Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-31 00:00:00IN ELEC FOR REVIEW, IN PROGRESS
 *********** UNSAT 2ND REVIEW **********
  
 PALLADIO
 2211 N. FLAGLER DR.
 PLANS CONVERTED BACK TO PERMIT> THIS IS
 TECHNICALLY THE 2ND REVIEW, HOWEEVR
 FIRST REVIEW WAS UNDER "PROJECT"/PLAN
 REVIEW.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO NEW
 INFORMATION, CHANGES, CODES.
  
 1)NOTE: NOTE#1 NO. COULD NOT LOCATE
 SPECS AS REQUESTED.
 PLEASE SUBMIT ALL MANUFACTURE
 SPECIFICATION SHEETS/ CUT SHEETS FOR
 FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER,
 GENERATOR, AUTOMATIC TRANSFER SWITCH
 (ATS) AND ANY SUB BASE FUEL TANKS.
 PLEASE SURE ALL INFORMATION SUBMITTED
 MUST SHOW LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LAB. (NRTL).
 PLEASE BE SURE ALL FIRE PUMP CONTROLLERS
 ETC COMPLY WITH NFPA-20 AND OTHER
 APPLICABLE CODES.
  
 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE
 NOTES PERTAINING TO SPECS SUBMITTED.
 PLEASE SEE 16450.1 WHICH REFERENCES
 CODES FROM THE 1996 NEC.
 PLEASE SEE COLOR CODING FOR 277/480V
 SYSTEMS SHALL BE BROWN/PURPLE/YELLOW.
 PLEASE SEE 16100-2
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 YES,NO, PLEASE SEE STAIR
 AND EGRESS TUNNELS ARE OK, HOWEVER
 PLEASE SEE GARAGE AND OTHER EGRESS PATHS
 WHICH WILL REQUIRE A MIN OF 1 FT CANDLE.
 PLEASE ALSO SEE FIRE REVIOEW COMMENTS
 WITH RESPECT TO EM EGRESS LIGHTING FROM
 POOL AREA TO PUBLIC RIGHT OF WAY
 REQUIRED.
 PLEASE ALSO VERIFY THE LOBBY AREAS BEING
 USED AS A MEANS OF EGRESS FROM UNITS.
 2003 NFPA-101 7.8.1.3, 7.9.2.2
 ** PLEASE SEE NEW NOTES PERTAINING TO
 PHOTO-METRICS.
  
 7)NOTE: NOTE #7 YES,NO, PLEASE SEE MOST
 WERE ADDED HOWEVER PLEASE SEE E-21 AN
 ELECTRICAL RM AND THE FIRE COMMAND RM DO
 NOT INDICATE A CHANGE IN FIXTURE TYPE.
 700.16, LS 101 7-9, 90.4
  
 8)NOTE: NOTE #8OK.
  
 9)NOTE: NOTE #9OK
  
 10)NOTE: NOTE #10, OK.
  
 11)NOTE: NOTE #11 OK
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE SOME
 UNITS MISSING RECEPTS PER 210.52.
 PLEASE SEEONE REDLINED SET.
 "L" SOUTH, BED RM #3, "N", BR#3 #4,
 LOFTS WITH WHAT APPEARS TO BE WALL SPACE
 BY STAIRS ON LOWER LEVELS/ WITHIN 6' FRO
 THE EDGE.
  
 19)NOTE: NOTE #19 NO,PLEASE SEE
 CIRCUITING MISSING FROM SOME DEVICES
 SHOWN IN SOME OF THE UNITS. PLEASE SEE
 SD'S, RECEPTS.
 PLEASE SEE REDLINED PLANS AS MOST ARE
 CIRCIRLED.
  
 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE
 SOME AREA DESIGNATIONS ON UNITS ARE NOW
 SHOWN WHICH DINING AREAS/BREAKFAST AREAS
 ARE ON 15A #14 GEN LT CIRCUITS.
 CIR #42
 PLEASE SEE UNIT "N", "Q"
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK, HOWEVER PLEASE SEE
 NEW NOTE FOR ONE GFI LOCATION.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 OK.
  
 29)NOTE: NOTE #29 OK.
  
 30)NOTE: NOTE #30 OK.
  
 31)NOTE: NOTE #31 OK.
  
 32)NOTE: NOTE #32 NO.
 PLEASE SEE MISSING SMOKE DETECTORS
 REQUIRED UNDER NFPA-72 11.5.1.1,
 11.8.3.5
 PLEASE SEE SD'S ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING RMS AND ON EACH
 LEVELOF A MULTY LEVEL DWELLING.
 PLEASE SEE SOME MISSING, DEN IN UNIT "R"
 WILL BE REQUIRED TO HAVE A SD AS IT IS
 SHOWN WITH AN ATTACHED BATH OR CLOSET
 WHICH MAKES THIS AN ADAPTABLE SLEEPING
 RM BY AHJ. PLEASE SEE MISSING SD "Q"
 NORTH,LEADING TO FLR ABOVE.
 PLEASE SEE SD'S ARE REDLINED AT
 LOCATIONS REQUIRED IN OTHER UNITS.
  
