Plan Review Notes
Plan Review Notes For Permit 05071027
Permit Number 05071027
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-24 00:00:00PLAN DENIED
 1) PAGE AC-6 AND AC-7 NEED SMOKE FIRE
 DAMPERS AT RATED CHASE.
 2) PAGE AC-9 NEED DUCT DETECTORS ON ALL
 PACKAGE UNITS OVER 2000 CFM.SECTION
 606.2.1 FBC(M)
 3) PAGE AC-9 PLEASE SHOW MOUNTING DETAIL
 ON A/C DUCT STANDS.
 4) PLEASE SHOW SEQUENCE OF OPERATION FOR
 SF.35 AND SF.37.
 5) PLEASE REFER TO SECTION 501.5 METAL
 DUCT.
 6) GARAGE VENTILATION MUST RUN
 CONTINUOUSLY.PLEASE REMOVE CO2 SENCERS
 7)PAGE AC-32PLEASE REMOVE SMOKE
 DETECTORS FROM
 SF9,15,17,11,13,19 STAIR RISER
 UNITS
 1) PLEASE INDECATE TYPE OF DOORS USED ON
 A/C CLOSITS ON PLANS.
 2) A/C UNITS OVER 2000 CFM INCLUDING
 COMBINED AIRWITH TWO A/C UNITSMUST
 HAVE FAN SHUTDOWN SECTION 606.2.1
 3) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.
 4) DRYER BOOSTER FANS MUST BE SUBMITED
 THROUGH ALTERNATIVE METERALS ,METHODS.
 5) NEED SMOKE FIRE DAMPERS IN ALL DUCT
 GOING THROUGH RATED WALLS IN LOBBEYS.
 6) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 7) PLEASE REFER TO SECTION 602.2.1
 MATERALS EXPOSED WITHIN PLENUMS.
 8) PLEASE REFER TO SECTION 401.6 OUT
 DOOR OPENING PROTUCTION (BATHROOM
 EXHAUST CAPS NEED SCREENS)
 9) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR #3 HABITABLE ROOMS.
 10) PAGE AC-20 RETURN AIR GRILL IS NOT
 IN RETURN AIR PLENUM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  