Date |
Text |
2005-09-10 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05071027 |
| ADD: 2211 N FLAGLER DR |
| CONT: PLAN REVIEW |
| OWNER: MERCO GROUP |
| TEL: (561)296-3300 |
| ARCH: SONG & ASSOC/ JOHN STRNDBERG |
| |
| TEL: (561) 655-2423 |
| |
| -PALADIO TERRACE- |
| |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) ALTHOUGH THERE IS A FOUNDATION PERMIT |
| PLEASE SUBMIT THE FOLLOWING ITEMS SINCE |
| THE FOUNDATION AND BUILDING PERMITS ARE |
| STAND ALONE PERMITS. |
| A) SOILS REPORT (3) |
| B) THRESHOLD INSPECTION PLAN (3) |
| C) THRESHOLD INSPECTOR AGREEMENT(1) |
| D) NOTICE OF COMENCEMENT (1) |
| E) UNITY OF TITLE |
| F) PROVIDE A SITE PLAN W/ BUILDING LINE |
| |
| VS. THE PROPERTY LINE. |
| |
| 2) LS0.00 CODE ANALYSIS IS MISSING: |
| 2A) 412.3.3 FIRE DEPARTMENT |
| COMMUNICATION SYSTEM. A TWO-WAY FIRE |
| DEPARTMENT COMMUNICATION SYSTEM SHALL BE |
| PROVIDED FOR FIRE DEPARTMENT USE. |
| IT SHALL OPERATE BETWEEN THE FIRE |
| COMMAND STATION AND EVERY ELEVATOR, |
| ELEVATOR LOBBY, ENTRY TO EVERY ENCLOSED |
| EXIT STAIRWAY AND IN CORRIDORS. |
| |
| 412.3.4 COMBINED SYSTEM. WHEN APPROVED, |
| THE FIRE DEPARTMENT COMMUNICATIONS |
| SYSTEM MAY BE COMBINED WITH THE VOICE |
| ALARM SIGNALING SYSTEM. |
| |
| FIRE COMMAND STATION |
| |
| 412.4.1 A FIRE COMMAND STATION FOR |
| FIRE DEPARTMENT OPERATIONS SHALL BE |
| PROVIDED IN A LOCATION APPROVED BY THE |
| FIRE DEPARTMENT. |
| |
| 412.4.3 A FIRE COMMAND STATION SHALL |
| CONTAIN: |
| |
| 1. CONTROLS FOR THE ONE-WAY VOICE |
| ALARM SYSTEM. |
| |
| 2. CONTROLS FOR THE TWO-WAY FIRE |
| DEPARTMENT COMMUNICATION SYSTEM. |
| |
| 3. FIRE ALARM SYSTEM ANNUNCIATOR |
| PANELS. |
| |
| 4. STATUS INDICATORS SHOWING |
| LOCATION OF ELEVATORS IN THE HOISTWAYS |
| AND |
| SWITCHES TO SELECTIVELY TURN |
| POWER TO ELEVATORS ON OR OFF. |
| |
| 5. STATUS INDICATORS AND CONTROLS |
| FOR AIR HANDLING SYSTEMS. |
| |
| 6. CONTROLS FOR UNLOCKING ALL |
| STAIRWAY DOORS SIMULTANEOUSLY. |
| |
| 7. SPRINKLER VALVE, WATERFLOW |
| DETECTOR AND FIRE PUMP DISPLAY PANELS. |
| |
| 8. EMERGENCY POWER, LIGHT AND |
| EMERGENCY SYSTEM CONTROLS AND STATUS |
| INDICATORS. |
| |
| 9. A TELEPHONE FOR FIRE DEPARTMENT |
| USE WITH CONTROLLED ACCESS TO THE |
| PUBLIC TELEPHONE SYSTEM. |
| |
| 10. GENERATOR SUPERVISION DEVICES, |
| MANUAL START AND TRANSFER FEATURES. |
| |
| PLANS INDICATE THAT THEY WILL COMPLY |
| WITH FBC CHAPTER 9, SECTION 412.3 & NFPA |
| 72-2002. 104.2.1 W.P.B. ADMINISTRATIVE |
| CODE DRAWINGS & SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF |
| NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| *************** |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". PLEASE PROVIDE ADDITIONAL |
