Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop Z
Sequence Number 2
Notes
Date Text
2006-01-27 00:00:001) THE BUILDING FOOTPRINT AND POOL DECK
 DOES NOT MATCH THOSE APPROVED BY ORD.
 NO. 3804-04.PROVIDE A PLAN SHOWING THE
 DIFFERENCES.DEPENDING ON THE SCALE OF
 THE CHANGES, EITHER A MINOR OR MAJOR
 AMENDMENT WILL BE REQUIRED.
  
 2) PARKING DETAILS FOR REGULAR, COMPACT
 AND DISABLED SPACES ARE REQUIRED.
  
 3) ALL DRIVE AISLES HAVING 90 DEGREE
 PARKING STALLS REQUIRE A 24 FOOT WIDTH.
 THIS STANDARD IS NOT MET ON THE NORTHERN
 AND WESTERN MOST PARKING AISLES ON
 LEVELS 1, 2 AND 3 AND THE EASTERNMOST
 AISLES ON LEVELS 2 AND 3.
  
 4) COMPACT SPACES SHALL BE CLEARLY
 MARKED ON ALL SHEETS.
  
 5) THE PARKING SPACE LABELS/COUNTS ON
 SHEET A1.02 ARE INCORRECT AND
 MISLABELED.
  
 6) SUPPORT COLUMNS MAY NOT BE LOCATED IN
 THE DOUBLE STRIPED AREA ON BOTH SIDES OF
 A REGULAR SPACE AS THIS RENDERS THE
 SPACE TOO NARROW TO PROVIDE ADEQUATE
 TURNING RADIUS.
  
 7) THE SPACE LABELS AS 1-233 DOES NOT
 ALLOW FOR ADEQUATE TURN RADIUS TO USE.
 THE WALL BY THE SPACE BLOCKS THE ABILITY
 OF SPACES 1-233 AND 1-234 TO SAFELY BACK
 OUT.
  
 8) THE STOP BARS AT THE ANGLED SPACES BY
 THE ENTRANCE ARE INCORRECTLY PLACED.
  
 9) 13 DISABLED SPACES, NOT 9 ARE
 REQUIRED FOR THE PROJECT.
  
 10) LOCATION OF STOP BARS INCORRECT FOR
 COMPACT SPACES.
  
 11) SPACE 1-196 TOO NARROW.SPACE 1-236
 MARKED INCORRECTLY.SPACE 1-035 IS NOT
 DEEP ENOUGH.
  
 12) WALLS ENCROACH INTO SPACES 1-047,
 1-048, 1-065, 1-066, 1-068, 1-069,
 1-086, 1-087, 1-104, 1-105, 1-122,
 1-123, 1-125, 1-126, 1-143, 1-144,
 1-166, 1-167, 1-178, 1-179, 1-184,
 1-185, 1-204 AND 1-205.
  
 13) ADJUST THE CURBING BY THE PARALLEL
 SPACES BY THE WEST ENTRANCE ISLAND TO
 HAVE 45 DEGREE ANGLES FOR EASIER
 PARKING.
  
 14) SPACES 2-001, 2-002, 2-053, 2-092,
 2-131, 2-172, 2-206 AND 2-207 HAVE
 COLUMNS INTRUDING IN THEM.
  
 15) THE DISABLED ACCESS WAY BY SPACE
 2HC-004 HAS COLUMNS INTRUDING IN IT.
  
 16) SPACE 2-037 IS NOT DEEP ENOUGH.
 SPACES 2-198 AND 2-199 ARE NOT STRIPED
 CORRECTLY.
  
 17) THE SPACE LABELED AS 2-202 MAY NOT
 BE COUNTED AS IT DOES NOT CONFORM TO ANY
 OF THE CODE REQUIREMENTS.
  
 18) THE WALL ADJACENT TO SPACE 2-202
 SPACE BLOCKS THE ABILITY OF SPACES 2-202
 AND 2-203 TO SAFELY BACK OUT.THE WALL
 ALSO EXTENDS INTO THE DRIVE AISLE.
  
 19) THE COLUMN ADJACENT TO SPACE 2-036
 EXTENDS INTO THE DRIVE AISLE.
  
 20) THE COLUMN BETWEEN SPACES 2-198 AND
 2-199 EXTENDS INTO THE DRIVE AISLE.
  
 21) WALLS ENCROACH INTO SPACES 2-049,
 2-050, 2-070, 2-071, 2-088, 2-089,
 2-127, 2-128, 2-168, 2-169, 2-180, AND
 2-181.
  
 22) SPACES 3-001, 3-002, 3-053, 3-122,
 3-161 AND 3-162 HAVE COLUMNS INTRUDING
 IN THEM.
  
 23) SPACE 3-037 IS NOT DEEP ENOUGH.
 SPACES 3-148 AND 3-149 ARE NOT STRIPED
 CORRECTLY.
  
 24) THE WALL ADJACENT TO SPACE 3-152
 SPACE BLOCKS THE ABILITY OF SPACES 3-152
 AND 3-153 TO SAFELY BACK OUT.THE WALL
 ALSO EXTENDS INTO THE DRIVE AISLE.
  
 25) THE COLUMN ADJACENT TO SPACE 3-036
 EXTENDS INTO THE DRIVE AISLE.
  
 26) THE COLUMN BETWEEN SPACES 3-148 AND
 3-149 EXTENDS INTO THE DRIVE AISLE.
  
 27) WALLS ENCROACH INTO SPACES 3-049,
 3-050, 3-067, 3-068, 3-070, 3-071,
 3-088, 3-089, 3-108, 3-109, 3-118,
 3-119, 3-130, 3-131, 3-136 AND 3-137.
  
 28) IT APPEARS THAT THE RETAINING WALL
 ATTACHED TO THE BUILDING IS OUTSIDE OF
 THE PROPERTY LINE ON THE NORTH SIDE OF
 THE SITE AND MAY BE AN ISSUE IN THE
 SOUTHEAST CORNER.ALL RETAINING WALLS,
 PLANTER BOXES AND OTHER FEATURES
 ATTACHED TO THE BUILDING SHALL BE INSIDE
 THE PROPERTY LINE NOT IN THE PUBLIC
 RIGHT-OF-WAY.ENSURE THAT THIS
 REQUIREMENT IS MET AROUND THE ENTIRE
 BUILDING.SHOW THE PROPERTY LINES ON
 THE ELEVATIONS TO VERIFY THERE IS NO
 ENCROACHMENT.
  
 29) A LANDSCAPE PLAN AND A SURVEY
 SHOWING THE BUILDING FOOTPRINT ARE
 REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.