2005-12-31 00:00:00 | IN ELEC FOR REVIEW, IN PROGRESS |
| *********** UNSAT 2ND REVIEW ********** |
| |
| PALLADIO |
| 2211 N. FLAGLER DR. |
| PLANS CONVERTED BACK TO PERMIT> THIS IS |
| TECHNICALLY THE 2ND REVIEW, HOWEEVR |
| FIRST REVIEW WAS UNDER "PROJECT"/PLAN |
| REVIEW. |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW AND SOME NEW NOTES DUE TO NEW |
| INFORMATION, CHANGES, CODES. |
| |
| 1)NOTE: NOTE#1 NO. COULD NOT LOCATE |
| SPECS AS REQUESTED. |
| PLEASE SUBMIT ALL MANUFACTURE |
| SPECIFICATION SHEETS/ CUT SHEETS FOR |
| FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, |
| GENERATOR, AUTOMATIC TRANSFER SWITCH |
| (ATS) AND ANY SUB BASE FUEL TANKS. |
| PLEASE SURE ALL INFORMATION SUBMITTED |
| MUST SHOW LISTINGS FROM A NATIONALLY |
| RECOGNIZED TESTING LAB. (NRTL). |
| PLEASE BE SURE ALL FIRE PUMP CONTROLLERS |
| ETC COMPLY WITH NFPA-20 AND OTHER |
| APPLICABLE CODES. |
| |
| 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE |
| NOTES PERTAINING TO SPECS SUBMITTED. |
| PLEASE SEE 16450.1 WHICH REFERENCES |
| CODES FROM THE 1996 NEC. |
| PLEASE SEE COLOR CODING FOR 277/480V |
| SYSTEMS SHALL BE BROWN/PURPLE/YELLOW. |
| PLEASE SEE 16100-2 |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE: NOTE #4 OK. |
| |
| 5)NOTE: NOTE #5 OK. |
| |
| 6)NOTE: NOTE #6 YES,NO, PLEASE SEE STAIR |
| AND EGRESS TUNNELS ARE OK, HOWEVER |
| PLEASE SEE GARAGE AND OTHER EGRESS PATHS |
| WHICH WILL REQUIRE A MIN OF 1 FT CANDLE. |
| PLEASE ALSO SEE FIRE REVIOEW COMMENTS |
| WITH RESPECT TO EM EGRESS LIGHTING FROM |
| POOL AREA TO PUBLIC RIGHT OF WAY |
| REQUIRED. |
| PLEASE ALSO VERIFY THE LOBBY AREAS BEING |
| USED AS A MEANS OF EGRESS FROM UNITS. |
| 2003 NFPA-101 7.8.1.3, 7.9.2.2 |
| ** PLEASE SEE NEW NOTES PERTAINING TO |
| PHOTO-METRICS. |
| |
| 7)NOTE: NOTE #7 YES,NO, PLEASE SEE MOST |
| WERE ADDED HOWEVER PLEASE SEE E-21 AN |
| ELECTRICAL RM AND THE FIRE COMMAND RM DO |
| NOT INDICATE A CHANGE IN FIXTURE TYPE. |
| 700.16, LS 101 7-9, 90.4 |
| |
| 8)NOTE: NOTE #8OK. |
| |
| 9)NOTE: NOTE #9OK |
| |
| 10)NOTE: NOTE #10, OK. |
| |
| 11)NOTE: NOTE #11 OK |
| |
| 12)NOTE: NOTE #12 OK. |
| |
| 13)NOTE: NOTE #13 OK. |
| |
| 14)NOTE: NOTE #14 OK. |
| |
| 15)NOTE: NOTE #15 OK. |
| |
| 16)NOTE: NOTE #16 OK. |
| |
| 17)NOTE: NOTE #17 OK. |
| |
| 18)NOTE: NOTE #18 NO, PLEASE SEE SOME |
| UNITS MISSING RECEPTS PER 210.52. |
| PLEASE SEEONE REDLINED SET. |
| "L" SOUTH, BED RM #3, "N", BR#3 #4, |
| LOFTS WITH WHAT APPEARS TO BE WALL SPACE |
| BY STAIRS ON LOWER LEVELS/ WITHIN 6' FRO |
| THE EDGE. |
| |
| 19)NOTE: NOTE #19 NO,PLEASE SEE |
| CIRCUITING MISSING FROM SOME DEVICES |