| INFORMATION FOR CODE COMPLIANCE. |
| *************** |
| |
| 2B)SMOKE CONTROL 412.5 |
| PROVIDE CODE COMPLIANCE. IF SYSTEM IS TO |
| COMPLY WITH (3) 412.7.2).UNDER FIRE |
| CONDITIONS, THE RETURN AND EXHAUST AIR |
| SHALL BE MOVED DIRECTLY TO THE |
| OUTSIDE WITHOUT RECIRCULATION TO OTHER |
| SECTIONS OF THE BUILDING.THE AIR |
| HANDLING SYSTEM SHALL HAVE THE |
| CAPABILITY OF PROVIDING A MINIMUM OF ONE |
| EXHAUST AIR CHANGE EVERY 10 MINUTES FOR |
| ANY AREA WHICH MIGHT BE INVOLVED. |
| |
| 3) LS0.03 HAS THE TERM "TOWNHOUSE" |
| DESCRIBING R2 UNITS. THESE UNITS ARE |
| CONDOMINIUMS NOT TOWNHOUSES. THE FL BLDG |
| CODE 2001 DEFINITION OF TOWNHOUSE IS: |
| 202.TOWNHOUSE. A SINGLE FAMILY DWELLING |
| CONSTRUCTED IN A SERIES OR GROUP OF |
| ATTACHED UNITS WITH PROPERTY LINES |
| SEPARATING EACH UNIT. |
| IF TRUELY TOWNHOUSE CONSTRUCTION, |
| PROVIDE THE RECORDED PLAT PLAN WWITH |
| SEPERATE LOTS, OTHERWISE REMOVE TREM |
| FROM ALL DOCUMENTS. |
| |
| 4) CONDO UNITS 1-14 (TOWNHOUSE UNITS) |
| ARE TO COMPLY WITH FAIR HOUSING MANUAL |
| REVISED APRIL 1998, PAGE 1.32. BUILDINGS |
| WITH ONE OR MORE COMMON ENTRANCES TO ALL |
| DWELLING UNITS IN BUILDINGS WITH ONE OR |
| MORE ELEVATORS. AT LEAST ONE COMMON |
| ENTRANCE SHALL BE ON AN ACCESSIBLE |
| ROUTE. SITE IMPRACTICABILITY TEST DOES |
| NOT APPLY TO ELEVATORED BUILDINGS. |
| PROVIDE ON THE LIFE SAFETY PLAN THE |
| ACCESSIBLE ROUTE FROM THE ELEVATOR TO |
| THESE UNITS. |
| |
| 5) THESE UNITS ARE MISSING EXIT ACCESS |
| CORRIDORS, EXIT ACCESS. THAT PORTION OF |
| A MEANS OF EGRESS WHICH LEADS TO AN |
| ENTRANCE TO AN EXIT. |
| |
| SEE MEANS OF EGRESS DEFINITIONS, MEANS |
| OF EGRESS. A CONTINUOUS AND UNOBSTRUCTED |
| WAY OF EXIT TRAVEL FROM ANY POINT IN A |
| BUILDING OR STRUCTURE TO A PUBLIC WAY, |
| CONSISTING OF THREE SEPARATE AND |
| DISTINCT PARTS: (1) THE WAY OF EXIT |
| ACCESS, (2) THE EXIT, AND (3) THE WAY OF |
| EXIT DISCHARGE. A MEANS OF EGRESS |
| COMPRISES THE VERTICAL AND HORIZONTAL |
| WAYS OF TRAVEL AND SHALL INCLUDE THE |
| INTERVENING ROOM SPACE, DOORS, |
| CORRIDORS, PASSAGEWAYS, BALCONIES, |
| STAIRS, RAMPS, ENCLOSURES, LOBBIES, |
| HORIZONTAL EXITS, COURTS AND YARDS. |
| PROVIDE EXIT ACCESS CORRIDORS FOR |
| UNITS 1-14 COMPLING WITH TABLE 1004 |
| TRAVEL DISTANCES FOR R2/ SPRINKLERED |
| BUILDINGS MAXIMUM TRAVEL DISTANCE OF |
| 325 FT TO AN EXIT. |
| |
| RESIDENTIAL UNITS 101-105 ARE AT |
| GRADE LEVEL AND WILL NOT REQUIRE EXIT |
| ACCESS CORRIDORS SINCE THEY CAN EXIT AT |
| STREET LEVEL AND GO DIRECTLY TO THE WAY |
| OF THE EXIT DISCHARGE. |
| |
| 6) A0.02 NOTE# 35 CABANA CANVAS TO BE |
| REMOVED AT 75MPH, STRUCTURES ARE TO BE |
