Date |
Text |
2005-10-06 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT A0.04C ACCESSIBILITY REQUIREMENTS |
| PER SECTIONS 11-4.16.5, 11-4.19.5 AND |
| 11.4.21.7 TO BE SHOWN ON PLANS. |
| 2. SHT A0.04.4 DETAIL 04. SUBMIT |
| CALCULATIONS FOR GRAB BAR BACKING PER |
| SECTION 609.8 OF THE ANSI A117.1 |
| STANDARD FOR THE SUPPORTIVE STRUCTURE. |
| INDICATE GUAGE OF METAL PLATE. |
| 3. SHT C1 SURVEY NOT SIGNED, SEALED, AND |
| DATED AS REQUIRED BY FAC 61G15-23.002 & |
| FS 471.025. |
| 4. SHTS C-2 THRU C-5 ENGINEERS SEAL |
| SHALL IMPART INFORMATION REQUIRED BY FAC |
| 61G15-233.001 & FS 471.025 ON EACH |
| SHEET. THE INFORMATION REQUIRED ON SEAL |
| HAS NOT BEEN IMPRESSED ON EACH SHEET AS |
| REQUIRED. - THE SIGNATURE REQUIRED |
| APPEARS TO BE INITIALS WHICH ACCORDING |
| TO FBPE IS NOT APPROVED AND A SIGNATURE |
| IS REQUIRED. IF INDEED THIS IS YOUR |
| LEGAL SIGNATURE, PROVIDE A SIGNED, |
| SEALED, DATED, AND NOTORIZED LETTER |
| INDICATING YOUR LEGAL SIGNATURE FOR OUR |
| FILES. |
| 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO |
| INFORMATION ON THE SEAL HAS BEEN |
| IMPRESSED ON THE SHEETS AS REQUIRED BY |
| FAC 61G1-16.001. ALSO THE CERTIFICATE OF |
| AUTHORIZATION NUMBER AND THE PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT |
| SHALL APPEAR ON THE TITLE BLOCK PER FAC |
| 61G1-16.004(2) & (6) AND FS 481.219, |
| 481.2055. |
| 6. SHT A1.02C DETAIL 04 SHOW TURNING |
| AREA IN THE STAFF TOILET AS REQUIRED BY |
| SECTION 11-4.22.3. |
| 7. SHT A1.02C DETAIL 01 SHOW TURNING |
| AREA IN THE RESTROOMS, NOT IN THE |
| STALLS. SECTION 11-4.22.3 |
| 8. SHT A1.02C A DRINKING FOUNTAIN IS |
| REQUIRED PER TABLE 403.1. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.15 AND ALL SUBSECTIONS AND WITH |
| SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING. |
| 9. SHT 1.05C DETAIL 02 SHOW THE TURNING |
| AREA IN RESTROOM NOT IN THE STALL. |
| SECTION 11-4.22.3 |
| 10. PLEASE INDICATE IF THE KITCHEN WILL |
| BE BUILT-OUT ON THIS PERMIT OR WILL IT |
| BE A SEPARATE PERMIT, AS THE PLANS WILL |
| HAVE TO BE ROUTED TO DBPR RESTURANT AND |
| HOTEL DIVISION PRIOR TO APPROVAL. |
| SECTION 101.4.7. |
| 11. SHTS A1.05, A1.09, A1.10, & A1.11. |
| SS-1 SUBMIT CALCULATIONS FOR PRIMARY & |
| SECONDARY ROOF DRAINS. SHOW TOTAL AREA, |
| 1/2 AREA OF ALL VERTICAL WALLS, |
| (INCLUDING PARAPETS), ALL AREAS OF ROOFS |
| ADDED TO ROOF AREA FROM ABOVE ADDED TO |
| ROOF AREA IN CALCULATIONS. INDICATE |
| TOTAL AREA DRAINED BY EACH ROOF DRAIN. - |
| THIS IS REQUIRED FOR EACH ROOF LEVEL AND |
| FOR THE RECREATION LEVEL. SHOW THE |
| LOCATION OF ALL SECONDARY ROOF DRAINS |
| AND SCUPPERS. INDICATE THE SIZE OF ALL |
| SCUPPERS AND SUBMIT A DETAIL SHOWING THE |
| HEIGHT, WIDTH AND THE HEIGHT OF THE FLOW |
| LINE OFF THE ROOF. SECTIONS 1106 & 1107 |
| AND ALL SUBSECTIONS. |
