2005-09-14 00:00:00 | ******DENIED****** |
| |
| 1) PLEASE PROVIDE MORE DETAILS AND |
| LOCATIONS OF ALL GATES. C-1, C-2. |
| |
| 2) PLEASE CORRELATE LOCATIONS OF FIRE |
| HYDRANTS ON APPROPRIATE SHEETS. |
| |
| 3) PLEASE PROVIDE DETAILS AND FLAME |
| SPREAD INFORMATION ON TENSILE FABRIC FOR |
| CANOPY. |
| |
| 4) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR GATES. |
| |
| 5) ALL CONSTRUCTION, ALTERATION AND |
| DEMOLOITION TO COMPLY WITH NFPA-241. |
| CONSTRUCTION DEBRIS TO BE REMOVED DAILY. |
| |
| 6) STAIRS SHALL BE MAINTAINED DURING |
| CONSTRUCTION. |
| |
| 7) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN BUILDINGS REACH 3 STORIES OR 30' IN |
| HEIGHT. |
| |
| 8) ALL CUTTING/WELDING TO COMPLY WITH |
| NFPA 51-B. |
| |
| 9) ELECTONIC SWITCHES, CHAIN AND LOCK IS |
| REQUIRED ON DOUBLE CHECK DETECTOR |
| ASSEMBLY. |
| |
| 10) WORK TO COMPLY WITH HIGHRISE |
| REQUIREMENTS IN ACCORDANCE WITH FBC AND |
| NFPA 101, SECTION 11. |
| |
| 11) TACTILE SIGNAGE IS REQUIRED IN |
| STAIRWELLS. |
| |
| 12) KNOX BOXES WILL BE REQUIRED. |
| |
| 13) LOCKING CAPS ARE REQUIRED FOR FIRE |
| DEPARTMENT CONNECTIONS. |
| |
| 14) EMERGENCY LIGHTING SHALL BE PROVIDED |
| IN EXIT PASSAGEWAYS. SHT LS0.01 |
| |
| 15) THE EXIT SIGN APPEARS TO LEAD |
| PERSONS TO THE TRASH ROOM. SHEET LS0.02 |
| |
| 16) EXIT SIGNS TO BE CLEAR/VISIBLE AND |
| NOT TO EXCEED 100' APART. |
| |
| 17) CLARIFY GATE CONTROL AT STAIR #13. |
| SHT LSO.02 |
| |
| 18) PLEASE IDENTIFY ALL STRETCHER |
| ACCESSIBLE ELEVATORS WITH APPROPRIATE |
| SIGNAGE. |
| |
| 19) PLEASE IDENTIFY THE MARKING AROUND |
| THE ATRIUM. SHT LSO.03 |
| |
| 20) AN EXIT SIGN IS SHOWN IN FRONT OF A |
| PARKING SPACE? SHT LSO.04 |
| |
| 21) ELEVATOR WARNING SIGNS ARE REQUIRED. |
| |
| 22) MACHINE/EQUIPMENTROOMS SHALL HAVE |
| APPROPRIATE SIGNS INDICATING NO STORAGE. |
| |
| 23) EXIT SIGNS APPEAR TO BE MISSING FROM |
| A STORAGE AREA. SHT LSO.04 |
| |
| 24) PLEASE IDENTIFY ALL POOL CHEMICALS |
| IN POOL EQUIPMENT ROOM. LSO.04 |
| |
| 25) PANIC HARDWARE IS REQUIRED ON DOORS |
| IN AREAS THAT SERVE AN OCCUPANT LOAD |
| GREATER THAN 100. |
| |
| 26) OCCUPANT LOAD FACTORS DON'T APPEAR |
| TO CORRELATE WITH TOTAL PLAZA LOAD. |
| |
| 27) WHAT COOKING ACTIVITIES ARE PLANNED |
| FOR THE KITCHEN? |
| |
| 28) PLEASE INDICATE ON THE PLANS THAT |
| APPROPRIATE WALKING SURFACES ARE TO BE |
| SLIP RESISTANT. |
| |
| 29) TACTILE SIGNAGE IS MISSING ON SHT |
| LSO.05. |
| |
| 30) PLEASE INDICATE MINIMUM INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS. |
| |
| 31) PLEASE PROVIDE FINISH CLASSIFICATION |
| FOR FLOOR SURFACES. |
| |
| 32) ALL REQUIRED STAIRWELLS SHALL HAVE |
| STANDPIPE CONNECTIONS WITH 2 1/2" - 1 |
| 1/2" REDUCERS. |
| |
| 33) EXIT SIGNS ARE MISSING NEAR STAIRS |
| 1-A AND 2-A. SHT LSO.08 |
| |
| 34) SMOKE DETECTORS SHALL BE INSTALLED A |
| MINIMUM OF 3' FROM HVAC DIFFUSERS. |
| |
| 35) PLEASE ILLUSTRATE ATRIUM |
| REQUIREMENTS. SHT 1.02 C |
| |
| 36) PLEASE PROVIDE MORE DETAILS ON |
| AUTOMATIC DOORS. |
| |
| 37) PLEASE EXPLAIN EGRESS GATE. SHT 1.02 |
| |
| 38)PLEASE EXPLAIN WHERE FANS WILL |
| EXHAUST. PROVIDE DIMENSIONS WHERE |
| APPLICABLE. SHT A 1.02 NW |
| |
| 39) PARKING GARAGE TO COMPLY WITH NFPA |
| 88A AND FBC. |
| |
| 40) PLEASE PROVIDE STRENGTH REQUIREMENTS |
| FOR STEEL CABLE BARRIER. SHT A 1.02 |
| |
| 41) PLEASE PROVIDE HEIGHT AND OVERALL |
| DIMENSIONS FOR ATRIUM. |
| |
| 42) 2A- 10 B,C RATED FIRE EXTINGUISHERS |
| ARE REQUIRED AND SHALL BE MOUNTED AT |
| DISTANCES NOT TO EXCEED 75' APART. |
| |
| 43) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR GLASS GUARDRAIL. SHT A |
| 1.03 C |
| |
| 44) ALL FIRE DOORS AND WINDOWS TO COMPLY |
| WITH NFPA 80 AND FBC. |
| |
| 45) TRASH CHUTES TO COMPLY WITH NFPA 82 |
| REQUIREMENTS. |
| |
| 46) PLEASE PROVIDE OCCUPANT LOAD/FIXTURE |
| PLAN FOR HEALTH CLUB. SHT 1.04 |
| |
| 47) PLEASE PROVIDE FLAME SPREAD DETAILS |
| FOR CABANA MATERIAL. |
| |
| 48) PLEASE PROVIDE DETAILS AND PRODUCT |
| APPROVALS FOR 1 HOUR RATED GLASS SYSTEM. |
| SHT A 1.04 C |
| |
| 49) PLEASE PROVIDE A FIRE SAFETY PLAN TO |
| THE BUREAU OF FIRE PREVENTION PRIOR TO |
| CONSTRUCTION. |
| |
| 50) NO STORAGE IS PERMITTED IN EXIT |
| VESTIBULES. |
| |
| 51) PLEASE EXPLAIN TYPES OF BOILERS THAT |
| ARE PLANNED. |
| |
| 52) FIRE ALARM STROBES ARE REQUIRED IN |
| ALL COMMON BATHROOMS. |
| |
| 53) HANDRAILS ARE REQUIRED ON BOTH SIDES |
| OF STAIRS. |
| |
| 54) HANDRAILS ARE MISSING ON STAIRS NEAR |
| THE ELEVATED PLANTER AREA. SHT 1.05 |
| |
| 55) NO GAS OR BARBECUE GRILLES PARMITTED |
| TO BE USED ON BALCONIES. |
| |
| 56) ALL APPROPRIATE FIRE SEPARATIONS |
| SHALL BE GIVEN PRIORITY DURING |
| CONSTRUCTION. |
| |
| 57) ADDRESS NUMBER IS REQUIRED ON |
| BUILDING AND SHALL BE A MINIMUM OF 6" IN |
| HEIGHT AND CONTRASTING TO THE |
| BACKGROUND. |
| |
| 58) PLEASE EXPLAIN OPEN STORAGE IN |
| PARKING GARAGE. PLEASE INCLUDE CODE |
| REFERENCE THAT ALLOWS THIS ARRANGEMNENT. |
| |
| 59) ALL VERTICAL SHAFTS ARE REQUIRED TO |
| BE FIRE SPRINKLER PROTECTED. |
| |
| 60) BUILDING IS TO BE COMPLETELY FIRE |
| SPRINKLER PROTECTED. |
| |
| 61) STAIRS THAT ARE SUBJECT TO INCLEMENT |
| WEATHER SHALL BE SLIP RESISTANT. |
| |
| 62) COOLING TOWER TO COMPLY WITH NFPA |
| 214. |
| |
| 63) ALL PROPOSED SOFFITTS SHALL NOT |
| INTERFERE WITH THE OPERATION OF ANY |
| REQUYIRED FIRE SPRINKLER HEADS. |
| |
| 64) ALL RATED FIRE DOORS SHALL BE |
| EQUIPED WITH UL LISTED CLOSERS WHICH |
| SHALL CAUSE THE DOORS TO POSITIVELY |
| LATCH. |
| |
| 65) FIRE RATING IS MISSING FROM THE DOOR |
| SCHEDULE. SHT A 4.08. PLEASE VERIFY ON |
| OTHER SHEETS. |
| |
| 66) ARE THE AC CLOSET DOORS NOTED IN THE |
| HALLWAY RATED? |
| |
| 67) THE FIRE ALARM SYSTEM SHALL MEET THE |
| SURVIVABILITY REQUIREMENTS OF NFPA 72. |
| |
| 68) THE FIRE ALARM SYSTEM SHALL BE UL |
| CERTIFIED FOR CENTRAL STATION SERVICE. |
| |
| 69) MINIMUM OF 2 FDC'S ARE REQUIRED FOR |
| HIGHRISES. |
| |
| 70) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| ALARM SYSTEMS. |
| |
| 71) PLEASE EXPLAIN NOTE #1 REGARDING |
| SMOKE VENTS. |
| |
| 72) PLEASE PROVIDE MORE INFORMATION AND |
| FLAME SPREAD FOR FABRIC PANELS. SHT A |
| 7.01. |
| |
| 73) PLEASE SHOW ALL FDC'S ON PLANS. ALL |
| SHEETS DON'T CORRELATE. |
| |
| 74) FDV CABINETS IN THE PARKING GARAGE |
| TO REMAIN ACCESSIBLE AND UNOBSTRUCTED AT |
| ALL TIMES. |
| |
| 75) WHEN SUBMITTING FIRE SPRINKLER |
| DRAWINGS, PLEASE ILLUSTRATE ALL AREAS OF |
| COVERAGE ON SHEETS. |
| |
| 76) LIVING UNITS DON'T SHOW SPRINKLER |
| COVERAGE ON ALL APPROPRIATE SHEETS. |
| |
| 77) PLEASE PROVIDE MANUFACTURER SPEC |
| SHEETS FOR FIRE PUMP AND GENERATOR. |
| |
| 78) PLEASE REFERENCE NEWEST EDITIONS, |
| 2002 AND 2003 ON SHT SP-34. NFPA 13, 14, |
| 20 24. |
| |
| 79) FIRE PROTECTION HYDROSTATIC TESTS TO |
| BE AT 200 PSI FOR 2 HOURS. SHT SP- 34 |
| #9. |
| |
| 80) ARE CO DETECTORS TIED INTO THE FIRE |
| ALARM SYSTEM OR LOCAL AV DEVICE ONLY. |
| |
| 81) EXIT SIGNS APPEAR TO BE MISSING AT |
| SOME STAIRWELLS. |
| |
| 82) EXITS SIGNS ARE MISSING FROM EXIT |
| PASSAGEWAY NEAR TOWER #3. |
| |
| 83) SMOKE CONTROL PANEL SHALL DISPLAY A |
| GRAPHIC REPRESENTAION OF THE BUILDING |
| EQUIPMENT. HOA SWITCHES ONLY IS NOT |
| PERMITTED. |
| |
| 84) SMOKE DETECTORS IN LIVING UNITS |
| SHALL BE INTERCONNECTED. |
| |
| 85) DUCT SMOKE DETECTORS WHERE PROVIDED |
| SHALL INITIATE A FIRE ALARM CONDITION |
| WHEN ACTIVATED PER LOCAL REQUIREMENTS. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |