Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****************************************
 A. COMMENTS FROM PREVIOUS REVIEW: NO
 COMMENT RESPONSES TO REVIEW WERE NOT
 SUBMITTED. COMMENT NUMBERS SHALL REMAIN
 THE SAME AS FIRST REVIEW UNTIL ADDRESSED
 ****************************************
  
 1. SHT A0.04C ACCESSIBILITY REQUIREMENTS
 PER SECTIONS 11-4.16.5, 11-4.19.5 AND
 11.4.21.7 TO BE SHOWN ON PLANS. (SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART.)
 2. SHT A0.04.4 DETAIL 04.(NOT SHOWN AS
 DETAIL 10) SUBMIT CALCULATIONS FOR GRAB
 BAR BACKING PER SECTION 609.8 OF THE
 ANSI A117.1 STANDARD FOR THE SUPPORTIVE
 STRUCTURE. INDICATE GUAGE OF METAL
 PLATE. (NOT ADDRESSED, NO RESPONSE)
 3. SHT C1 SURVEY NOT SIGNED, SEALED, AND
 DATED AS REQUIRED BY FAC 61G15-23.002 &
 FS 471.025. (NO RESPONSE, NOT ADDRESSED)
 4. SHTS C-2 THRU C-5 ENGINEERS SEAL
 SHALL IMPART INFORMATION REQUIRED BY FAC
 61G15-233.001 & FS 471.025 ON EACH
 SHEET. THE INFORMATION REQUIRED ON SEAL
 HAS NOT BEEN IMPRESSED ON EACH SHEET AS
 REQUIRED. - THE SIGNATURE REQUIRED
 APPEARS TO BE INITIALS WHICH ACCORDING
 TO FBPE IS NOT APPROVED AND A SIGNATURE
 IS REQUIRED. IF INDEED THIS IS YOUR
 LEGAL SIGNATURE, PROVIDE A SIGNED,
 SEALED, DATED, AND NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR
 FILES. (NO RESPONSE, NOT ADDRESSED)
 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO
 INFORMATION ON THE SEAL HAS BEEN
 IMPRESSED ON THE SHEETS AS REQUIRED BY
 FAC 61G1-16.001. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 SHALL APPEAR ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) & (6) AND FS 481.219,
 481.2055.(NO RESPONSE, SHEETS NOT
 RESUBMITTED. PLEASE CLARIFY)
 6. SHT A1.02C DETAIL 04 SHOW TURNING
 AREA IN THE STAFF TOILET AS REQUIRED BY
 SECTION 11-4.22.3. (TURNING AREA TO BE
 UNOBSTRUCTED, AND AS SHOWN IS IN TWO
 SEPARATE ROOMS WITH THE WALL IN THE
 MIDDLE OF THE TURNING AREA).
 7. SHT A1.02C DETAIL 01 SHOW TURNING
 AREA IN THE RESTROOMS, NOT IN THE
 STALLS. SECTION 11-4.22.3. (NO RESPONSE,
 NOT ADDRESSED).
 8. SHT A1.02C A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AND WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. (NO RESPONSE, NOT ADDRESSED).
 9. SHT 1.05C DETAIL 02 SHOW THE TURNING
 AREA IN RESTROOM NOT IN THE STALL.
 SECTION 11-4.22.3. (NO RESPONSE, NOT
 ADDRESSED).
 10. PLEASE INDICATE IF THE KITCHEN WILL
 BE BUILT-OUT ON THIS PERMIT OR WILL IT
 BE A SEPARATE PERMIT, AS THE PLANS WILL
 HAVE TO BE ROUTED TO DBPR RESTURANT AND
 HOTEL DIVISION PRIOR TO APPROVAL.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 11. SHTS A1.05, A1.09, A1.10, & A1.11.