| 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW |
| BACKING & OPENING DIMENSIONS FOR THE W/C |
| OPENINGS FOR ADDITIONAL BATHROOMS PER |
| BATHROOM REQUIREMENTS PAGE 7.35. THIS |
| WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS' |
| SHT A4.03 UNIT 'BS', SHT A4.04 UNIT |
| 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06 |
| UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15 |
| UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20 |
| UNIT 'KN', SHT A4.22 UNIT 'LS', SHT |
| A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2', |
| SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT |
| 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28 |
| UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT |
| A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT |
| 'QN', SHT A4.32 UNIT 'RN', SHT A4.33 |
| UNIT 'RS', SHT A4.34 UNIT 'SN', SHT |
| A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS', |
| SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT |
| 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT |
| A4.31.1 UNIT 'STSM'. |
| 13. SHTS A4.10 - A4.16 CLEAR FLOOR SPACE |
| SHALL BE FLUSH WITH THE CONTROL WALL FOR |
| SHOWERS AND PARALLEL TO SHOWER. PAGE |
| 7.56. |
| 14. SHT A4.36 SUBMIT USABLE BATH DETAIL. |
| 15. SHT A4.37 SUBMIT USABLE BATH DETAIL. |
| 16. SHTS A4.38, A4.39, & A4.40 ENTRY |
| LEVEL TO BE COVERED PER FHA. SUBMIT |
| DETAILS FOR BATHROOMS. |
| 17. GROUND FLOOR CONFERENCE ROOM SINKS |
| SHALL BE ACCESSIBLE. SUBMIT A DETAIL |
| SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| AND ALL SUBSECTIONS. |
| 18. SHT P-1 REGULATORS SHOW 7"W/C - |
| TABLE 402(2) IS FOR 1/2 PSI WHICH IS 11" |
| TO 14"W/C. PLEASE CLARIFY AND VERIFY |
| INPUT PRESSURE FOR GAS SYSTEM. |
| 19. SHT P-1 INDICATE MATERIAL TO BE USED |
| FOR THE REGULATOR VENT PIPING. (NON |
| COMBUSTABLE REQUIRED). |
| 20. GAS RISER INDICATES 6396 MBH, BUT |
| ADDS UP TO 6196 MBH. PLEASE CLARIFY. - |
| LAST PIPE SECTION TO SPA @ 300 MBH SHALL |
| BE 1" NOT 3/4" AS SHOWN. TABLE 402(2). - |
| ALL PIPE SECTIONS SHALL SHOW THE LENGTH |
| OF EACH SECTION ON THE RISER DIAGRAM. |
| SOME SECTIONS DO NOT SHOW A LENGTH. |
| 21. THE FOLLOWING INFORMATION IS |
| REQUIRED FOR GAS PERMIT: |
| A. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| B. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| (DOWNSTREAM OF REGULATOR). |
| C. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| 22. SEPARATE GAS PERMIT REQUIRED. AT |
| TIME OF APPLICATION, CONTRACTOR SHALL |
| SUBMIT A PICTURE I.D. OF THE WELDER, |
| WELDING CERTIFICATION, AND A COPY OF THE |
| WELDING PROCEDURE. |
| 23. ALL FLOOR PLAN SHEETS, SHOW THE |
| LOCATION & NUMBER OF EACH RISER THRU THE |
| BUILDING ON EACH FLOOR PLAN AND EACH |
| LEVEL. SECTION 104.2.1. |
| 24.SHT P-2 RISER DESIGNATIONS 35, 36, |
| 45, 46, 46A, & 47 ARE NOT SHOWN. |
