Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-12-16 00:00:001. MORE DETAILS REQUIRED ON THE ATRIUM.
 THIS WOULD INCLUDE FIRE SEPERATIONS,
 DEFINED AREAS, EXITING, AND MECHANICAL
 SYSTEMS. VOLUME CALCULATIONS NEEDED.
  
 2. DOOR MARKS MISSING FROM LEVEL THREE,
 PAGE A1.04C.
  
 3. ELEVATOR SHAFTS (TOPS) ON LSO.10 DO
 NOT DISPLAY ANY FIRE RATING.
  
 4. EXIT SIGNS APPEAR TO BE MISSING ON
 PAGE LSO.05A.
  
 5. AN ENGINEERING ANALYSIS WILL BE
 REQUIRED FOR THE NEW ATRIUM.
  
 6. SITE PLAN PAGE A0.03 ONLY DISPLAYS
 THREE FIRE HYDRANTS. THIS IS NOT
 SUFFICIENT FOR THE SIZE AND COMPLEXITY
 OF THIS PROJECT.
  
 7. TWO SIDE SWINGING DOORS LOCATED ON
 PAGE A1.02C APPEAR TO BE DIRECTLY NEXT
 TO CURBING.
  
 8. PLEASE HATCH AREA OF ATRIUM.
  
 9. PLEASE EXPLAIN BUS DUCT STORAGE ROOM
 DOORS. THEY APPEAR TO OPEN TOO FAR INTO
 EXIT CORRIDOR.
  
 10. PLEASE VERIFY ATRIUM SMOKE SYSTEM
 FANS, CFM'S, ETC. THERE APPEARS TO BE
 SOME DISCREPANCY WITH INFORMATION.
  
 11. COLUMN WAS OBSERVED DIRECTLY INFRONT
 OF DOOR LEADING INTO CORRIDOR FOR HEALTH
 CLUB, C-101.
  
 12. PLEASE DISPLAY EXIT ROUTES FROM
 STORAGE 00.
  
 13. PARKING CARS, COLUMN, AND SHEER WALL
 OBSERVED.
  
 14. PLEASE EXPLAIN MEZZANINE. PLEASE
 PROVIDE PRESCRIPTIVE REQUIREMENTS
 REGARDING MEZZANINE.
  
 15. PLEASE PROVIDE DETAILS ON GLASS WALL
 SYSTEM AROUND MONUMENTAL STAIR.
  
 16. POOL EQUIPMENT ROOM 00 WILL BE
 CONSIDERED HAZARDOUS UNTIL SUFFICIENT
 INFORMATION IS PROVIDED.
  
 17. JANITOR CLOSET AND CLOSET DOOR NEAR
 KICHEN C0405 OPPOSE ONE ANOTHER.
  
 18. PLEASE IDENTIFY SMALL AREA WITH DOOR
 NEAR TOWER 7 ELEVATOR LOBBY.
  
 19. WHAT INTERPRETATION IS BEING USED
 FOR DOORS OPENING ONTO EXIT ACCESS
 CORRIDORS. PLEASE SEE TELLCOM CLOSETS.
  
 20. ALL NEW ELEVATORS SHALL COMPLY WITH
 ASME A17.1 SAFETY CODE FOR ELEVATORS AND
 ESCALATORS.
  
 21. EGRESS SIGN MISSING NEAR STAIR
 LOCATED AT G25 LOCATION ON PAGE
 A1.05S-2.
  
 22. MORE DETAILS NEEDED FOR THE TWO HOUR
 RATED SLIDING DOORS SHOWN IN FRONT OF
 ELEVATORS. HOW WOULD FIRE RESCUE ACCESS
 BEYOND THESE DOORS.
  
 23. ON ELEVATION DRAWINGS A REVISION IS
 SHOWN FOR ITEM # 4 HOWEVER ON PAGE
 A2.02-N ITEM # 7 IS DEPICTED.
  
 24. WILL ANY COMBUSTIBLE MATERIALS BE
 STORED OR HANDELED UNDERNEATH THE PORTE
 COCHERE.
  
 25. PLEASE ILLUSTRATE DISTANCES OF FIXED
 GLASS ANGLED WINDOWS FOR THE ATRIUM
 ENCLOSURE TO TOWER WINDOWS. IT IS
 DIFFICULT TO DETERMINE. PLEASE SEE PAGE
 A3.05-A.
  