 33)NOTE: NOTE #33 OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE THESE
 LOBBY AREAS ARE STILL UNCLEAR BY THE
 BLDG REVIEW COMMENTS IF THEY BELONG TO
 THE UNIT OR PART OF "HOUSE/COMMON" AREA.
 PLEASE SEE EXTENSIVE BLDG REVIEW
 COMMENTS.
 PLEASE SEE 210.25 WHICH STATES NO COMMON
 AREAS SHALL CONTAIN ELECTRICAL DEVICES
 FED FROM UNITS. IF THESE ARE "PRIVATE"
 LOBBIES,PLEASE SHOW HOW THESE AREAS
 CONTAIN NUMEROUS ELECTRICAL ITEMS FED
 FROM HOUSE POWER?
 PLEASE ALSO SEE NEW EXT LTS ETC ADDED TO
 UNITS.
  
 35)NOTE: NOOTE #35 OK.
  
 36)NOTE: NOTE #36 OK.
  
 37)NOTE: NOTE #37 NO, PLEASE ADD NOTE TO
 THE ROOF TOP PLANS.
 PLEASE SEE ANY PROPOSED LIGHTNING
 PROTECTION SYSTEM SHALL BE
 INSTALLED AND ACCEPTABLE PER NFPA-780.
 ALTHOUGH A LIGHTNING PROTECTION SYSTEM
 IS NOT SHOWN ON ANY PLANS, PLEASE BE
 SURE A NOTE IS PLACED ON "ROOF-TOP"
 SHEET WITH REFERENCE TO NFPA-780.
 AS NOTED IN MEETING , "LIGHTNING
 PREVENTION" SYSTEMS ARE NOT PERMITTED OR
 ACCEPTABLE IN THIS JURISTICTION.
  
 38)NOTE: NOTE #38 OK, HOWEVER SEE ELEC
 NOTES FOR SERVICE.
  
 39)NOTE: NOTE #39 OK.
  
 40)NOTE: NOTE #40,NO, PLEASE SEE
 ELECTRICAL SERVICE WAS MOVED AROUND ,
 HOWEVER THE INTENT OF ORIGINAL NOTE HAS
 NOT BEEN ADDRESSED. PLEASE SEE EM MAIN
 HAS NOW BEEN MOVED TO MAIN ELECTRICAL
 RM, WHICH WHEN SHUT OFF WILL TRIGGER THE
 GEN TO START, TRANSFER POWER OVER TO
 HXDP, WHICH IS STILL LOCATED IN THE GEN
 RM. THEMCB ADDED TO THE HXDP WOULD NOT
 BE READILY ACCESSIBLE, GROUPED OR IN
 CLOSE PROXIMITY AND OTHER HAZARDS MAY
 PREVENT THE SHUTTING DOWN OF POWER IN A
 TIMELY AND SAFE MANOR.
 THIS LOCATION WITH A 1500KW GENERATOR
 RUNNING AT FULL NOISE LEVEL, HEAT ETC
 MAY DISTRACT IN SHUTTING DOWN OF EM
 POWER IN A SAFE AND TIMELY FASHION. IT
 IS NOTED THAT THESE MAINS AND GEN WILL
 HAVE SHUNT TRIPS IN FIRE COMMAND RM,
 HOWEVER THESE ARE NOT CONSIDERED AS THE
 MEANS OF DISC. 230.76,230.79
 PLEASE SEE IT IS UNCLEAR AT THIS TIME IF
 BRKR ON GEN IS LOCATED ON THE OUTSIDE OF
 EQUIPMENT WITH A MANUAL MEANS OF
 DISCONNECT WITH EXPOSING OF LIVE PARTS.
 110.27.
 PLEASE SEE SOME OF THIS CAN NOT BE
 VERIFIED AT THIS TIME AS SPECS FOR THIS
 EQUIPMENT, GENERATOR ETC WAS NOT
 SUBMITTED.
 PLEASE SEE ROUTE, LOCATION TRAVEL
 DISTANCE ETC MAY BE GONE IN A MEETING
 WHICH MAY BE REQUESTED.
  
 41)NOTE: NOTE #41 OK.
  
 42)NOTE: NOTE #42 OK.
  
 43)NOTE: NOTE #43 OK.
  
 44)NOTE: NOTE #44 OK.
  
 45)NOTE: NOTE #45 OK.
  
 46)NOTE: NOTE #46 OK, HOWEVER NO
 CONNECTION FOR GEN GROUNDING ELECTRODE
 SYSTEM WAS SHOWN. ONLY NOTES TO GEN
 FRAME. PLEASE SEE 250.30, AS THIS GEN IS
 SEPARATELY DERIVED.
  
 47)NOTE: NOTE #47 OK.
  
 48)NOTE: NOTE #48 OK.
  
 49)NOTE: NOTE #49 OK.
  
 50)NOTE: NOTE #50 OK.
  
 51)NOTE: NOTE #51 OK.
  
 52)NOTE: NOTE #52 OK.
  
 53)NOTE: NOTE #53 OK.
  
 54)NOTE: NOTE #54 OK.
  
 55)NOTE: NOTE #55 OK.
  