| 25. SHT P-2 SHOW THE PIPING FOR ALL |
| TRENCH DRAINS WITH PIPE SIZES. THIS |
| SHALL BE REFLECTED ON THE STORM RISER |
| DIAGRAM. SECTION 104.3.1.1. |
| 26. GREASE INTERCEPTOR SHALL BE SIZED BY |
| THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| WASTE ORD. #3434. PLEASE CONTACT LYNN |
| MASSON AT (561) 822-2271, FAX (561) |
| 822-2279 OR E-MAIL [email protected]. |
| 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL |
| PIPE SIZES. RECALCULATE ADDITION ON SOME |
| RWL'S, INDICATE RWL RISER NUMBERS, 3" |
| OVERFLOW SHOWN CONNECTING TO PRIMARY |
| SYSTEM AT COL. 24 BETWEEN COLS, A&B. |
| PLEASE CLARIFY. SECTION 104.2.1. - SHOW |
| ALL SECONDARY ROOF DRAINS, WITH PIPE |
| SIZES, SF, ECT. INDICATE SF OF DRAIN |
| BETWEEN COLS. S.06 & S.05 BETWEEN COLS. |
| 20 & 21, AND THE DRAIN BETWEEN COLS. H & |
| I, AND BETWEEN COLS 18 & 19. |
| 28. SHT P-4 STATES "3"S FOR CONT. SEE |
| P-4 HEALTH CLUB". THIS WAS NOT FOUND ON |
| SHT P-4. PLEASE CLARIFY. |
| 29. SHT P-4 INDICATE WHAT THE |
| DESIGNATION FOR "DL" REPRESENTS. |
| 30. SHT P-7 RISER DESIGNATIONS 35, 36, |
| 38, 45, 46, & 46A NOT SHOWN. PLEASE SHOW |
| ALL RISERS FOR EACH FLOOR LEVEL. SECTION |
| 104.2.1. |
| 31. SHT P-7 SANT. PIPING NOT ALLOWED IN |
| THE EGRESS STAIRWAY. NFPA-101 SECTION |
| 7.1.3.2.1(6). |
| 32. SHT P-8 OFFSETS SHOWN FOR RISERS 6, |
| 10, 11, 12, 15, & 17, 18, 19, 20 ARE NOT |
| SHOWN ON THE RISER DIAGRAMS. SECTIONS |
| 104.2.1, & 104.3.1.1. |
| 33. SHT P-9 OFFSETS SHOWN FOR RISERS 42, |
| 44, 47, 30, 34, 35, 36, 21, 25, 1, AND |
| TO TOILET ROOMS RECREATION LEVEL 4 ARE |
| NOT SHOWN NO THE RISER DIAGRAMS. |
| SECTIONS 104.2.1, & 104.3.1. |
| 34. SHT P-9SHOW THE TYPICAL PIPING |
| LAYOUTS FOR RISERS 16, 22, 28, & 29. |
| SECTION 104.3.1.1. |
| 35. SHT P-9 THE FOLLOWINGPIPING |
| LAYOUTS DO NOT REFLECT RISER DIAGRAMS |
| 44, 47, 42, 40, 39, 20, & 4. SECTION |
| 104.2.1. |
| 36. SHT P-13 PIPING FOR THE DWV AND |
| STORM SYSTEMS NOT APPROVED IN EGRESS |
| STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6) |
| AND SECTION 1006.1.3.1. |
| 37. P-14. CONDENSATE IS INDICATED AS 5' |
| SEPARATION FOR THE SUPPORTS. INDICATE |
| MATERIAL FOR CONDENSATE PIPING. IF PVC, |
| MAXIMUM 4' SEPARATION OF SUPPORTS PER |
| TABLE 305.5. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH 140 MPH WIND LOAD FOR |
| SUPPORTS. |
| 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON |
| RISER DIAGRAM 56, 59A, 92, 93, 94, 95, |
| 96, 97, 98, 99, & 100. |
| 39. SHT P-15 PIPING NOT APPROVED IN |
| EGRESS STAIRWAYS. NFPA-101 SECTION |
| 7.1.3.2.1(6). |
| 40. SHT P-15 RISER DIAGRAM 72 NOT SHOWN |
| ON SHEET. SECTION 104.2.1. |
| 41. SHT P-15 THE FOLLOWING PIPING |
| LAYOUTS DO NOT REFLECT THE RISER |
| DIAGRAMS: 48, 48A, 49, 50, 51, 56, 58, |
| 59, 59A, 61, 62, 64, 67, & 67A. - NOT |
| ALL PIPING SHOWN ON THE RISER DIAGRAMS. |
| SECTION 104.3.1.1. |
| 42. SHT P-16 NO PIPING TO W/M SHOWN AT |
| EITHER SIDE OF STAIRS COL. LINE N.05, |
| BETWEEN UNITS NLT103 & NLT104. INDICATE |
| WHICH RISERS THESE W/M'S CONNECT TO. |
| SECTION 104.2.1. |
| 43. SHT P-17 MAXIMUM 6' FROM POINT OF |
| VENT TO TUB TRAP. (NEAR RISER 95) TABLE |
| 906.1. |
| 44. SHT P-17 THE FOLLOWING RISERS DO NOT |
| REFLECT PIPING LAYOUT: 50, 51, 52, & 55. |
| SECTION 104.2.1. |
| 45. SHT P-18 INDICATED AS LEVEL (5-15) |
| PLEASE CLARIFY. |
| 46. SHT P-18 RISER 102 INDICATES 3"V DN |
| TO RISER #34. THIS IS NOT SHOWN ON SHT |
| P-17 NOR ON RISER 102. PLEASE CLARIFY. |
| SECTION 104.2.1. - WHAT IS RISER #3W? |
| WHERE IS IT LOCATED? SECTION 104.2.1. |
| 47. SHT P-20 PIPING FOR KIT SINKS NOT |
| SHOWN. RISER #61. SECTION 104.3.1. |
| 48. SHT P-22 CONDENSATE LINE SHOWN AS 5' |
| SEPARATION BETWEEN SUPPORTS. INDICATE |
| TYPE OF MATERIAL. IF PVC PER TABLE 305.5 |
| MAXIMUM 4' SEPARATION BETWEEN SUPPORTS. |
| SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW |
| THEY ARE ATTACHED TO THE ROOF AND SHOW |
| COMPLIANCE WITH 140 MPH WIND LOAD. |
| 49. SHT P-23 BATHROOM MAIN LOBBY LEVEL 1 |
| SHOWN 36FU, BUT IS SHOWN AS 34FU ON SHT |
| P-2. CORRELATE PLANS. SECTION 104.2.1. |
| 50. SHT P-23 RECREATION AT LEVEL 4 |
| PIPING DOES NOT REFLECT THE FIXTURE |
| LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT |
| WITH PIPING LAYOUT. SECTION 104.2.1. |
| (RISER DIAGRAM DOES NOT REFLECT FIXTURE |
| LAYOUT EITHER). |
| 51. SHT P-23 RECREATION AT LEVEL 2 |
| INDICATES 40FU FOR FUTURE GYM, BUT ONLY |
| 44FU AFTER ADDING MEN'S & WOMEN'S TOILET |
| ROOMS. PLEASE RECALCULATE FU'S. (ALSO |
| ADJUST ON RISER DIAGRAM). SECTION |
| 104.2.1. |
| 52. SHT P-23 RISER DIAGRAMS STATE "FOR |
| CONT. SEE P-68". P-68 SHOWS STORM RISER |
| ONLY. PLEASE CLARIFY. SECTION 104.2.1. |
| 53. SHT P-39 FLOOR DRAIN NOT SHOWN |
| BETWEEN 1ST & 2ND WLI UNITS FIRST FLOOR. |
| PLEASE CLARIFY. SECTION 104.2.1. |
| 54. SHT P-52 SANT. RISER DIAGRAM UNIT |
| TOWNHOME, MAXIMUM 4FU ON 2" WET VENT PER |
| TABLE 909.3. |
| 55. SHT P-52 RISER DIAGRAMS STATE "FOR |
| CONT. SEE P-69". CONT. NOT FOUND ON |
| P-69. PLEASE CLARIFY. SECTION 104.2.1. |
| 56. SHT P-53 RISER 13 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SECTION 914.1. |
| - DRY HORIZONTAL VENTS NOT APPROVED 17TH |
| FLOOR. SECTIONS 905.3/905.4. |
| 57. SHT P-53 RISER 8 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SECTION 914.1. |
| 58. SHT P-54 RISER 10 LOWER OFFSET VENT |
| REQUIRED. SECTION 915.3. - HORIZONTAL |
| BRANCH CONNECTIONS NOT APPROVED ON THE |
| HORIZONTAL OFFSET. SECTION 711.2 |
| 59. SHT P-54 RISER 12 LOWER OFFSET VENT |
| REQUIRED. SECTION 915.3. - MAX 10 BRANCH |
| INTERVALS TO RELIEF VENT. SECTION 914.1. |
| - 4" VENT TO RISER #8 READS "FROM RISER |
| 8. PLEASE CORRELATE RISERS. SECTION |
| 104.2.1. |
