2006-06-28 00:00:00 | PERMIT: 05071027 |
| ADD: 2211 N FLAGLER DR |
| CONT: PLAN REVIEW |
| OWNER: MERCO GROUP |
| TEL: (561)296-3300 |
| ARCH: SONG & ASSOC/ JOHN STRNDBERG |
| |
| TEL: (561) 655-2423 |
| |
| -PALADIO TERRACE- |
| |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 3RD REVIEW |
| ACTION: DENIED |
| |
| 1)LS 0.00 SHEET: |
| A) OCCUPANCY CALCULATION AT THE BOTTOM |
| OF SHEET, THE OCCUPANCY LOADS FOR THE |
| VARIOUS FLOORS DO NOT TOTAL WHAT THE |
| PLAN CALLS FOR, INDICATED 6316 ACTUAL |
| COUNT IS 6186, CORRECT. |
| |
| B) TOP CENTER THE TABLE FOR TRAVEL |
| DISTANCE AND DEAD ENDS TOTAL THE |
| OCCUPANT LOAD BY FLOOR AND THE TOTAL IS |
| 100 LESS THAN THE OCCUPANT LOAD TABLE. |
| |
| C) ON THE RIGHT SIDE OF THE PAGE THERE |
| IS A THIRD AREA WHICH PROVIDES THE |
| OCCUPANT LOAD AND THE FIGURE STATED |
| THERE (6081) DOESN'T MATCH EITHER OF THE |
| OTHERS QUOTED. |
| |
| 2)COMMENT2A FROM THE PREVIOUS REVIEW.ATRIUM.WE |
| WILL BE REVIEWING FOR CODE |
| COMPLIANCE UNDER SECTION 412.5 (HIGH |
| RISE SMOKE CONTROL) AND SECTION 414.1-10 (ATRIUM). |
| |
| THE NEW LIFE SAFETY PLANS DATED 07-07-06 INDICATE THE |
| NEW |
| RATED WALL AND OPENING PROTECTIVES FOR TTHE ATRIUM |
| AREA. THE ARCHITECTURAL PLANS NEED TO BE UPDATED TO |
| REFLECT |
| THE FIRE RATINGS AS WELL AS THE DOOR SCHEDULE. |
| CURRENTLY THTHE A SHEETS DO NOT INDICATE ANY RATINGS AT |
| ALL. |
| 2ND FLOOR: C207B, C205A, C206A, |
| DOUBLE DOORS TO GARAGE NOT IDENTIFIED, |
| C203A INDICATES 45MIN RATED, PIVOT |
| DELUGE PROTECTION FRAMELESS, SEE NFPA 80 |
| DELUGE SYSTEM IS FOR WINDOWS NOT DOORS, |
| THE SECOND ISSUE IS THE 45 MIN RATING ON |
| A FRAMELESS GLASS DOOR, HOW DO YOU SEAL |
| FOR SMOKE AND FIRE? |
| 3RD FLOOR: AREA WITH ISSUES, STILL |
| UNDER CONSIDERATION IN COMMUNICATING |
| WITH DESIGN TEAM.C301 PIVOT, FRAMELESS, |
| |
| |
| |
| SHEET LS1-02C HAS A 8 1/2X11 SHEET STAPLED TO THE PLAN |
| INDICATING THE SEQUENCE OF OPERATION FOR THE MECHANICAL |
| AND ELECTRICAL DEVISES. |
| THE MECHANICAL AND ELECTRICAL SHEETS WILL NEED TO BE |
| FURTHER DEVELOPED TO INCORPORATETHE SEQUENCE OF |
| OPERATION ALSO. |
| |
| PLEASE PROVIDE COMPUTER MODELING FOR |
| THE ATRIUM THERE HAS BEEN NO STUDY |
| COMPLETED EITHER FOR SMOKE / FIRE PLUME. |
| |
| 3) A SHEETS ARE RED LINED WHERE MISSING FIRE RATINGS ON |
| WALLSOR DOORS ARE MISSING IDENTIFICATION. |
| |
| 4)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| |
| A) R.C. HORIZONTAL ROLLING WINDOWS LOW |
| PRESSURE. |
| |
| B) R.C. FX100 ALUMINUM FIXED WINDOWS |
| LOW PRESSURES. |
| |
| C) GAF MODIFIED BITAMEN ROOF FOR |
| CONCRETE DECKS, THE CONTRACTOR |
| DIDN'T HIGHLIGHT WHICH SUBSYSTEM |
| WILL BE USED. MAY HAVE LOW PRESSURE |
| DEPENDING ON THE TYPE OF SYSTEM. |
| D) EXTERIOR GUARDRAIL- NO REPORT |
| SUBMITTED. |
| E) PANEL WALL SYSTEMS: SOFFITS, EFIS |
| SYSTEMS, DENSEGLASS |
| |
| 5)SHEET A6.01 DETAIL# 1, INDICATES THE USE OF AN |
| EMERGENCY OVERFLOW DRAIN 4 INCHES ABOVE THE ROOF DECK. |
| 1503.4.2 OVERFLOW DRAINS SHALL BE |
| THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| WITH THE INLET FLOW LINE LOCATED 2" |
| ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| OR PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| |
| 6 COMMENT#37 FROM THE PREVIOUS REVIEW, |
| 50) A6.06 MAIN GLASS CANOPY, PROVIDE |
| INFORMATION ON THE CANOPY SYSTEM. ALSO |
| PROVIDE INFORMATION ON THE GLAZING |
| SYSTEM INDICATING COMPLIANCE WITH |
| 2407.2.1 ALLOWABLE GLAZING MATERIALS. |
| THIS SYSTEM SHALL ALSO BE AN ENGINEERED |
| SYSTEM. IT DOESN,T FIT THE PARAMETERS OF |
| THE PRODUCT APPROVAL UNDER RULE 9-B, THE |
| CANOPY DESIGN WILL BE SITE SPECIFIC. SEE |
| "FLORIDA.BUILDING.ORG" FOR REQUIREMENTS. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |