2005-09-14 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MORE DETAILS AND
 LOCATIONS OF ALL GATES. C-1, C-2.
  
 2) PLEASE CORRELATE LOCATIONS OF FIRE
 HYDRANTS ON APPROPRIATE SHEETS.
  
 3) PLEASE PROVIDE DETAILS AND FLAME
 SPREAD INFORMATION ON TENSILE FABRIC FOR
 CANOPY.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR GATES.
  
 5) ALL CONSTRUCTION, ALTERATION AND
 DEMOLOITION TO COMPLY WITH NFPA-241.
 CONSTRUCTION DEBRIS TO BE REMOVED DAILY.
  
 6) STAIRS SHALL BE MAINTAINED DURING
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDINGS REACH 3 STORIES OR 30' IN
 HEIGHT.
  
 8) ALL CUTTING/WELDING TO COMPLY WITH
 NFPA 51-B.
  
 9) ELECTONIC SWITCHES, CHAIN AND LOCK IS
 REQUIRED ON DOUBLE CHECK DETECTOR
 ASSEMBLY.
  
 10) WORK TO COMPLY WITH HIGHRISE
 REQUIREMENTS IN ACCORDANCE WITH FBC AND
 NFPA 101, SECTION 11.
  
 11) TACTILE SIGNAGE IS REQUIRED IN
 STAIRWELLS.
  
 12) KNOX BOXES WILL BE REQUIRED.
  
 13) LOCKING CAPS ARE REQUIRED FOR FIRE
 DEPARTMENT CONNECTIONS.
  
 14) EMERGENCY LIGHTING SHALL BE PROVIDED
 IN EXIT PASSAGEWAYS. SHT LS0.01
  
 15) THE EXIT SIGN APPEARS TO LEAD
 PERSONS TO THE TRASH ROOM. SHEET LS0.02
  
 16) EXIT SIGNS TO BE CLEAR/VISIBLE AND
 NOT TO EXCEED 100' APART.
  
 17) CLARIFY GATE CONTROL AT STAIR #13.
 SHT LSO.02
  
 18) PLEASE IDENTIFY ALL STRETCHER
 ACCESSIBLE ELEVATORS WITH APPROPRIATE
 SIGNAGE.
  
 19) PLEASE IDENTIFY THE MARKING AROUND
 THE ATRIUM. SHT LSO.03
  
 20) AN EXIT SIGN IS SHOWN IN FRONT OF A
 PARKING SPACE? SHT LSO.04
  
 21) ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 22) MACHINE/EQUIPMENTROOMS SHALL HAVE
 APPROPRIATE SIGNS INDICATING NO STORAGE.
  
 23) EXIT SIGNS APPEAR TO BE MISSING FROM
 A STORAGE AREA. SHT LSO.04
  
 24) PLEASE IDENTIFY ALL POOL CHEMICALS
 IN POOL EQUIPMENT ROOM. LSO.04
  
 25) PANIC HARDWARE IS REQUIRED ON DOORS
 IN AREAS THAT SERVE AN OCCUPANT LOAD
 GREATER THAN 100.
  
 26) OCCUPANT LOAD FACTORS DON'T APPEAR
 TO CORRELATE WITH TOTAL PLAZA LOAD.
  
 27) WHAT COOKING ACTIVITIES ARE PLANNED
 FOR THE KITCHEN?
  
 28) PLEASE INDICATE ON THE PLANS THAT
 APPROPRIATE WALKING SURFACES ARE TO BE
 SLIP RESISTANT.
  
 29) TACTILE SIGNAGE IS MISSING ON SHT
 LSO.05.
  
 30) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 31) PLEASE PROVIDE FINISH CLASSIFICATION
 FOR FLOOR SURFACES.
  
 32) ALL REQUIRED STAIRWELLS SHALL HAVE
 STANDPIPE CONNECTIONS WITH 2 1/2" - 1
 1/2" REDUCERS.
  
 33) EXIT SIGNS ARE MISSING NEAR STAIRS
 1-A AND 2-A. SHT LSO.08
  
 34) SMOKE DETECTORS SHALL BE INSTALLED A
 MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 35) PLEASE ILLUSTRATE ATRIUM
 REQUIREMENTS. SHT 1.02 C
  
 36) PLEASE PROVIDE MORE DETAILS ON
 AUTOMATIC DOORS.
  
 37) PLEASE EXPLAIN EGRESS GATE. SHT 1.02
  
 38)PLEASE EXPLAIN WHERE FANS WILL
 EXHAUST. PROVIDE DIMENSIONS WHERE
 APPLICABLE. SHT A 1.02 NW
  
 39) PARKING GARAGE TO COMPLY WITH NFPA
 88A AND FBC.
  
 40) PLEASE PROVIDE STRENGTH REQUIREMENTS
 FOR STEEL CABLE BARRIER. SHT A 1.02
  
 41) PLEASE PROVIDE HEIGHT AND OVERALL
 DIMENSIONS FOR ATRIUM.
  
 42) 2A- 10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' APART.
  
 43) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR GLASS GUARDRAIL. SHT A
 1.03 C
  
 44) ALL FIRE DOORS AND WINDOWS TO COMPLY
 WITH NFPA 80 AND FBC.
  