 SS-1 SUBMIT CALCULATIONS FOR PRIMARY &
 SECONDARY ROOF DRAINS. SHOW TOTAL AREA,
 1/2 AREA OF ALL VERTICAL WALLS,
 (INCLUDING PARAPETS), ALL AREAS OF ROOFS
 ADDED TO ROOF AREA FROM ABOVE ADDED TO
 ROOF AREA IN CALCULATIONS. INDICATE
 TOTAL AREA DRAINED BY EACH ROOF DRAIN. -
 THIS IS REQUIRED FOR EACH ROOF LEVEL AND
 FOR THE RECREATION LEVEL. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS
 AND SCUPPERS. INDICATE THE SIZE OF ALL
 SCUPPERS AND SUBMIT A DETAIL SHOWING THE
 HEIGHT, WIDTH AND THE HEIGHT OF THE FLOW
 LINE OFF THE ROOF. SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW
 BACKING & OPENING DIMENSIONS FOR THE W/C
 OPENINGS FOR ADDITIONAL BATHROOMS PER
 BATHROOM REQUIREMENTS PAGE 7.35. THIS
 WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS'
 SHT A4.03 UNIT 'BS', SHT A4.04 UNIT
 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06
 UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15
 UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20
 UNIT 'KN', SHT A4.22 UNIT 'LS', SHT
 A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2',
 SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT
 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28
 UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT
 A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT
 'QN', SHT A4.32 UNIT 'RN', SHT A4.33
 UNIT 'RS', SHT A4.34 UNIT 'SN', SHT
 A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS',
 SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT
 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT
 A4.31.1 UNIT 'STSM'. (NO RESPONSE, NOT
 ADDRESSED. ADDITIONAL BATHROOMS IN THE
 UNIT ARE EXEMPT -ONLY- FROM MANEUVERING
 AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES)
 13. SHTS A4.10 - A4.16 CLEAR FLOOR SPACE
 SHALL BE FLUSH WITH THE CONTROL WALL FOR
 SHOWERS AND PARALLEL TO SHOWER. PAGE
 7.56. (NO RESPONSE, NOT ADDRESSED).
 16. SHTS A4.38, A4.39, & A4.40 ENTRY
 LEVEL TO BE COVERED PER FHA. SUBMIT
 DETAILS FOR BATHROOMS. (RESPONSE NOTED,
 BUT THE FIRST FLOOR SHALL HAVE A
 ACCESSIBLE PATH TO THE ELEVATORS).
 17. GROUND FLOOR CONFERENCE ROOM SINKS
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 18. SHT P-1 REGULATORS SHOW 7"W/C -
 TABLE 402(2) IS FOR 1/2 PSI WHICH IS 11"
 TO 14"W/C. PLEASE CLARIFY AND VERIFY
 INPUT PRESSURE FOR GAS SYSTEM. (NO
 RESPONSE, NOT ADDRESSED).
 19. SHT P-1 INDICATE MATERIAL TO BE USED
 FOR THE REGULATOR VENT PIPING. (NON
 COMBUSTABLE REQUIRED). (NO RESPONSE, NOT
 ADDRESSED).
 21. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. (NO RESPONSE, NOT
 ADDRESSED).
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (DOWNSTREAM OF REGULATOR). (NO RESPONSE,
 NOT ADDRESSED).
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (NO RESPONSE, NOT
 ADDRESSED).
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 22. SEPARATE GAS PERMIT REQUIRED. AT
 TIME OF APPLICATION, CONTRACTOR SHALL
 SUBMIT A PICTURE I.D. OF THE WELDER,
 WELDING CERTIFICATION, AND A COPY OF THE
 WELDING PROCEDURE. (INFORMATIONAL)
 23. ALL FLOOR PLAN SHEETS, SHOW THE
 LOCATION & NUMBER OF EACH RISER THRU THE
 BUILDING ON EACH FLOOR PLAN AND EACH
 LEVEL. SECTION 104.2.1. (NO RESPONSE,
 NOT ADDRESSED).
 24.SHT P-2 RISER DESIGNATIONS 35, 36,
 45, 46, 46A, & 47 ARE NOT SHOWN. (NO
 RESPONSE, NOT ADDRESSED).
 25. SHT P-2 SHOW THE PIPING FOR ALL
 TRENCH DRAINS WITH PIPE SIZES. THIS
 SHALL BE REFLECTED ON THE STORM RISER
 DIAGRAM. SECTION 104.3.1.1. (NO
 RESPONSE, NOT ADDRESSED FOR TRENCH DRAIN
 AT COL. LINE G/01).
 26. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD. #3434. PLEASE CONTACT LYNN
 MASSON AT (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. (NO
 RESPONSE, NOT ADDRESSED).