| DESIGNED FOR 140 MPH WIND ZONE.SEE |
| FIGURE 1606. |
| |
| 7A) A1.02C PLANS INDICATE A VALET DRIVE |
| & A DROP OFF ZONE WITH A ZERO CURB |
| PASSENGER DROP OFF. PROVIDE MORE |
| INFORMATION ON THE DROP OFF ZONE. SHOW |
| COMPLIANCE WITH FL ACCESSIBILITY FOR |
| ACCESS AILSLE AT PASSENGER LOADING ZONES |
| FIGURE 10 TO BE 240" LONG(ZERO CURB) AND |
| 60" WIDE. 11-4.1.2(1)/ 11-4.6.6. |
| |
| 7B)A1.02NE & A1.02SE VALET DRIVE |
| INDICATES "MAINTAIN 8'-0" MINIMUM |
| CLEARENCE THROUGHOUT VALET DRIVE". |
| 11-4.6.5 VERTICAL CLEARANCE. PROVIDE |
| MINIMUM VERTICAL CLEARANCE OF 114 " |
| (2895 MM) AT ACCESSIBLE PASSENGER |
| LOADING ZONES AND ALONG AT LEAST ONE |
| VEHICLE ACCESS ROUTE TO SUCH AREAS FROM |
| SITE ENTRANCE(S) AND EXIT(S). |
| |
| 7C)11-4.1.2(7) BUILDING SIGNAGE. SIGNS |
| WHICH DESIGNATE PERMANENTROOMS AND |
| SPACES SHALL COMPLY WITH 11-4.30.1, |
| 11-4.30.4, 11-4.30.5 AND 11-4.30.6. |
| OTHER SIGNS WHICH PROVIDE DIRECTION TO, |
| OR INFORMATION ABOUT, FUNCTIONAL SPACES |
| OF THE BUILDING SHALL COMPLY WITH |
| 11-4.30.1, 11-4.30.2, 11-4.30.3, AND |
| 11-4.30.5.ELEMENTS AND SPACES OF |
| ACCESSIBLE FACILITIES WHICH SHALL BE |
| IDENTIFIED BY THE INTERNATIONAL SYMBOL |
| OF ACCESSIBILITY AND WHICH SHALL COMPLY |
| WITH 11-4.30.7 ARE: |
| 11-4.1.2(7)(A) PARKING SPACES DESIGNATED |
| AS RESERVED FOR INDIVIDUALS WITH |
| DISABILITIES; |
| 11-4.1.2(7)(B) ACCESSIBLE PASSENGER |
| LOADING ZONES; |
| 11-4.1.2(7)(C) ACCESSIBLE ENTRANCES WHEN |
| NOT ALL ARE ACCESSIBLE (INACCESSIBLE |
| ENTRANCES SHALL HAVE DIRECTIONAL SIGNAGE |
| TO INDICATE THE ROUTE TO THE NEAREST |
| ACCESSIBLE ENTRANCE); |
| 11-4.1.2(7)(D) ACCESSIBLE TOILET AND |
| BATHING FACILITIES WHEN NOT ALL ARE |
| ACCESSIBLE. |
| |
| 7D) FOR ALL GROUPINGS OF ELEVATORS SHOW |
| COMPLIANCE WITH; |
| 3003.4 STRETCHER REQUIREMENTS |
| 3003.4.1 IN ALL STRUCTURES THAT ARE |
| MORE THAN THREE STORIES HIGH OR IN |
| WHICH THE VERTICAL DISTANCE BETWEEN THE |
| BOTTOM TERMINAL LANDING AND THETOP |
| TERMINAL LANDING EXCEEDS 25 FEET (7.6 M) |
| MUST BE CONSTRUCTED TOCONTAIN AT |
| LEAST ONE PASSENGER ELEVATOR THAT IS |
| OPERATIONAL AND WILL ACCOMMODATE AN |
| AMBULANCE STRETCHER 76 INCHES (1931 MM) |
| LONG AND 24 INCHES (610 MM) WIDE IN THE |
| HORIZONTAL POSITION.THIS ELEVATOR |
| SHALL BE IDENTIFIED. |
| |
| 7E) 3003.3 SIGNS. A PERMANENT SIGN SHALL |
| BE INSTALLED IMMEDIATELY ABOVE EACH |
| HALL PUSH BUTTON STATION ON EACH FLOOR |
| READING:IN FIRE EMERGENCY, DO NOT |
| USE ELEVATOR.USE EXIT STAIRS.THIS |
| SIGN SHALL BE LETTERS NOT LESS THAN |
| 1/2 INCH (12.7 MM) HIGH. |
| |
| |
| 7F)EACH ELEVATOR MUST BE MADE |
| ACCESSIBLE TO PHYSICALLY HANDICAPPED |