 45) TRASH CHUTES TO COMPLY WITH NFPA 82
 REQUIREMENTS.
  
 46) PLEASE PROVIDE OCCUPANT LOAD/FIXTURE
 PLAN FOR HEALTH CLUB. SHT 1.04
  
 47) PLEASE PROVIDE FLAME SPREAD DETAILS
 FOR CABANA MATERIAL.
  
 48) PLEASE PROVIDE DETAILS AND PRODUCT
 APPROVALS FOR 1 HOUR RATED GLASS SYSTEM.
 SHT A 1.04 C
  
 49) PLEASE PROVIDE A FIRE SAFETY PLAN TO
 THE BUREAU OF FIRE PREVENTION PRIOR TO
 CONSTRUCTION.
  
 50) NO STORAGE IS PERMITTED IN EXIT
 VESTIBULES.
  
 51) PLEASE EXPLAIN TYPES OF BOILERS THAT
 ARE PLANNED.
  
 52) FIRE ALARM STROBES ARE REQUIRED IN
 ALL COMMON BATHROOMS.
  
 53) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS.
  
 54) HANDRAILS ARE MISSING ON STAIRS NEAR
 THE ELEVATED PLANTER AREA. SHT 1.05
  
 55) NO GAS OR BARBECUE GRILLES PARMITTED
 TO BE USED ON BALCONIES.
  
 56) ALL APPROPRIATE FIRE SEPARATIONS
 SHALL BE GIVEN PRIORITY DURING
 CONSTRUCTION.
  
 57) ADDRESS NUMBER IS REQUIRED ON
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 58) PLEASE EXPLAIN OPEN STORAGE IN
 PARKING GARAGE. PLEASE INCLUDE CODE
 REFERENCE THAT ALLOWS THIS ARRANGEMNENT.
  
 59) ALL VERTICAL SHAFTS ARE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 60) BUILDING IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED.
  
 61) STAIRS THAT ARE SUBJECT TO INCLEMENT
 WEATHER SHALL BE SLIP RESISTANT.
  
 62) COOLING TOWER TO COMPLY WITH NFPA
 214.
  
 63) ALL PROPOSED SOFFITTS SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY
 REQUYIRED FIRE SPRINKLER HEADS.
  
 64) ALL RATED FIRE DOORS SHALL BE
 EQUIPED WITH UL LISTED CLOSERS WHICH
 SHALL CAUSE THE DOORS TO POSITIVELY
 LATCH.
  
 65) FIRE RATING IS MISSING FROM THE DOOR
 SCHEDULE. SHT A 4.08. PLEASE VERIFY ON
 OTHER SHEETS.
  
 66) ARE THE AC CLOSET DOORS NOTED IN THE
 HALLWAY RATED?
  
 67) THE FIRE ALARM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 68) THE FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 69) MINIMUM OF 2 FDC'S ARE REQUIRED FOR
 HIGHRISES.
  
 70) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 71) PLEASE EXPLAIN NOTE #1 REGARDING
 SMOKE VENTS.
  
 72) PLEASE PROVIDE MORE INFORMATION AND
 FLAME SPREAD FOR FABRIC PANELS. SHT A
 7.01.
  
 73) PLEASE SHOW ALL FDC'S ON PLANS. ALL
 SHEETS DON'T CORRELATE.
  
 74) FDV CABINETS IN THE PARKING GARAGE
 TO REMAIN ACCESSIBLE AND UNOBSTRUCTED AT
 ALL TIMES.
  
 75) WHEN SUBMITTING FIRE SPRINKLER
 DRAWINGS, PLEASE ILLUSTRATE ALL AREAS OF
 COVERAGE ON SHEETS.
  
 76) LIVING UNITS DON'T SHOW SPRINKLER
 COVERAGE ON ALL APPROPRIATE SHEETS.
  
 77) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND GENERATOR.
  
 78) PLEASE REFERENCE NEWEST EDITIONS,
 2002 AND 2003 ON SHT SP-34. NFPA 13, 14,
 20 24.
  
 79) FIRE PROTECTION HYDROSTATIC TESTS TO
 BE AT 200 PSI FOR 2 HOURS. SHT SP- 34
 #9.
  
 80) ARE CO DETECTORS TIED INTO THE FIRE
 ALARM SYSTEM OR LOCAL AV DEVICE ONLY.
  
 81) EXIT SIGNS APPEAR TO BE MISSING AT
 SOME STAIRWELLS.
  
 82) EXITS SIGNS ARE MISSING FROM EXIT
 PASSAGEWAY NEAR TOWER #3.
  
 83) SMOKE CONTROL PANEL SHALL DISPLAY A
 GRAPHIC REPRESENTAION OF THE BUILDING
 EQUIPMENT. HOA SWITCHES ONLY IS NOT
 PERMITTED.
  
 84) SMOKE DETECTORS IN LIVING UNITS
 SHALL BE INTERCONNECTED.
  
 85) DUCT SMOKE DETECTORS WHERE PROVIDED
 SHALL INITIATE A FIRE ALARM CONDITION
 WHEN ACTIVATED PER LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  