 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL
 PIPE SIZES. RECALCULATE ADDITION ON SOME
 RWL'S, INDICATE RWL RISER NUMBERS, 3"
 OVERFLOW SHOWN CONNECTING TO PRIMARY
 SYSTEM AT COL. 24 BETWEEN COLS, A&B.
 PLEASE CLARIFY. SECTION 104.2.1. -(SHOW
 ALL SECONDARY ROOF DRAINS, WITH PIPE
 SIZES, SF, ETC.). (NO RESPONSE NOT
 ADDRESSED).
 28. SHT P-4 STATES "3"S FOR CONT. SEE
 P-4 HEALTH CLUB". THIS WAS NOT FOUND ON
 SHT P-4. PLEASE CLARIFY. (NO RESPONSE,
 NOT ADDRESSED).
 29. SHT P-4 INDICATE WHAT THE
 DESIGNATION FOR "DL" REPRESENTS. (NO
 RESPONSE, NOT ADDRESSED).
 30. SHT P-7 RISER DESIGNATIONS 35, 36,
 38, 45, 46, & 46A NOT SHOWN. PLEASE SHOW
 ALL RISERS FOR EACH FLOOR LEVEL. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 31. SHT P-7 SANT. PIPING NOT ALLOWED IN
 THE EGRESS STAIRWAY. NFPA-101 SECTION
 7.1.3.2.1(6). (NO RESPONSE, NOT
 ADDRESSED).
 32. SHT P-8 OFFSETS SHOWN FOR RISERS 6,
 10, 11, 12, 15, & 17, 18, 19, 20 ARE NOT
 SHOWN ON THE RISER DIAGRAMS. SECTIONS
 104.2.1, & 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 33. SHT P-9 OFFSETS SHOWN FOR RISERS 42,
 44, 47, 30, 34, 35, 36, 21, 25, 1, AND
 TO TOILET ROOMS RECREATION LEVEL 4 ARE
 NOT SHOWN NO THE RISER DIAGRAMS.
 SECTIONS 104.2.1, & 104.3.1. (NO
 RESPONSE, NOT ADDRESSED).
 34. SHT P-9SHOW THE TYPICAL PIPING
 LAYOUTS FOR RISERS 16, 22, 28, & 29.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 35. SHT P-9 THE FOLLOWINGPIPING
 LAYOUTS DO NOT REFLECT RISER DIAGRAMS
 44, 47, 42, 40, 39, 20, & 4. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 36. SHT P-13 PIPING FOR THE DWV AND
 STORM SYSTEMS NOT APPROVED IN EGRESS
 STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6)
 AND SECTION 1006.1.3.1. (METHOD OF
 ADDRESSING NOT APPROVED. SEE BUILDING
 PLAN REVIEW COMMENT #38).
 37. P-14. CONDENSATE IS INDICATED AS 5'
 SEPARATION FOR THE SUPPORTS. INDICATE
 MATERIAL FOR CONDENSATE PIPING. IF PVC,
 MAXIMUM 4' SEPARATION OF SUPPORTS PER
 TABLE 305.5. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 140 MPH WIND LOAD FOR
 SUPPORTS. (NO RESPONSE, NOT ADDRESSED).
 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON
 RISER DIAGRAM 56, 59A, 92, 93, 94, 95,
 96, 97, 98, 99, & 100. (NO RESPONSE, NOT
 ADDRESSED).
 39. SHT P-15 PIPING NOT APPROVED IN
 EGRESS STAIRWAYS. NFPA-101 SECTION
 7.1.3.2.1(6). (METHOD OF ADDRESSING NOT
 APPROVED. SEE BUILDING PLAN REVIEW #38).
 41. SHT P-15 THE FOLLOWING PIPING
 LAYOUTS DO NOT REFLECT THE RISER
 DIAGRAMS: 48, 48A, 49, 50, 51, 56, 58,
 59, 59A, 61, 62, 64, 67, & 67A. - NOT
 ALL PIPING SHOWN ON THE RISER DIAGRAMS.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 42. SHT P-16 NO PIPING TO W/M SHOWN AT
 EITHER SIDE OF STAIRS COL. LINE N.05,
 BETWEEN UNITS NLT103 & NLT104. INDICATE
 WHICH RISERS THESE W/M'S CONNECT TO.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 43. SHT P-17 MAXIMUM 6' FROM POINT OF
 VENT TO TUB TRAP. (NEAR RISER 95) TABLE
 906.1. (NO RESPONSE, NOT ADDRESSED).
 44. SHT P-17 THE FOLLOWING RISERS DO NOT
 REFLECT PIPING LAYOUT: 50, 51, 52, & 55.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 46. SHT P-18 RISER 102 INDICATES 3"V DN
 TO RISER #3W. THIS IS NOT SHOWN ON SHT
 P-17 NOR ON RISER 102. PLEASE CLARIFY.
 SECTION 104.2.1. - WHAT IS RISER #3W?
 WHERE IS IT LOCATED? SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 48. SHT P-22 CONDENSATE LINE SHOWN AS 5'
 SEPARATION BETWEEN SUPPORTS. INDICATE
 TYPE OF MATERIAL. IF PVC PER TABLE 305.5
 MAXIMUM 4' SEPARATION BETWEEN SUPPORTS.
 SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW
 THEY ARE ATTACHED TO THE ROOF AND SHOW
 COMPLIANCE WITH 140 MPH WIND LOAD. (NO
 RESPONSE, NOT ADDRESSED).
 49. SHT P-23 BATHROOM MAIN LOBBY LEVEL 1
 SHOWN 36FU, BUT IS SHOWN AS 34FU ON SHT
 P-2. CORRELATE PLANS. SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 50. SHT P-23 RECREATION AT LEVEL 4
 PIPING DOES NOT REFLECT THE FIXTURE
 LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT
 WITH PIPING LAYOUT. SECTION 104.2.1.
 (RISER DIAGRAM DOES NOT REFLECT FIXTURE
 LAYOUT EITHER).(W/C MISSING ON RISER
 DIAGRAM).
 51. SHT P-23 RECREATION AT LEVEL 2
 INDICATES 40FU FOR FUTURE GYM, BUT ONLY
 44FU AFTER ADDING MEN'S & WOMEN'S TOILET
 ROOMS. PLEASE RECALCULATE FU'S. (ALSO
 ADJUST ON RISER DIAGRAM). SECTION
 104.2.1. (CHECK ADDIDION, NOW READS
 94FU).
 52. SHT P-23 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-68". P-68 SHOWS STORM RISER
 ONLY. PLEASE CLARIFY. SECTION 104.2.1.
 (ONE STILL READS P-68).
 53. SHT P-39 FLOOR DRAIN NOT SHOWN
 BETWEEN 1ST & 2ND WLI UNITS FIRST FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1. (ALSO
 NEW PIPING DOES NOT REFLECT PIPING SHOWN
 ON SHT P-1. - UNITS AR REFERRED TO AS
 UNITS LW101, THRU LW105 ON SHT P-1, BUT
 AS UNITS WL1 & WL2 ON SHT P-39. PLEASE
 CLARIFY AND CORRELATE UNIT DESIGNATIONS
 BETWEEN SHEETS. - INDICATE LOCATION OF
 RISER DIAGRAM. P-67 STATES "SEE P-53",
 BUT RISERS ARE NOT LOCATED ON SHT P-53).
 54. SHT P-52 SANT. RISER DIAGRAM UNIT
 TOWNHOME, MAXIMUM 4FU ON 2" WET VENT PER
 TABLE 909.3. (NO RESPONSE, NOT
 ADDRESSED).
 55. SHT P-52 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-69". CONT. NOT FOUND ON
 P-69. PLEASE CLARIFY. SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 56. SHT P-53 RISER 13 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - DRY HORIZONTAL VENTS NOT APPROVED 17TH
 FLOOR. SECTIONS 905.3/905.4. (NO
 RESPONSE, NOT ADDRESSED).
 57. SHT P-53 RISER 8 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 58. SHT P-54 RISER 10 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - HORIZONTAL
 BRANCH CONNECTIONS NOT APPROVED ON THE
 HORIZONTAL OFFSET. SECTION 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 59. SHT P-54 RISER 12 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - 4" VENT TO RISER #6 READS "FROM RISER
 6. PLEASE CORRELATE RISERS. SECTION
 104.2.1.(CHANGED FROM RISER #8 TO RISER
 #6). (NO RESPONSE, NOT ADDRESSED).