| SHOWN IN SOME OF THE UNITS. PLEASE SEE |
| SD'S, RECEPTS. |
| PLEASE SEE REDLINED PLANS AS MOST ARE |
| CIRCIRLED. |
| |
| 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE |
| SOME AREA DESIGNATIONS ON UNITS ARE NOW |
| SHOWN WHICH DINING AREAS/BREAKFAST AREAS |
| ARE ON 15A #14 GEN LT CIRCUITS. |
| CIR #42 |
| PLEASE SEE UNIT "N", "Q" |
| |
| 21)NOTE: NOTE #21 OK. |
| |
| 22)NOTE: NOTE #22 OK. |
| |
| 23)NOTE: NOTE #23 OK. |
| |
| 24)NOTE: NOTE #24 OK, HOWEVER PLEASE SEE |
| NEW NOTE FOR ONE GFI LOCATION. |
| |
| 25)NOTE: NOTE #25 OK. |
| |
| 26)NOTE: NOTE #26 OK. |
| |
| 27)NOTE: NOTE #27 OK. |
| |
| 28)NOTE: NOTE #28 OK. |
| |
| 29)NOTE: NOTE #29 OK. |
| |
| 30)NOTE: NOTE #30 OK. |
| |
| 31)NOTE: NOTE #31 OK. |
| |
| 32)NOTE: NOTE #32 NO. |
| PLEASE SEE MISSING SMOKE DETECTORS |
| REQUIRED UNDER NFPA-72 11.5.1.1, |
| 11.8.3.5 |
| PLEASE SEE SD'S ARE REQUIRED INSIDE AND |
| OUTSIDE ALL SLEEPING RMS AND ON EACH |
| LEVELOF A MULTY LEVEL DWELLING. |
| PLEASE SEE SOME MISSING, DEN IN UNIT "R" |
| WILL BE REQUIRED TO HAVE A SD AS IT IS |
| SHOWN WITH AN ATTACHED BATH OR CLOSET |
| WHICH MAKES THIS AN ADAPTABLE SLEEPING |
| RM BY AHJ. PLEASE SEE MISSING SD "Q" |
| NORTH,LEADING TO FLR ABOVE. |
| PLEASE SEE SD'S ARE REDLINED AT |
| LOCATIONS REQUIRED IN OTHER UNITS. |
| |
| 33)NOTE: NOTE #33 OK. |
| |
| 34)NOTE: NOTE #34 NO, PLEASE SEE THESE |
| LOBBY AREAS ARE STILL UNCLEAR BY THE |
| BLDG REVIEW COMMENTS IF THEY BELONG TO |
| THE UNIT OR PART OF "HOUSE/COMMON" AREA. |
| PLEASE SEE EXTENSIVE BLDG REVIEW |
| COMMENTS. |
| PLEASE SEE 210.25 WHICH STATES NO COMMON |
| AREAS SHALL CONTAIN ELECTRICAL DEVICES |
| FED FROM UNITS. IF THESE ARE "PRIVATE" |
| LOBBIES,PLEASE SHOW HOW THESE AREAS |
| CONTAIN NUMEROUS ELECTRICAL ITEMS FED |
| FROM HOUSE POWER? |
| PLEASE ALSO SEE NEW EXT LTS ETC ADDED TO |
| UNITS. |
| |
| 35)NOTE: NOOTE #35 OK. |
| |
| 36)NOTE: NOTE #36 OK. |
| |
| 37)NOTE: NOTE #37 NO, PLEASE ADD NOTE TO |
| THE ROOF TOP PLANS. |
| PLEASE SEE ANY PROPOSED LIGHTNING |
| PROTECTION SYSTEM SHALL BE |
| INSTALLED AND ACCEPTABLE PER NFPA-780. |
| ALTHOUGH A LIGHTNING PROTECTION SYSTEM |
| IS NOT SHOWN ON ANY PLANS, PLEASE BE |
| SURE A NOTE IS PLACED ON "ROOF-TOP" |
| SHEET WITH REFERENCE TO NFPA-780. |
| AS NOTED IN MEETING , "LIGHTNING |
| PREVENTION" SYSTEMS ARE NOT PERMITTED OR |
| ACCEPTABLE IN THIS JURISTICTION. |
| |
| 38)NOTE: NOTE #38 OK, HOWEVER SEE ELEC |
| NOTES FOR SERVICE. |
| |
| 39)NOTE: NOTE #39 OK. |
| |
| 40)NOTE: NOTE #40,NO, PLEASE SEE |
| ELECTRICAL SERVICE WAS MOVED AROUND , |
| HOWEVER THE INTENT OF ORIGINAL NOTE HAS |
| NOT BEEN ADDRESSED. PLEASE SEE EM MAIN |
| HAS NOW BEEN MOVED TO MAIN ELECTRICAL |
| RM, WHICH WHEN SHUT OFF WILL TRIGGER THE |
| GEN TO START, TRANSFER POWER OVER TO |
| HXDP, WHICH IS STILL LOCATED IN THE GEN |
| RM. THEMCB ADDED TO THE HXDP WOULD NOT |
| BE READILY ACCESSIBLE, GROUPED OR IN |
| CLOSE PROXIMITY AND OTHER HAZARDS MAY |
| PREVENT THE SHUTTING DOWN OF POWER IN A |
| TIMELY AND SAFE MANOR. |
| THIS LOCATION WITH A 1500KW GENERATOR |
| RUNNING AT FULL NOISE LEVEL, HEAT ETC |
| MAY DISTRACT IN SHUTTING DOWN OF EM |
| POWER IN A SAFE AND TIMELY FASHION. IT |
| IS NOTED THAT THESE MAINS AND GEN WILL |
| HAVE SHUNT TRIPS IN FIRE COMMAND RM, |
| HOWEVER THESE ARE NOT CONSIDERED AS THE |
| MEANS OF DISC. 230.76,230.79 |
| PLEASE SEE IT IS UNCLEAR AT THIS TIME IF |
| BRKR ON GEN IS LOCATED ON THE OUTSIDE OF |
| EQUIPMENT WITH A MANUAL MEANS OF |
| DISCONNECT WITH EXPOSING OF LIVE PARTS. |
| 110.27. |
| PLEASE SEE SOME OF THIS CAN NOT BE |
| VERIFIED AT THIS TIME AS SPECS FOR THIS |
| EQUIPMENT, GENERATOR ETC WAS NOT |
| SUBMITTED. |
| PLEASE SEE ROUTE, LOCATION TRAVEL |
| DISTANCE ETC MAY BE GONE IN A MEETING |
| WHICH MAY BE REQUESTED. |
| |
| 41)NOTE: NOTE #41 OK. |
| |
| 42)NOTE: NOTE #42 OK. |
| |
| 43)NOTE: NOTE #43 OK. |
| |
| 44)NOTE: NOTE #44 OK. |
| |
| 45)NOTE: NOTE #45 OK. |
| |
| 46)NOTE: NOTE #46 OK, HOWEVER NO |
| CONNECTION FOR GEN GROUNDING ELECTRODE |
| SYSTEM WAS SHOWN. ONLY NOTES TO GEN |
| FRAME. PLEASE SEE 250.30, AS THIS GEN IS |
| SEPARATELY DERIVED. |
| |
| 47)NOTE: NOTE #47 OK. |
| |
| 48)NOTE: NOTE #48 OK. |
| |
| 49)NOTE: NOTE #49 OK. |
| |
| 50)NOTE: NOTE #50 OK. |
| |
| 51)NOTE: NOTE #51 OK. |
| |
| 52)NOTE: NOTE #52 OK. |
| |
| 53)NOTE: NOTE #53 OK. |
| |
| 54)NOTE: NOTE #54 OK. |
| |
| 55)NOTE: NOTE #55 OK. |
| |
| 56)NOTE: NOTE #56 OK, HOWEVER SEE NEW |
| NOTE AS PANEL SCHEDULES REVIEWED FOR THE |
| FIRST TIME. |
| |
| 57)NOTE: NOTE #57 OK. |
| |
| 58)NOTE: NOTE #58 OK. |
| |
| 59)NOTE: NOTE #59 OK. |
| |
| 60)NOTE: NOTE #60 OK. |
| |
| 61)NOTE: NOTE #61 |
| |
| 62)NOTE: NOTE #63, NOPLEASE SEE POOL |
| WILL BE REQUIRED TO BE UNDER A SEPARATE |
| PERMIT WHICH IS NOTED ON PLANS. |
| THIS IS OK, HOWEVER PLEASE KNOW, IF |
| THERE IS GOING TO BE ANY AFTER DUSK |
| SWIMMING, THIS WILL HAVE AN IMPACT ON |
| THE MIN LIGHTING LEVELS AND DESIGN FOR |
| POOL DECK/EGRESS LIGHTING. PLEASE SEE |
| OTHER NOTES PERTAINING TO EGRESS.. |
| IF NIGHT-TIME/AFTER DUSK WILL BE |
| PROPOSED, SIGNED, SEALED PHOTOMETRICS |
| WILL BE REQUIRED TO BE SUBMITTED TO PALM |
| BEACH COUNTY HEALTH DEPT FOR REVIEW AND |
| STAMPING. |
| |
| |
| |