| PERSONS WITH THE FOLLOWING REQUIREMENTS: |
| OF 3003.4.2 (1-3) |
| |
| 7G) PROVIDE DETAILS HOW IN EACH GROUP OF |
| 2 ELEVATORS ONE WILL COMPLY WITH: |
| 3003.5 STANDBY POWER. IN ALL BUILDINGS |
| OR STRUCTURES WHERE STANDBY POWER |
| IS REQUIRED OR FURNISHED TO OPERATE AN |
| ELEVATOR, THE OPERATION SHALL BE AS |
| FOLLOWS: |
| |
| 1. WHERE ONLY ONE ELEVATOR IS |
| INSTALLED, THE ELEVATOR SHALL TRANSFER |
| TO STANDBY POWER WITHIN 60 SECONDS AFTER |
| FAILURE OF NORMAL POWER. |
| 2. WHERE TWO OR MORE ELEVATORS ARE |
| CONTROLLED BY A COMMON OPERATING |
| SYSTEM, ALL ELEVATORS MAY TRANSFER TO |
| STANDBY POWER WITHIN 60 SECONDS AFTER |
| FAILURE OF NORMAL POWER; OR IF THE |
| STANDBY POWER SOURCE IS OF |
| INSUFFICIENT CAPACITY TO OPERATE ALL |
| ELEVATORS AT THE SAME TIME, ALL |
| ELEVATORS SHALL TRANSFER TO STANDBY |
| POWER IN SEQUENCE, RETURN TO THE |
| DESIGNATED LANDING AND DISCHARGE THEIR |
| LOAD.AFTER ALL ELEVATORS HAVE BEEN |
| RETURNED TO THE DESIGNATED LANDING, AT |
| LEAST ONE ELEVATOR SHALL REMAIN OPERABLE |
| FROM THE STANDBY POWER SOURCE. |
| |
| 8A) INDICATE COMPLIANCE WITH: VAN |
| PARKING:11-4.1.2(5)(B) IN PARKING |
| STRUCTURES, ONE IN EVERY EIGHT |
| ACCESSIBLE SPACES, BUT NOT LESS THAN |
| ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL |
| BE DESIGNED AS REQUIRED BY 11-4.6.3. |
| THE VERTICAL CLEARANCE AT SUCH SPACES |
| SHALL COMPLY WITH 11-4.6.5.ALL SUCH |
| SPACES MAY BE GROUPED ON ONE LEVEL OF A |
| PARKING STRUCTURE.WHEN SUCH SPACES ARE |
| PROVIDED IN A PARKING STRUCTURE AND ONLY |
| ONE IN EIGHT MEET THE HEIGHT REQUIREMENT |
| OF 11-4.6.5 (98")AT THE PARKING SPACE |
| AND ALONG AT LEAST ONE VEHICLE |
| ACCESSIBLE ROUTE TO SUCH SPACES FROM |
| SITE ENTRANCES AND EXITS, THEY SHALL BE |
| DESIGNATED AS REQUIRED BY 11-4.6.4. |
| |
| 9) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEETS A1.02 NORTH VALET DRIVE INDICATES |
| A "TILT UP SERVICE DOOR": |
| |
| 9A) PROVIDE DETAILS OF THIS UNIT, AND |
| WHAT IT WILL BE USED FOR? |
| |
| 9B) IT APPEARS THERE MAY BE A DISCEPANCY |
| BETWEEN THE TILT UP DOOR AND THE |
| UNDERGROUND PASSAGE WAY. LS0.02 |
| INDICATES THIS UNIT DIRECTLY OVER THE |
| UNDERGROUND EXIT!LS0.01 DOESN'T INDICATE |
| ANY OTHER STRUCTURE IN THIS AREA? |
| |
| 10A) SHEET A1.02SE & A1.02NE INDICATE A |
| PEDESTRAIN CROSS WALK ON THE VALET DRIVE |
| AND A CROSS SECTION #6 ON A3.12. THIS |
| SECTION INDICATES THIS TO BE A RAISED |
| CROSS WALK RATHER THAN CURB CUTS WITH |
| A DESIGNATED EGRESS LANE. SINCE THIS IS |
| A ELEVATED SLAB INDICATE THE HEIGHT |
| DIFFERENCE BETWEEN THE CROSS WALK AND |
| ADJACENT DRIVE? IT APPEARS THE CROSS |
| WALKS RAMPS MAY NOT MEET THE 1:20 |