 60. SHT P-54 RISER 14 LOWER OFFSET VENT
 REQUIRED. SEC. 915.3 - MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 62. SHT P-55 RISER 20 BATHROOM SHOWN ON
 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON
 5TH FLOOR ON RISER. CORRELATE RISER AND
 FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH
 FLOOR NOT SHOWN ON RISER. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 63. SHT P-55 RISER 22 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 64. SHT P-55 RISER 23 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 LOWER OFFSET VENT REQD. SEC. 915.3. (NO
 RESPONSE, NOT ADDRESSED).
 65. SHT P-56 RISER 25 SINK MISSING 17TH
 FLOOR. SEC. 402.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 66. SHT P-56 RISER 26 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO BRANCH CONNECTIONS ON HORIZONTAL
 OFFSET. SEC. 711.2. (NO RESPONSE, NOT
 ADDRESSED).
 67. SHT P-56 RISER 28 NO HORIZONTAL DRY
 VENTS. SEC. 905.3/905.4 (16TH FLOOR)
 68. SHT P-56 RISER 29 LOWER OFFSET VENT
 REQD. SEC 915.3. - NO CONNECTION TO
 HORIZONTAL OFFSET. SEC. 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 69. SHT P-56 RISER 30 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. (NO RESP0NSE, NOT
 ADDRESSED).
 70. SHT P-56 RISER 32 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. - UPPER OFFSET VENT REQD.
 SEC. 915.2. - SEPARATE RISER SECTION AT
 BASE OF STACK FOR POWDER ROOM, INDICATE
 RISERS CONNECTING FROM UPSTREAM. (33,
 37, 37A) SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 71. SHT P-56 RISER 33 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENT. SEC. 905.3/905.4
 - DOES NOT REFLECT FLOOR PLAN @ 4TH
 LEVEL. (BASE OF STACK) SEC. 104.2.1. -
 VENT FROM 1ST FLOOR FLOOR DRAIN NOT
 SHOWN ON RISER. (SEE P-3, P-4, P-67).
 (NO RESPONSE, NOT ADDRESSED).
 72. SHT P-57. RISERS 39, 40,41, 42, 43,
 44 DO NOT REFLECT THE FLOOR PLANS AT THE
 BASE OF RISER. SEC. 1-4.2.1. (NO
 RESPONSE, NOT ADDRESSED).
 73. SHT P-57 RISER 42 VENT FROM FIRST
 FLOOR FLOOR DRAINS NOT SHOWN. PLEASE
 CLARIFY. SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 74. SHT P-58 RISERS 45, 46, 47 DO NOT
 REFLECT FLOOR PLANS FOR 4TH LEVEL.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 75. SHT P-59 RISER 50 DOES NOT REFLECT
 THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 76. SHT P-59 RISER 51 DOES NOT REFLECT
 THE FLOOR PLAN AT BASE OF RISER AND ON
 THE 4TH LEVEL. PLEASE CLARIFY SEC.
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 77. SHT P-59 RISER 52 DOES NOT REFLECT
 FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT
 REQUIRED. SEC. 915.2. (NO RESPONSE, NOT
 ADDRESSED).
 78. SHT P-59 RISERS 53, 55 DO NOT
 REFLECT THE FLOOR PLAN 4TH LEVEL.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 79. SHT P-60 RISER 56 DOES NOT REFLECT
 THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS
 REQD. SECS. 915.2/915.3. - MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. - NO CONNECTIONS TO HORIZONTAL
 OFFSET. SEC. 711.2.- NO HORIZONTAL DRY
 VENTS. SECS. 905.3/905.4. (NO RESPONSE,
 NOT ADDRESSED).
 80. SHT P-60 RISER 58 DOES NOT REFLECT
 THE FLOOR PLAN, CHECK LOCATION OF
 CONNECTION OF RISER 59. - RISER 58 & 61
 NOT TIED TOGETHER ON FLOOR PLAN. - UPPER
 OFFSET VENT REQD. 915.2. (NO RESPONSE,
 NOT ADDRESSED).