| 60. SHT P-54 RISER 14 LOWER OFFSET VENT |
| REQUIRED. SEC. 915.3 - MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. |
| 61. SHT P-54 RISER 17 LOWER OFFSET VENT |
| REQD. SEC. 915.3. - MAX 10 BRANCH |
| INTERVALS TO RELIEF VENT. SECT. 914.1. |
| 62. SHT P-55 RISER 20 BATHROOM SHOWN ON |
| 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON |
| 5TH FLOOR ON RISER. CORRELATE RISER AND |
| FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH |
| FLOOR NOT SHOWN ON RISER. SEC. 104.2.1. |
| 63. SHT P-55 RISER 22 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. |
| 64. SHT P-55 RISER 23 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| LOWER OFFSET VENT REQD. SEC. 915.3. |
| 65. SHT P-56 RISER 25 SINK MISSING 17TH |
| FLOOR. SEC. 402.1.1. |
| 66. SHT P-56 RISER 26 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| NO BRANCH CONNECTIONS ON HORIZONTAL |
| OFFSET. SEC. 711.2. |
| 67. SHT P-56 RISER 28 NO HORIZONTAL DRY |
| VENTS. SEC. 905.3/905.4 (16TH FLOOR) |
| 68. SHT P-56 RISER 29 LOWER OFFSET VENT |
| REQD. SEC 915.3. - NO CONNECTION TO |
| HORIZONTAL OFFSET. SEC. 711.2. |
| 69. SHT P-56 RISER 30 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| NO HORIZONTAL DRY VENTS. SEC. |
| 905.3/905.4 |
| 70. SHT P-56 RISER 32 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| NO HORIZONTAL DRY VENTS. SEC. |
| 905.3/905.4. - UPPER OFFSET VENT REQD. |
| SEC. 915.2. - SEPARATE RISER SECTION AT |
| BASE OF STACK FOR POWDER ROOM, INDICATE |
| RISERS CONNECTING FROM UPSTREAM. (33, |
| 37, 37A) SEC. 104.2.1. |
| 71. SHT P-56 RISER 33 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| NO HORIZONTAL DRY VENT. SEC. 905.3/905.4 |
| - DOES NOT REFLECT FLOOR PLAN @ 4TH |
| LEVEL. (BASE OF STACK) SEC. 104.2.1. - |
| VENT FROM 1ST FLOOR FLOOR DRAIN NOT |
| SHOWN ON RISER. (SEE P-3, P-4, P-67). |
| 72. SHT P-57. RISERS 39, 40,41, 42, 43, |
| 44 DO NOT REFLECT THE FLOOR PLANS AT THE |
| BASE OF RISER. SEC. 1-4.2.1. |
| 73. SHT P-57 RISER 42 VENT FROM FIRST |
| FLOOR FLOOR DRAINS NOT SHOWN. PLEASE |
| CLARIFY. SEC. 104.2.1. |
| 74. SHT P-58 RISERS 45, 46, 47 DO NOT |
| REFLECT FLOOR PLANS FOR 4TH LEVEL. |
| SECTION 104.2.1. |
| 75. SHT P-59 RISER 50 DOES NOT REFLECT |
| THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1. |
| 76. SHT P-59 RISER 51 DOES NOT REFLECT |
| THE FLOOR PLAN AT BASE OF RISER AND ON |
| THE 4TH LEVEL. PLEASE CLARIFY SEC. |
| 104.2.1. |
| 77. SHT P-59 RISER 52 DOES NOT REFLECT |
| FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT |
| REQUIRED. SEC. 915.2. |
| 78. SHT P-59 RISERS 53, 55 DO NOT |
| REFLECT THE FLOOR PLAN 4TH LEVEL. |
| SECTION 104.2.1. |
| 79. SHT P-60 RISER 56 DOES NOT REFLECT |
| THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS |
| REQD. SECS. 915.2/915.3. - MAX. 10 |
| BRANCH INTERVALS TO RELIEF VENT. SEC. |
| 914.1. - NO CONNECTIONS TO HORIZONTAL |