| ADJOINING SLOPE REQUIREMENTS. |
| |
| 10B)11-4.7.7 DETECTABLE WARNINGS. A CURB |
| RAMP SHALL HAVE A DETECTABLEWARNING |
| COMPLYING WITH 11-4.29.2.THE |
| DETECTABLE WARNING SHALL EXTEND THE FULL |
| WIDTH AND DEPTH OF THE CURB RAMP. |
| |
| 10C)11-4.29.2(2) DETECTABLE WARNING |
| TEXTURES ON WALKING SURFACES SHALL |
| CONSIST OF EXPOSED AGGREGATE CONCRETE, |
| CUSHIONED SURFACES MADE OF RUBBER OR |
| PLASTIC, RAISED STRIPS, OR GROOVES. |
| TEXTURES SHALL CONTRAST WITH THAT OF THE |
| SURROUNDING SURFACE.RAISED STRIPS OR |
| GROOVES SHALL COMPLY WITH FIGURE |
| 11-40(A) AND FIGURE 11-40(B). |
| |
| 10D) BOTH SHEETS A1.02NE & A1.02SE BOTH |
| INDICATE THE USE OF HORIZONTAL SLIDING |
| DOORS C-0101-C & C-0101-E, 1012.4(9) 9. |
| IN APARTMENT BUILDINGS, HOTELS AND |
| DORMITORIES, HORIZONTAL SLIDING DOORS |
| SHALL NOT BE USED ACROSS CORRIDORS. |
| |
| 11)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A1.02 NE UNITS 18& 19 APPEAR TO |
| HAVE (3) COLUMNS JUST TO THE SOUTH OF |
| THESE UNITS. JUST EAST OF THESE COLUMNS |
| THERE IS A GATE, THERE IS ONLY 18" |
| BETWEEN THE COLUMNS AND WALL LINE. WITH |
| THE GATE IN THIS PLAN IT APPEARS THAT |
| THIS AREA IS TO BE USED FOR A WALKWAY? |
| EXPLAIN RATIONAL? |
| |
| 12) A1-04 HAS 2 AREAS NAMED OPEN STORAGE |
| THAT ARE IN COMMON TO THE ENCLOSED |
| PARKING AREAS. SEE 411.2.6 AUTOMOBILE |
| PARKING GARAGES SHALL BE SEPARATED FROM |
| OTHER OCCUPANCIES IN ACCORDANCE WITH |
| 704. PROVIDE WHAT TYPE OF STORAGE WILL |
| TAKE PLACE IN THESE AREAS, RATE DOORS |
| ACCORDINGLY. |
| |
| 13) A1.04 THE REFUSE CHUTE ACCESS ROOM: |
| |
| 13A) PLANS DO NOT INDICATE AN ACCESS |
| ROOM DOOR NOR IS THERE A CUT SECTION |
| PROVIDING A HORIZONTAL SECTION OF THE |
| CHUTE, WALL RATINGS AND DOOR RATINGS |
| . |
| 13B) 705.2.4.3 REFUSE CHUTES SHALL BE |
| LOCATED IN ROOMS OR COMPARTMENTS |
| COMPLETELY ENCLOSED BY CONSTRUCTION AND |
| OPENING PROTECTIVES IN ACCORDANCE WITH |
| TABLE 705.1.2. SHOW COMPLIANCE, ALSO SEE |
| NFPA 82 5.2.5.3.3.THIS IS TAKEN WITH THE |
| REFUSE CHUTE DOOR OPEN!!!! |
| |
| 13C) PROVIDE DETAILS FOR FIRE SPRINKLERS |
| IN ACCORDANCE WITH: |
| 705.2.4.6 AUTOMATIC SPRINKLERS. AN |
| APPROVED AUTOMATIC SPRINKLER SYSTEM |
| SHALL BE INSTALLED AT THE TOP AND AT |
| ALTERNATE FLOOR LEVELS IN REFUSE AND |
| LAUNDRY CHUTES AND IN THE TERMINATION |
| AND INCINERATOR ROOMS. |
| |
| 14) PLANS DO NOT HAVE A DOOR SCHEDULE . |
| 14A)RATED DOORS SHALL COMPLY WITH TABLE |
| 705.1.2 |
| 14B) RATED DOORS ARE TO SHOW CLOSING |
| DEVICES, HARDWARE, FRAMES AND SILLS |
| INACCORDANCE WITH 705.1.3 AND UNDER CUT |
| AS TO NFPA 80. |
| |
| 15) PLANS DO NOT HAVE A FINISH SCHEDULE |