 81. SHT P-60 RISER 61 DOES NOT REFLECT
 THE FLOOR PLAN LEVEL 17. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 82. SHT P-60 RISER 57 DOES NOT REFLECT
 THE FLOOR PLAN UPPER LEVEL. - MAX 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 83. SHT P-60 RISER 60 DOES NOT REFLECT
 THE FLOOR PLAN. SHOWS CONNECTING TO
 HORIZONTAL DRAIN LINE. (GROUND FLOOR?) -
 UPPER OFFSET VENT REQD. SEC. 915.2. -
 DOES NOT REFLECT THE FLOOR PLAN AT THE
 TOP OF THE RISER. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 84. SHT P-61 RISER 62 DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 85. SHT P-61 RISERS 63, 64 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CLARIFY
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 86. SHT P-61 RISER 67 MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 87. SHT P-61 RISER 67A DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 89. SHT P-62 RISER 70 LOWER OFFSET VENT
 REQD. SEC 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 90. SHT P-62 RISER 71 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO DRY HORIZONTAL VENT. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 91. SHT P-62 RISER 72 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 3.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 92. SHT P-62 RISER 73 & 74 MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 94. SHT P-62 RISER 79 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 4.
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 95. SHT P-63 RISERS 75,76,77,78,87,88
 DO NOT REFLECT THE FLOOR PLAN PIPING
 LAYOUTS LEVEL 4. SECTION 104.2.1. (NO
 RESPONSE, NOT ADDRESSED).
 96. SHT P-63 RISER 80 FLOOR DRAIN LEVEL
 16 ROOF NOT SHOWN ON RISER DIAGRAM.
 SECTION 104.2.1. CORRELATE RISER/FLOOR
 PLAN. (NO RESPONSE, NOT ADDRESSED).
 97. SHT P-63 RISERS 89,94,95,99,101,102
 & 103 DO NOT REFLECT THE FLOOR PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 98. SHT P-67 HORIZONTAL SANT. RISER
 DIAGRAM MISLABELED AS "WATER RISER
 DIAGRAM". PLEASE CLARIFY. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 99. SHT P-67 FOLLOWING ARE CORRECTIONS
 TO BE MADE TO SANT. RISER DIAGRAM: -
 RISERS 35 & 36 NOT SHOWN. - PIPING
 LAYOUT DOWNSTREAM OF RISER 33,37,37 DOES
 NOT REFLECT FLOOR PLAN FOR POWDER ROOM.
 - RISERS 23 & 23A MISLABELED. - PIPING
 BETWEEN RISERS 6,10,11,12,15 & RISER
 9,13 DOES NOT SHOW POWDER ROOM OR WASH
 MACHINE. - OFFSETS & PIPING LAYOUT SHOWN
 ON SHT P-9 ARE NOT SHOWN ON RISER
 DIAGRAM. - NO VENT SHOWN FOR GREASE
 LINE. - GREASE LINE DOES NOT REFLECT THE
 FLOOR PLAN, AND IS NOT SHOWN ON FLOOR
 PLANS P-15 THRU P-18. -4"-34FU FOR CONT.
 SEE P-23 SHOWS 36FU ON SHT P-23.
 CORRELATE SHEETS. - 2" VENT FROM 2 SINKS
 SHOWS 3" VENT ON SHTS P-3, P-4, & P-5.
