUIREMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  