| FOR THE COMMON AREAS. |
| |
| 16) A1.04C THERE IS A TRUE ISSUE OF THE |
| ATRIUM VERSUS THE ELEVATOR LOBBY.BY |
| DEFINITION, ATRIUM. A SPACE, INTENDED |
| FOR OCCUPANCY WITHIN A BUILDING, |
| EXTENDING VERTICALLY THROUGH THE |
| BUILDING AND ENCLOSED AT THE TOP.SINCE |
| THE 3RD FLOOR IS ENCLOSED BY GLASS, THIS |
| TRUELY MAKES A SHAFT SEPERATING IT FROM |
| THE REST OF THE BUILDING. |
| SINCE THIS IS A HIGH RISE, AND THE |
| SHAFT SEPERATES THIS AREA REMOVING THE |
| ATRIUM THEORY,412.6.1 CAN NOT TAKE THE |
| EXEMPTION FOR ATRIUMS MAKING AN ELEVATOR |
| LOBBY REQUIRED FOR FLOORS 2,3 & 4. |
| 16B) FOR INFORMATION AS TO SMOKE CONTROL |
| FOR THE ATRIUM THE MECHANICAL PLANS |
| INDICATE ON PAGE AC-01 AC-02 TO SEE |
| SHEET AC-20 FOR WORK IN THIS AREA, THIS |
| PAGE IS FOR THE PENTHOUSE SUITES? |
| 16C) PROVIDE THE AMOUNT OF CU FT OF AIR |
| INCLUDED UNDER THE ATRUIM SMOKE CONTROL |
| SYSTEM SEE 414.4.2 AND SHOW COMPLIANCE. |
| (C)(1) LS0.03 PROVIDES THE TENANT |
| SEPERATION WALLS AND OR FIRE SEPERATION |
| WALLS. 414.5 ATRIUM SPACES SHALL |
| SEPERATED FROM ADJACENT SPACES BY A |
| 1-HR FIRE SEPERATION WALL. THE |
| MECHANICAL PLAN DOESN'T INDICATE ANY |
| FIRE DAMPERS SO THESE AREAS? |
| 16D) PROVIDE INFORMATION FOR AUTOMATIC |
| FIRE DETECTION IN ACCORDANCE WITH |
| 414.6.1 SPOT-TYPE DETECTORS OR BEAM |
| DETECTORS. |
| 16D) PROVIDE INFORMATION, 414.7 STANDBY |
| POWER. ALL EQUIPMENT REQUIRED TO PROVIDE |
| SMOKE CONTROL SHALL BE CONNECTED TO A |
| STANDBY POWER SYSTEM IN ACCORDANCE WITH |
| 412.7. |
| 16E) 414.10 INTERIOR FINISH. THE |
| INTERIOR FINISH OF WALLS AND CEILINGS OF |
| THE ATRIUM SHALL NOT EXCEED CLASS B WITH |
| NO REDUCTION IN CLASS FOR SPRINKLER |
| PROTECTION. |
| 16F) PLEASE PROVIDE AREA CALCULATIONS |
| FOR THE FIRST FLOOR OF THE ATRIUM AND |
| THE MEZZANINE LEVEL 503.2.3.2. |
| 16G) MEZZANINE LEVEL MUST MEET THE |
| REQUIREMENTS OF 1005.7.3 THE SPACE |
| BENEATH THE MEZZANINE MAY BE ENCLOSED |
| PROVIDEDTHE ENCLOSED SPACE IS |
| PROTECTED THROUGHOUT WITH A SMOKE |
| DETECTION SYSTEM IN ACCORDANCE WITH NFPA |
| 72 WHICH SOUNDS AN ALARM IN THE |
| MEZZANINE. |
| |
| 17) A1.04C THE STAIR TOWERS TO THE LEFT |
| AND RIGHT OF THE CENTER ASSEMBLY AREA |
| HAVE EXIT ACCESS CORRIDORS WITH DOORS |
| # 0302 N&S. WHAT IS THIS ROOM TO BE USED |
| FOR. IF THIS IS SHAFT INDICATE SUCH. |
| ALSO NO DOOR SCHEDULE TO INDICATE |
| RATING. |
| |
| 18) THESE SAME STAIR TOWERS INDICATE A |
| CIRCLE AND SQUARE IN THE LANDINGS OF THE |
| STAIR TOWER BUT NOT SHOWN ON THE |
| ENLARGED PLANS A5.07 & A5.08? |
| |
| 19) A1.04 INDICATES A HEALTH CLUB NO |
| WALLS NOR DOORS SHOW RATINGS.A 5.15 |
| PROVIDES ELEVATIONS BUT NO CROSS SECTION |