| ******* NEW NOTES ************ |
| |
| 1)NOTE: PLEASE CORRELATE CONDUCTORS |
| SHOWN ON HS FOR LS. |
| 215.5 |
| PLEASE ALSO LABEL WHICH TRANSFORMER HS |
| IS FEEDING AS OTHER PANEL SCHEDULES ARE |
| LABELED. |
| |
| 2)NOTE: PLEASE SEE CIRCUITS WHICH |
| REQUIRE ARC FAULT PROTECTION, PLEASE SEE |
| "Q", #32, UNIT "A", #28. |
| |
| 3)NOTE: PLEASE SEE A "MISPRINT" OF AN |
| ADDITIONAL "ELEC PANEL" IN UNIT "B". |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE NOTES WITH RESPECT TO |
| ARC FAULT PROTECTION. NOTE MENTIONS |
| "RECEPT" WHERE-AS ALL OTHER NOTES WERE |
| CHANGED TO "OUTLETS". |
| |
| 5)NOTE: PLEASE SEE BLDG NOTES PERTAINING |
| TO MEZZANINE, AND TOWNHOUSE DESIGNATIONS |
| WHICH ARE ON E-SHEETS AND OTHER |
| LOCATIONS. |
| |
| 6)NOTE: PLEASE PROVIDE THE INFORMATION |
| AS REQUESTED BY FIRE AND BLDG REVIEW |
| PERTAINING TO POOL EQUIPMENT ROOM AND |
| ANY STORAGE OF HAZARDOUS MATERIALS. |
| ADJUST ELECTRICAL AS NEEDED,PLACE NOTE |
| ON PLANS. |
| |
| 7)NOTE: PLEASE PROVIDE A BUS-DUCT CURB |
| DETAIL AS REQUIRED PER 368.6, THIS |
| SHOULD HAVE BEEN REQUESTED ON ORIGINAL |
| REVIEW. |
| |
| 8)NOTE: PLEASE VERIFY NEW NOTE WHICH |
| MENTIONS A FLOOR? MOUNTED GFI IN BATHRM |
| FOR JACUZZI TUB IN UNIT "Q". THIS SHALL |
| NOT BE MOUNTED FACING UP, AND SHOWN BE |
| OFF THE FLOOR/WET AREA LOCATED UNDER TUB |
| ACCESS PANEL. |
| PLEASE SEE MIN CLEARENCES FROM TUBS, |
| 410.8 |
| |
| 9)NOTE: PLEASE KNOW THE FOLLOWING MAY BE |
| SET-UP AS A "PROVISO" OR MAY BE |
| ADDRESSED AT THIS TIME. |
| PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR |
| STAIRS TOWERS, EGRESS TUNNELS, AND ALL |
| OTHER PATHS FOR MEANS OF EGRESS AS |
| PREVIOUSLY NOTED TO PUBLIC RIGHT-OF-WAY. |
| PLEASE SEE 7.8.1.3, WHICH REQUIRES A MIN |
| OF 10FT CANDLES(108 LUX) UNDER NORMAL |
| POWER AT ALL WALKING SURFACES OF |
| STAIRS/STAIRWAYS. |
| PLEASE SEE STAIRS CAN BE REDUCED TO .8 |
| LUX OR 1FT CANDLE UNDER EM POWER/BATTERY |
| BACK UP. |
| PLEASE SEE ALL OTHER AREAS FOR EGRESS |
| MUST HAVE A MIN OF 1 FT CANDLE UNDER |
| NORMAL AND EM POWER ON ALL WALKING |
| SURFACES. |
| |
| |
| ** PLEASE SEE MOST OF THE ABOVE |
| ITEMS ARE REDLINED ON ONE SET OF |
| ELECTRICAL PLANS, HOWEVER THESE DO NOT |
| IDICATE ALL POSSIBLE LOCATIONS OF NEEDED |
| CORRECTIONS. |
| |
| **PLEASE KNOW, SOME ITEMS STILL NEED TO |
| BE VERIFIED ONCE ALL INFORMATION IS |
| SUBMITTED. |
| |
| **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE A |
| DIRECT EFFECT ON ELECTRICAL PLANS. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE AREA ANY QUESTIONS, |
| PLEASE DO NOT HESIATE IN CONTACTING THIS |
| OFFICE. |
| |