 CORRELATE SHEETS. (VENTS NOW NOT FOUND
 ON SHEET). - 2" VENT UP TO RISER
 67 TO READ "TO RISER 67A". (SEE RISER
 67A). - "2" VENT FOR CONT. SEE P-53"
 INDICATE RISER VENT WILL CONNECT TO. -
 "UNITS WL1, WL2 & UNITS 1T THRU 10T,
 4"-28FU FOR CONT. SEE P-53. NOT FOUND ON
 SHT P-53. PLEASE CLARIFY - 6" LINE FROM
 RISER 92,93,94,95,96,97,98, 99,100 DOES
 NOT SHOW OFFSET ON RISER SHOWN ON SHT
 P-15. - THIS SHEET SHOWS LEVELS AS PARK,
 PARK 2, PARK 3 ECT., BUT SHEETS P-15,
 P-16. & P-17 SHOWS LEVELS AS GROUND
 FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS
 MEZZ. ECT. PLEASE CLARIFY & CORRELATE
 SHEET LEVELS. - RECHECK ADDITION OF
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SOME FIXTURES UNITS ARE NOT
 SHOWN AND ADDED TO THE SYSTEM. INDICATE
 THE SLOPE OF THE PIPE WHERE THE FIXTURES
 UNITS ARE MORE THAN ALLOWED FOR MINIMUM
 SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE
 INSTALLED IN A UNIFORM SLOPE AS REQUIRED
 IN SECTION 704.1. INDICATE ON PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 100. SHT P-68 HORIZONTAL STORM RISER
 DOES NOT REFLECT STORM PIPING IN
 BUILDING. STRUCTURES S1 THRU S9 NOT
 SHOWN. - NO ROOF DRAINS 2650SF, 2350SF,
 2450SF ECT. FOUND. - NO EXFILTRATION
 TRENCHES FOUND. - NO TRENCH DRAINS
 FOUND, RISERS SHOWS 25TH, 26TH, 27TH
 FLOORS ECT. - NO POINT OF REFERENCE TO
 FLOOR PLAN CAN BE FOUND. - RISER HARD TO
 READ, PLEASE INCREASE THE SIZE OF THE
 STORM RISER DIAGRAM AND POSSIBLY SPLIT
 UP TO TWO PAGES TO MAKE RISER EASIER TO
 READ. SECTION 104.2.1.3. (NO RESPONSE,
 NOT ADDRESSED).
 101. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES AND INDICATE
 MATERIAL. SECTION 104.3.1.1. (PIPING
 MATERIAL NOT INDICATED)
 102. SUBMIT A P/T VALVE DISCHARGE RISER
 DIAGRAM SHOWING ALL PIPE SIZES AND
 INDICATE PIPING/FITTING MATERIAL.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 103. SUBMIT AN EMERGENCY PAN DRAIN RISER
 DIAGRAM FOR THE WATER HEATERS. INDICATE
 PIPE SIZES AND MATERIAL FOR PIPE AND
 FITTINGS. (NO RESPONSE, NOT ADDRESSED).
 104. BACKFLOW PROTECTION REQUIRED FOR
 IRRIGATION, POOLS, TRASH CHUTE WASH
 DOWN, AND COOLING TOWER MAKE UP WATER.
 SECTION 608. INDICATE METHOD OF
 PROTECTION FOR EACH SYSTEM. (NO
 RESPONSE, NOT ADDRESSED).
 105. PLANS ARE INCOMPLETE AT THIS TIME
 AND MORE COMMENTS MAY BE FORTHCOMING
 WITH THE NEXT REVIEW.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 (NO RESPONSE)
 ****************************************
 ****************************************
  
 NEW COMMENTS:
  
 1B. SHT P-1, THE GAS RISER DIAGRM SHOWS
 THE POOL HEATERS ADD UP TO 2400 BTU, BUT
 NOTE INDICATING "GAS RISER DIAGRAM" ONLY
 SHOWS 2200 BTU. PLEASE CORRELATE RISER &
 NOTE. SECTION 104.2.1.
 2B. SHOW PIPING FOR FIXTURES IN THE
 SHEET WITH FIXTURES, NOT ON THE FLOOR
 BELOW. THIS IS CONFUSING AND IS HARD TO
 FOLLOW THE PIPING, FIXTURES, AND RISER
 DIAGRAM ISOMETRICS. SECTION 104.2.1.
 3B. BUILDING PLANS SHALL BE DRAWN TO
 MINIMUM OF 1/8" SCALE. SECTION
 104.2.1.3. ( SEE SHEETS P-2 THRU P-6.
 PLEASE SUBMIT 1/8" SCALE FOR THESE
 SHEETS FOR REVIEW).
 4B. RESUBMIT ALL PLUMBING SHEETS MARKED
 UP FROM THE FIRST REVIEW TO AID IN
 SPEEDING UP THE REVIEW PROCESS.
 5B. SHT P-1A LOCATED BETWEEN P-19 &
 P-20. INDEX CALLS FOR IT TO BE PRIOR TO
 SHT P-1. PLEASE CORRELATE SHEETS &
 INDEX. SHT 104.2.1.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]