| SHOWING COMPLIANCE WITH A 2HR SHAFT. |
| |
| 20) A1.04NE : |
| A) ELEVATOR LOBBY# 7 HAS SOME |
| UNIDENTIFIED ITEM WITH A DOOR IN LOBBY? |
| B) THERE IS NO ELEVATOR LOBBY DOOR |
| SEPERATING THE LOBBY FROM THE REST OF |
| THE FLOOR. |
| C) TELEPHONE ROOM APPEARS TO HAVE NO |
| DOOR IT APPEARS TO HAVE THE REFUSE CHUTE |
| IN THE SAME ROOM? |
| D) ELEVATOR TOWERS# 3&5 INDICATES 2 |
| DISTINCT ELEVATOR LOBBIES BUT ENTRANCE |
| IS ONLY ON ONE SIDE? |
| E) IN FRONT OF UNIT 0317 THERE IS A |
| AREA THAT APPEARS TO BE A SHAFT?NO |
| DETAILS OR CUT SECTIONS TO INDICATE |
| USAGE. |
| |
| 21) A1.04 NW : |
| A) THERE APPEARS TO BE A PASSENGER |
| LOADING ZONE IN THE GARAGE JUST SOUTH OF |
| ELEVATOR# 7, PROVIDE PASSENGER LOADING |
| ZONE, AND ACROSS ELEVATION SECTION |
| INDICATING CLEAR HEIGHT. |
| B) NORTH END OF THE PARKING GARAGE HAS |
| AN OPEN STORAGE AREA, THERE IS NO |
| OCCUPANCY SEPERATION BETWEEN THE GARAGE |
| AND STORAGE OCCUPANCY. SEE 411.2.6 |
| C) THE OPEN STORAGE AREA, WHAT TYPE OF |
| STORAGE WILL THIS BE TO CONSIDER RATING |
| OF WALLS & DOORS. |
| C) AREA NOT LABELED JUST SOUTH OF |
| COLUMN LINE W-37, PLEASE PROVIDE USAGE? |
| |
| 22) A1.04SE AGAIN IT APPEARS THE THE |
| ELEVATOR LOBBIES SHOULD HAVE ELEVATOR |
| LOBBY DOORS , SAME OBJECT APPEARS |
| UNIDENTIFIED OBJECT. |
| |
| 23) A1.04SW/ A1.04NW THERE IS A WALKWAY |
| THAT BACKS UP AGAINST THE VARIOUS |
| SOCALLED (TOWNHOUSE) UNITS, IT APPEARS |
| TO BE A CROSSWALK OR MEANS OF EGRESS, |
| REQUIRING A 44" PATH, THE COLUMNS STICK |
| OUT CUTTING OF ABOUT 1/2 OF THE PATH OF |
| TRAVEL. |
| |
| 24) A1.04P1: |
| A) THE SOUTH END OF THE PARKING GARAGE |
| APPEARS TO HAVE OPEN STORAGE, PROVIDE |
| OCCUPANCY SEPERATION RATED WALLS AND |
| DOORS. 411.2.6. |
| B) PROVIDE INFORMATION FOR THE STEEL |
| CABLE BARRIER SYSTEM TO WITHSTAND THE |
| REQUIREMENTS IN 1608.2.3 GUARDRAIL |
| PARKING. |
| |
| 25) A1.05C : |
| A) CLARIFY, PLANS INDICATE AN ELEVATOR |
| LOBBY & INDICATE A STORAGE AREA NO WALLS |
| OR OCCUPANCY SEPERATION? |
| B) RATING OF ELEVATOR DOOR TO KITCHEN, |
| WHAT WILL THIS DOOR BE USED FOR?NO NAME |
| ON PLANS. |
| C) COVERED TERRACE THE OCCUPANT LOAD IS |
| GREATER THAN 50 REQUIRING A 2 HR |
| SEPERATION. |
| |
| 26) A1.05NE UNITS DO NOT HAVE EGRESS TO |
| STAIR TOWER WITHOUT TRAVEL THROUGH THE |
| ELEVATOR LOBBIES SEE 412.6.2. THE |
| BEDROOM TERRACE LEVEL, LOCKABLE DOORS, |
| 1001.1.3, 1012.4 FOR HORIZONTAL SLIDERS |
| PARTOF A MEANS OF EGRESS. UNIT 512 OK |
| UNITS THAT DO NOT COMPLY 513,514, 515, |
| 516 & 517. |
| |
| 27 DOOR/ROOM 436 USAGE? |
| |
| 28) A1.05SE UNITS DO NOT HAVE EGRESS TO |
| STAIRS WITHOUT TRAVEL THROUGH THE |