| OFFSET. SEC. 711.2.- NO HORIZONTAL DRY |
| VENTS. SECS. 905.3/905.4. |
| 80. SHT P-60 RISER 58 DOES NOT REFLECT |
| THE FLOOR PLAN, CHECK LOCATION OF |
| CONNECTION OF RISER 59. - RISER 58 & 61 |
| NOT TIED TOGETHER ON FLOOR PLAN. - UPPER |
| OFFSET VENT REQD. 915.2 |
| 81. SHT P-60 RISER 61 DOES NOT REFLECT |
| THE FLOOR PLAN LEVEL 17. SEC. 104.2.1. |
| 82. SHT P-60 RISER 57 DOES NOT REFLECT |
| THE FLOOR PLAN UPPER LEVEL. - MAX 10 |
| BRANCH INTERVALS TO RELIEF VENT. SEC. |
| 914.1. |
| 83. SHT P-60 RISER 60 DOES NOT REFLECT |
| THE FLOOR PLAN. SHOWS CONNECTING TO |
| HORIZONTAL DRAIN LINE. (GROUND FLOOR?) - |
| UPPER OFFSET VENT REQD. SEC. 915.2. - |
| DOES NOT REFLECT THE FLOOR PLAN AT THE |
| TOP OF THE RISER. - MAX 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. |
| 84. SHT P-61 RISER 62 DOES NOT REFLECT |
| THE FLOOR PLAN. - LOWER OFFSET VENT REQD |
| SEC. 915.3. |
| 85. SHT P-61 RISERS 63, 64 DO NOT |
| REFLECT THE FLOOR PLAN. PLEASE CLARIFY |
| SEC. 104.2.1. |
| 86. SHT P-61 RISER 67 MAX 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| NO HORIZONTAL DRY VENTS. SECS. 905.3 |
| 905.4. |
| 87. SHT P-61 RISER 67A DOES NOT REFLECT |
| THE FLOOR PLAN. - LOWER OFFSET VENT REQD |
| SEC. 915.3. |
| 88. SHT P-61 RISER 68 FIXTURES NOT SHOWN |
| FOR 4TH LEVEL ON THE RISER. PLEASE |
| CLARIFLY. SECTION 104.2.1. |
| 89. SHT P-62 RISER 70 LOWER OFFSET VENT |
| REQD. SEC 915.3 |
| 90. SHT P-62 RISER 71 MAX. 10 BRANCH |
| INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| NO DRY HORIZONTAL VENT. SECS. 905.3 |
| 905.4. |
| 91. SHT P-62 RISER 72 DOES NOT REFLECT |
| THE FLOOR PLAN PIPING LAYOUT LEVEL 3. |
| SECTION 104.2.1. |
| 92. SHT P-62 RISER 73 & 74 MAX. 10 |
| BRANCH INTERVALS TO RELIEF VENT. SEC. |
| 914.1. |
| 93. SHT P-62 RISER 74A DOES NOT REFLECT |
| THE FLOOR PLAN LEVEL 4. SECTION 104.2.1. |
| 94. SHT P-62 RISER 79 DOES NOT REFLECT |
| THE FLOOR PLAN PIPING LAYOUT LEVEL 4. |
| SEC. 104.2.1. |
| 95. SHT P-63 RISERS 75,76,77,78,87,88 |
| DO NOT REFLECT THE FLOOR PLAN PIPING |
| LAYOUTS LEVEL 4. SECTION 104.2.1. |
| 96. SHT P-63 RISER 80 FLOOR DRAIN LEVEL |
| 16 ROOF NOT SHOWN ON RISER DIAGRAM. |
| SECTION 104.2.1. CORRELATE RISER/FLOOR |
| PLAN. |
| 97. SHT P-63 RISERS 89,94,95,99,101,102 |
| & 103 DO NOT REFLECT THE FLOOR PLANS. |
| SECTION 104.2.1. |
| 98. SHT P-67 HORIZONTAL SANT. RISER |
| DIAGRAM MISLABELED AS "WATER RISER |
| DIAGRAM". PLEASE CLARIFY. SEC. 104.2.1. |
| 99. SHT P-67 FOLLOWING ARE CORRECTIONS |
| TO BE MADE TO SANT. RISER DIAGRAM: - |
| RISERS 35 & 36 NOT SHOWN. - PIPING |
| LAYOUT DOWNSTREAM OF RISER 33,37,37 DOES |
| NOT REFLECT FLOOR PLAN FOR POWDER ROOM. |
| - RISERS 23 & 23A MISLABELED. - 2" VENT |
| UP TO RISER 42 NOT SHOWN ON RISER 42. - |
| PIPING BETWEEN RISERS 6,10,11,12,15 & |
| RISER 9,13 DOES NOT SHOW POWDER ROOM OR |
| WASH MACHINE. - OFFSETS & PIPING LAYOUT |
| SHOWN ON SHT P-9 ARE NOT SHOWN ON RISER |
| DIAGRAM. - NO VENT SHOWN FOR GREASE |
| LINE. - GREASE LINE DOES NOT REFLECT THE |
| FLOOR PLAN, AND IS NOT SHOWN ON FLOOR |
| PLANS P-15 THRU P-18. -4"-34FU FOR CONT. |
| SEE P-23 SHOWS 36FU ON SHT P-23. |
| CORRELATE SHEETS. - 2" VENT FROM 2 SINKS |
| SHOWS 3" VENT ON SHTS P-3, P-4, & P-5. |
| CORRELATE SHEETS. - 2" VENT UP TO RISER |
| 67 TO READ "TO RISER 67A". (SEE RISER |
| 67A). - "2" VENT FOR CONT. SEE P-53" |
| INDICATE RISER VENT WILL CONNECT TO. - |
| "UNITS WL1, WL2 & UNITS 1T THRU 10T, |
| 4"-28FU FOR CONT. SEE P-53. NOT FOUND ON |
| SHT P-53. PLEASE CLARIFY - 6" LINE FROM |
| RISER 92,93,94,95,96,97,98, 99,100 DOES |
| NOT SHOW OFFSET ON RISER SHOWN ON SHT |
| P-15. - THIS SHEET SHOWS LEVELS AS PARK, |
| PARK 2, PARK 3 ECT., BUT SHEETS P-15, |
| P-16. & P-17 SHOWS LEVELS AS GROUND |
| FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS |
| MEZZ. ECT. PLEASE CLARIFY & CORRELATE |
| SHEET LEVELS. - RECHECK ADDITION OF |
| FIXTURE UNITS AS THEY ACCUMULATE IN THE |
| SYSTEM. SOME FIXTURES UNITS ARE NOT |
| SHOWN AND ADDED TO THE SYSTEM. INDICATE |
| THE SLOPE OF THE PIPE WHERE THE FIXTURES |
| UNITS ARE MORE THAN ALLOWED FOR MINIMUM |
| SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE |
| INSTALLED IN A UNIFORM SLOPE AS REQUIRED |
| IN SECTION 704.1. INDICATE ON PLANS. |
| SECTION 104.2.1. |
| 100. SHT P-68 HORIZONTAL STORM RISER |
| DOES NOT REFLECT STORM PIPING IN |
| BUILDING. STRUCTURES S1 THRU S9 NOT |
| SHOWN. - NO ROOF DRAINS 2650SF, 2350SF, |
| 2450SF ECT. FOUND. - NO EXFILTRATION |
| TRENCHES FOUND. - NO TRENCH DRAINS |
| FOUND, RISERS SHOWS 25TH, 26TH, 27TH |
| FLOORS ECT. - NO POINT OF REFERENCE TO |
| FLOOR PLAN CAN BE FOUND. - RISER HARD TO |
| READ, PLEASE INCREASE THE SIZE OF THE |
| STORM RISER DIAGRAM AND POSSIBLY SPLIT |
| UP TO TWO PAGES TO MAKE RISER EASIER TO |
| READ. SECTION 104.2.1.3. |
| 101. SUBMIT A CONDENSATE RISER DIAGRAM |
| SHOWING ALL PIPE SIZES AND INDICATE |
| MATERIAL. SECTION 104.3.1.1. |
| 102. SUBMIT A P/T VALVE DISCHARGE RISER |
| DIAGRAM SHOWING ALL PIPE SIZES AND |
| INDICATE PIPING/FITTING MATERIAL. |
| SECTION 104.3.1.1. |
| 103. SUBMIT AN EMERGENCY PAN DRAIN RISER |
| DIAGRAM FOR THE WATER HEATERS. INDICATE |
| PIPE SIZES AND MATERIAL FOR PIPE AND |
| FITTINGS. |
| 104. BACKFLOW PROTECTION REQUIRED FOR |
| IRRIGATION, POOLS, TRASH CHUTE WASH |
| DOWN, AND COOLING TOWER MAKE UP WATER. |
| SECTION 608. INDICATE METHOD OF |
| PROTECTION FOR EACH SYSTEM. |
| 105. PLANS ARE INCOMPLETE AT THIS TIME |
| AND MORE COMMENTS MAY BE FORTHCOMING |
| WITH THE NEXT REVIEW. |
| **************************************** |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| **************************************** |
| **************************************** |