 56)NOTE: NOTE #56 OK, HOWEVER SEE NEW
 NOTE AS PANEL SCHEDULES REVIEWED FOR THE
 FIRST TIME.
  
 57)NOTE: NOTE #57 OK.
  
 58)NOTE: NOTE #58 OK.
  
 59)NOTE: NOTE #59 OK.
  
 60)NOTE: NOTE #60 OK.
  
 61)NOTE: NOTE #61
  
 62)NOTE: NOTE #63, NOPLEASE SEE POOL
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT WHICH IS NOTED ON PLANS.
 THIS IS OK, HOWEVER PLEASE KNOW, IF
 THERE IS GOING TO BE ANY AFTER DUSK
 SWIMMING, THIS WILL HAVE AN IMPACT ON
 THE MIN LIGHTING LEVELS AND DESIGN FOR
 POOL DECK/EGRESS LIGHTING. PLEASE SEE
 OTHER NOTES PERTAINING TO EGRESS..
 IF NIGHT-TIME/AFTER DUSK WILL BE
 PROPOSED, SIGNED, SEALED PHOTOMETRICS
 WILL BE REQUIRED TO BE SUBMITTED TO PALM
 BEACH COUNTY HEALTH DEPT FOR REVIEW AND
 STAMPING.
  
  
  
 ******* NEW NOTES ************
  
 1)NOTE: PLEASE CORRELATE CONDUCTORS
 SHOWN ON HS FOR LS.
 215.5
 PLEASE ALSO LABEL WHICH TRANSFORMER HS
 IS FEEDING AS OTHER PANEL SCHEDULES ARE
 LABELED.
  
 2)NOTE: PLEASE SEE CIRCUITS WHICH
 REQUIRE ARC FAULT PROTECTION, PLEASE SEE
 "Q", #32, UNIT "A", #28.
  
 3)NOTE: PLEASE SEE A "MISPRINT" OF AN
 ADDITIONAL "ELEC PANEL" IN UNIT "B".
 215.5
  
 4)NOTE: PLEASE SEE NOTES WITH RESPECT TO
 ARC FAULT PROTECTION. NOTE MENTIONS
 "RECEPT" WHERE-AS ALL OTHER NOTES WERE
 CHANGED TO "OUTLETS".
  
 5)NOTE: PLEASE SEE BLDG NOTES PERTAINING
 TO MEZZANINE, AND TOWNHOUSE DESIGNATIONS
 WHICH ARE ON E-SHEETS AND OTHER
 LOCATIONS.
  
 6)NOTE: PLEASE PROVIDE THE INFORMATION
 AS REQUESTED BY FIRE AND BLDG REVIEW
 PERTAINING TO POOL EQUIPMENT ROOM AND
 ANY STORAGE OF HAZARDOUS MATERIALS.
 ADJUST ELECTRICAL AS NEEDED,PLACE NOTE
 ON PLANS.
  
 7)NOTE: PLEASE PROVIDE A BUS-DUCT CURB
 DETAIL AS REQUIRED PER 368.6, THIS
 SHOULD HAVE BEEN REQUESTED ON ORIGINAL
 REVIEW.
  
 8)NOTE: PLEASE VERIFY NEW NOTE WHICH
 MENTIONS A FLOOR? MOUNTED GFI IN BATHRM
 FOR JACUZZI TUB IN UNIT "Q". THIS SHALL
 NOT BE MOUNTED FACING UP, AND SHOWN BE
 OFF THE FLOOR/WET AREA LOCATED UNDER TUB
 ACCESS PANEL.
 PLEASE SEE MIN CLEARENCES FROM TUBS,
 410.8
  
 9)NOTE: PLEASE KNOW THE FOLLOWING MAY BE
 SET-UP AS A "PROVISO" OR MAY BE
 ADDRESSED AT THIS TIME.
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 STAIRS TOWERS, EGRESS TUNNELS, AND ALL
 OTHER PATHS FOR MEANS OF EGRESS AS
 PREVIOUSLY NOTED TO PUBLIC RIGHT-OF-WAY.
 PLEASE SEE 7.8.1.3, WHICH REQUIRES A MIN
 OF 10FT CANDLES(108 LUX) UNDER NORMAL
 POWER AT ALL WALKING SURFACES OF
 STAIRS/STAIRWAYS.
 PLEASE SEE STAIRS CAN BE REDUCED TO .8
 LUX OR 1FT CANDLE UNDER EM POWER/BATTERY
 BACK UP.
 PLEASE SEE ALL OTHER AREAS FOR EGRESS
 MUST HAVE A MIN OF 1 FT CANDLE UNDER
 NORMAL AND EM POWER ON ALL WALKING
 SURFACES.
  
  
 ** PLEASE SEE MOST OF THE ABOVE
 ITEMS ARE REDLINED ON ONE SET OF
 ELECTRICAL PLANS, HOWEVER THESE DO NOT
 IDICATE ALL POSSIBLE LOCATIONS OF NEEDED
 CORRECTIONS.
  
 **PLEASE KNOW, SOME ITEMS STILL NEED TO
 BE VERIFIED ONCE ALL INFORMATION IS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE A
 DIRECT EFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  