2005-12-16 00:00:00 | 1. MORE DETAILS REQUIRED ON THE ATRIUM. |
| THIS WOULD INCLUDE FIRE SEPERATIONS, |
| DEFINED AREAS, EXITING, AND MECHANICAL |
| SYSTEMS. VOLUME CALCULATIONS NEEDED. |
| |
| 2. DOOR MARKS MISSING FROM LEVEL THREE, |
| PAGE A1.04C. |
| |
| 3. ELEVATOR SHAFTS (TOPS) ON LSO.10 DO |
| NOT DISPLAY ANY FIRE RATING. |
| |
| 4. EXIT SIGNS APPEAR TO BE MISSING ON |
| PAGE LSO.05A. |
| |
| 5. AN ENGINEERING ANALYSIS WILL BE |
| REQUIRED FOR THE NEW ATRIUM. |
| |
| 6. SITE PLAN PAGE A0.03 ONLY DISPLAYS |
| THREE FIRE HYDRANTS. THIS IS NOT |
| SUFFICIENT FOR THE SIZE AND COMPLEXITY |
| OF THIS PROJECT. |
| |
| 7. TWO SIDE SWINGING DOORS LOCATED ON |
| PAGE A1.02C APPEAR TO BE DIRECTLY NEXT |
| TO CURBING. |
| |
| 8. PLEASE HATCH AREA OF ATRIUM. |
| |
| 9. PLEASE EXPLAIN BUS DUCT STORAGE ROOM |
| DOORS. THEY APPEAR TO OPEN TOO FAR INTO |
| EXIT CORRIDOR. |
| |
| 10. PLEASE VERIFY ATRIUM SMOKE SYSTEM |
| FANS, CFM'S, ETC. THERE APPEARS TO BE |
| SOME DISCREPANCY WITH INFORMATION. |
| |
| 11. COLUMN WAS OBSERVED DIRECTLY INFRONT |
| OF DOOR LEADING INTO CORRIDOR FOR HEALTH |
| CLUB, C-101. |
| |
| 12. PLEASE DISPLAY EXIT ROUTES FROM |
| STORAGE 00. |
| |
| 13. PARKING CARS, COLUMN, AND SHEER WALL |
| OBSERVED. |
| |
| 14. PLEASE EXPLAIN MEZZANINE. PLEASE |
| PROVIDE PRESCRIPTIVE REQUIREMENTS |
| REGARDING MEZZANINE. |
| |
| 15. PLEASE PROVIDE DETAILS ON GLASS WALL |
| SYSTEM AROUND MONUMENTAL STAIR. |
| |
| 16. POOL EQUIPMENT ROOM 00 WILL BE |
| CONSIDERED HAZARDOUS UNTIL SUFFICIENT |
| INFORMATION IS PROVIDED. |
| |
| 17. JANITOR CLOSET AND CLOSET DOOR NEAR |
| KICHEN C0405 OPPOSE ONE ANOTHER. |
| |
| 18. PLEASE IDENTIFY SMALL AREA WITH DOOR |
| NEAR TOWER 7 ELEVATOR LOBBY. |
| |
| 19. WHAT INTERPRETATION IS BEING USED |
| FOR DOORS OPENING ONTO EXIT ACCESS |
| CORRIDORS. PLEASE SEE TELLCOM CLOSETS. |
| |
| 20. ALL NEW ELEVATORS SHALL COMPLY WITH |
| ASME A17.1 SAFETY CODE FOR ELEVATORS AND |
| ESCALATORS. |
| |
| 21. EGRESS SIGN MISSING NEAR STAIR |
| LOCATED AT G25 LOCATION ON PAGE |
| A1.05S-2. |
| |
| 22. MORE DETAILS NEEDED FOR THE TWO HOUR |
| RATED SLIDING DOORS SHOWN IN FRONT OF |
| ELEVATORS. HOW WOULD FIRE RESCUE ACCESS |
| BEYOND THESE DOORS. |
| |
| 23. ON ELEVATION DRAWINGS A REVISION IS |
| SHOWN FOR ITEM # 4 HOWEVER ON PAGE |
| A2.02-N ITEM # 7 IS DEPICTED. |
| |
| 24. WILL ANY COMBUSTIBLE MATERIALS BE |
| STORED OR HANDELED UNDERNEATH THE PORTE |
| COCHERE. |
| |
| 25. PLEASE ILLUSTRATE DISTANCES OF FIXED |
| GLASS ANGLED WINDOWS FOR THE ATRIUM |
| ENCLOSURE TO TOWER WINDOWS. IT IS |
| DIFFICULT TO DETERMINE. PLEASE SEE PAGE |
| A3.05-A. |
| |
| 26. WHAT FIRE PROTECTION IS PLANNED FOR |
| THE CABANA'S. |
| |
| 27. DUCTS OVER FOUR FEET WIDE SHALL HAVE |
| FIRE SPRINKLER PROTECTION BELOW THEM. |
| |
| 28. UNIT DOOR AND HARDWARE SCHEDULE DOES |
| NOT ILLUSTRATE THAT THE GALLERY DOOR TO |