 26. WHAT FIRE PROTECTION IS PLANNED FOR
 THE CABANA'S.
  
 27. DUCTS OVER FOUR FEET WIDE SHALL HAVE
 FIRE SPRINKLER PROTECTION BELOW THEM.
  
 28. UNIT DOOR AND HARDWARE SCHEDULE DOES
 NOT ILLUSTRATE THAT THE GALLERY DOOR TO
 THE STAIRWELL IS FIRE RATED. PLEASE
 EXPLAIN RATIONALE. PLEASE SEE PAGE
 A4.02.
  
 29. NO FIRE RATING NOTED ON UNIT DOOR
 AND HARDWARE SCHEDULE LOCATED ON PAGE
 A4.08.
  
 30. SAME CONDITION EXISTS ON PAGES
 A4.09-20.
  
 31. PRESSURE REGULATING VALVES SHOWN ON
 PAGE SP-34. WILL THESE DEVICES BE
 FACTORY SET OR FIELD SET. FACTORY SET
 ONES ARE PREFERRED.
  
 32. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUM.
  
 33. PLEASE ILLUSTRATE EMERGENCY LIGHTING
 ON RECREATIONAL PLAZA.
  
 34. SINCE EXITING IS DIRECTED FROM THE
 GARAGE TOWARDS THE FUTURE TENANT
 BUILD-OUT AREA ON LEVEL ON PAGE E-03,
 PLEASE EXPLAIN HOW THIS WILL WORK.
  
 35. SEQUENCE OF OPERATIONS PAGE AC-38
 NEEDS TO BE REVISED. DUCT SMOKE
 DETECTORS SHALL INITIATE AN ALARM NOT A
 SUPERVISORY SIGNAL.
  
 36. ELECTRONIC SWITCHES, CHAINS AND
 LOCKS ARE REQUIRED ON THE FIRE LINE
 BACKFLOW DEVICE.
  
 37. ANY SECURITY DEVICES PLANNED SHALL
 NOT INTERFERE WITH ANY REQUIRED EXITING
 FROM THE BUILDING. PLEASE REVIEW SPECIAL
 LOCKING ARRANGEMENTS IN THE LIFE SAFETY
 CODE, 2003 EDITION.
  
 38. PLEASE PROVIDE CODE REQUIREMENTS FOR
 SECURITY DEVICES ON THE APPROPRIATE
 PAGES.
  
 39. PLEASE EXPLAIN ELEVATOR CONTROL
 PROGRAMMING. ARE THERE GOING TO BE ANY
 SPECIAL FEATURES REGARDING THE
 ELEVATORS.
  
 40. PLEASE PROVIDE FLAME SPREAD FOR CORK
 WALLCOVERINGS AND FLOOR, PAGE ID3.04.
  
 41. ADDITIONAL FIRE EXTINGUISHERS APPEAR
 TO BE REQUIRED. LARGE MECHANICAL AND
 SERVICE ROOMS APPEAR TO BE ABSENT OF
 THEM. NO FIRE EXTINGUISHERS APPEAR TO BE
 SHOWN ON THE OVERALL ROOF PLAN LS0.10.
  
 42. COULD NOT LOCATE FIRE EXTINGUISHERS
 LOCATIONS FOR LONG CORRIDORS SHOWN ON
 PAGE LSO.06.
  
 43. STAIR # 8B DISPLAYS 200 BUT IF THE
 DOOR CAN ONLY ACCOMODATE 140 PERSONS HOW
 DOES THIS WORK.
  
 44. STAIRS 10,11,12,AND 13 SHOW LARGE
 OCCUPANT LOADS BUT DOORS CAN ONLY
 SUPPORT 140 PERSONS. HOW DOES THIS WORK.
  
 45. WINDOWS APPEAR TO BE LOCATED
 DIRECTLY OPPOSITE OF EXIT STAIR DOORS ON
 THE RECREATIONAL DECK. WHAT PROTECTION
 IF ANY IS PLANNED.
  
 46.STAIR PRESSURIZATION NOTES NEED TO BE
 INCORPORATED ONTO THE LIFE SAFETY PLANS.
 PLEASE PROVIDE PRESCRIPTIVE
 REQUIREMENTS.
  
 47. THE STORE THAT IS PLANNED A SEPERATE
 TENANT OR WILL BE ANCILLARY TO THE REST
 OF THE BUILDING.
  
 48. ALL DOORS FOR EXIT ACCESS CORRIDORS
 SHALL BE SELF-CLOSING AND SELF-LATCHING.
  
 49. LISTED GUICK RESPONSE OR LISTED
 RESIDENTIAL FIRE SPRINKLERS SHALL BE
 USED IN LIVING AREAS.
  
 50. PLEASE REVIEW ALL EXIT ACCESS,
 EXITING, AND EXIT DISCHARGE CALCULATIONS
 TO ENSURE THEY ARE PROPERLY CALCULATED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709