| THE STAIRWELL IS FIRE RATED. PLEASE |
| EXPLAIN RATIONALE. PLEASE SEE PAGE |
| A4.02. |
| |
| 29. NO FIRE RATING NOTED ON UNIT DOOR |
| AND HARDWARE SCHEDULE LOCATED ON PAGE |
| A4.08. |
| |
| 30. SAME CONDITION EXISTS ON PAGES |
| A4.09-20. |
| |
| 31. PRESSURE REGULATING VALVES SHOWN ON |
| PAGE SP-34. WILL THESE DEVICES BE |
| FACTORY SET OR FIELD SET. FACTORY SET |
| ONES ARE PREFERRED. |
| |
| 32. NO COMBUSTIBLES ALLOWED IN ANY |
| RETURN AIR PLENUM. |
| |
| 33. PLEASE ILLUSTRATE EMERGENCY LIGHTING |
| ON RECREATIONAL PLAZA. |
| |
| 34. SINCE EXITING IS DIRECTED FROM THE |
| GARAGE TOWARDS THE FUTURE TENANT |
| BUILD-OUT AREA ON LEVEL ON PAGE E-03, |
| PLEASE EXPLAIN HOW THIS WILL WORK. |
| |
| 35. SEQUENCE OF OPERATIONS PAGE AC-38 |
| NEEDS TO BE REVISED. DUCT SMOKE |
| DETECTORS SHALL INITIATE AN ALARM NOT A |
| SUPERVISORY SIGNAL. |
| |
| 36. ELECTRONIC SWITCHES, CHAINS AND |
| LOCKS ARE REQUIRED ON THE FIRE LINE |
| BACKFLOW DEVICE. |
| |
| 37. ANY SECURITY DEVICES PLANNED SHALL |
| NOT INTERFERE WITH ANY REQUIRED EXITING |
| FROM THE BUILDING. PLEASE REVIEW SPECIAL |
| LOCKING ARRANGEMENTS IN THE LIFE SAFETY |
| CODE, 2003 EDITION. |
| |
| 38. PLEASE PROVIDE CODE REQUIREMENTS FOR |
| SECURITY DEVICES ON THE APPROPRIATE |
| PAGES. |
| |
| 39. PLEASE EXPLAIN ELEVATOR CONTROL |
| PROGRAMMING. ARE THERE GOING TO BE ANY |
| SPECIAL FEATURES REGARDING THE |
| ELEVATORS. |
| |
| 40. PLEASE PROVIDE FLAME SPREAD FOR CORK |
| WALLCOVERINGS AND FLOOR, PAGE ID3.04. |
| |
| 41. ADDITIONAL FIRE EXTINGUISHERS APPEAR |
| TO BE REQUIRED. LARGE MECHANICAL AND |
| SERVICE ROOMS APPEAR TO BE ABSENT OF |
| THEM. NO FIRE EXTINGUISHERS APPEAR TO BE |
| SHOWN ON THE OVERALL ROOF PLAN LS0.10. |
| |
| 42. COULD NOT LOCATE FIRE EXTINGUISHERS |
| LOCATIONS FOR LONG CORRIDORS SHOWN ON |
| PAGE LSO.06. |
| |
| 43. STAIR # 8B DISPLAYS 200 BUT IF THE |
| DOOR CAN ONLY ACCOMODATE 140 PERSONS HOW |
| DOES THIS WORK. |
| |
| 44. STAIRS 10,11,12,AND 13 SHOW LARGE |
| OCCUPANT LOADS BUT DOORS CAN ONLY |
| SUPPORT 140 PERSONS. HOW DOES THIS WORK. |
| |
| 45. WINDOWS APPEAR TO BE LOCATED |
| DIRECTLY OPPOSITE OF EXIT STAIR DOORS ON |
| THE RECREATIONAL DECK. WHAT PROTECTION |
| IF ANY IS PLANNED. |
| |
| 46.STAIR PRESSURIZATION NOTES NEED TO BE |
| INCORPORATED ONTO THE LIFE SAFETY PLANS. |
| PLEASE PROVIDE PRESCRIPTIVE |
| REQUIREMENTS. |
| |
| 47. THE STORE THAT IS PLANNED A SEPERATE |
| TENANT OR WILL BE ANCILLARY TO THE REST |
| OF THE BUILDING. |
| |
| 48. ALL DOORS FOR EXIT ACCESS CORRIDORS |
| SHALL BE SELF-CLOSING AND SELF-LATCHING. |
| |
| 49. LISTED GUICK RESPONSE OR LISTED |
| RESIDENTIAL FIRE SPRINKLERS SHALL BE |
| USED IN LIVING AREAS. |
| |
| 50. PLEASE REVIEW ALL EXIT ACCESS, |
| EXITING, AND EXIT DISCHARGE CALCULATIONS |
| TO ENSURE THEY ARE PROPERLY CALCULATED. |
| |
| MIKE CARSILLO, CHIEF FIRE PREVENTION |
| OFFICER |
| 804-4709 |