| ELEVATOR LOBBY, UNITS 411, 410, 409, 408 |
| & 404. LOCKABLE DOORS 1001.1.3 AND USE |
| OF HORIZONTAL SLIDERS 1012.4 |
| |
| 29) WHEN TENANTS ARE AT THE POOL DECK |
| WILL THE EXIT PASSAGEWAYS ALLOW ENTRENCE |
| BACK INTO THE BUILDING? |
| |
| 30) A1.05SW: |
| A) ROOM JUST NORTH OF THE POOL |
| COLLECTOR TANKS, USAGE? |
| B) STAIRWAY ( DOOR 401) WHAT WILL THE |
| VACANT SPACE BE USED FOR WITHIN THE |
| STAIR TOWER? |
| B) MAIN POOL AREA, SOUTH END THE CHANGE |
| IN GRADE IS GREATER THAN 6" GUARD RAILS |
| OR EDGE TREAMENT SO A WHEELCHAIR COULD |
| NOT JUST ROLL OVER INTO THE STEPPED |
| GRASSED AREAS. |
| C) DECK DRAINS OR GRATES SEE 11-5.4.5. |
| D) CUT SECTION @ STAIRS 03/A6.11 NO |
| HANDRAIL GUARDRAIL FOR STAIRS. |
| E) NOTE STATE STATUTE FOR "EFFECTIVE |
| BARRIER FOR THE PUBLIC POOLS/ SPAS |
| D.O.H.64E-9. |
| F) NOTE PUBLIC POOLS & SPAS |
| 13-412.1ABCD.2.4.2 COVERED POOLS |
| |
| 31) A1.05 P1/P2 CABANA NOTE- SHALL BE |
| DESIGNED TO 140 MPH WIND, 3 SECOND GUST. |
| |
| 32)A1.06NE |
| A) DETAIL 08/A6.14 THE BLOCK WORK THAT |
| ABUTTS STRUCTURAL COLUMNS, WHAT TYPE OF |
| HORIZONTAL TIE IN SYSTEM WILL BE USED/ |
| B) SAME SECTION INDICATES THE USE OF |
| VERTICAL REBAR IN THE BLOCK CELLS NEXT |
| TO OPENINGS, HOW WILL THE REINFORCING |
| RODS TIE INTO THE SLAB ABOVE FOR THE |
| HORIZONTAL AND VERTICAL REINFORCEMENT & |
| TRANSFER OF WALL AND WINDOW/ DOOR |
| LOADING? |
| THIS HOLDS TRUE FOR ALL SIMILAR LOADING |
| ISSUES. |
| |
| 33) A1.06NE THIS COMMENT WILL EFFECT |
| MOST OF THE STAIRWELL, (EXITS) WITHIN |
| THE BUILDING. THE PLANS INDICATE A EXIT |
| DOOR THAT LEADS DIRECTLY FROM THE CONDO |
| UNIT INTO THE SMOKEPROOF EXIT ENCLOSURE. |
| THE INTENT IS TO HAVE AN EXIT THAT |
| DOESN'T TRAVEL THROUGH THE ELEVATOR |
| LOBBY.THE CODE SECTION THAT DOESN'T |
| ALLOW HABITABLE ROOMS TO EMPTY DIRECTLY |
| INTO THE EXIT IS: |
| |
| 1005.6.7 ACCESS TO THE STAIRWAY SHALL BE |
| BY WAY OF A VESTIBULE OR BY WAY OF AN |
| OPEN EXTERIOR BALCONY OF NONCOMBUSTIBLE |
| MATERIALS. |
| EXCEPTION: ACCESS BY WAY OF A |
| VESTIBULE WHEN THE STAIRWAY MEETS THE |
| REQUIREMENTS OF 1005.6.9.2 (1-3), |
| 1005.6.9.9 AND 1005.6.9.10 & IS LOCATED |
| IN A FULLY SPRINKLEREDBUILDING. |
| PLEASE INDICATE COMPLIANCE. UNITS SUCH |
| AS 1615 ON SHEET A1.08NE CAN NOT MAKE |
| THE ROOM CONTAINING THE SECOND EXIT A |
| LOCKABLE ROOM SUCH AS A BEDROOM. |
| |
| 34) A1.10 NE LEVEL 18 SHOWS A STAIR |
| WITHIN THE UNIT GOING TO THE NEXT LEVEL |
| BUT THERE IS NO FLOOR PLAN INDICATEING |
| WHAT IS ON THIS LEVEL? A1.11NE DOES |
| INDICATE A ROOF PLAN FOR THE NEXT LEVEL, |
| IT APPEARS THIS IS THE ELEVATOR MACHINE |
| ROOM LEVEL. DOES THE STAIR BELOW SERVICE |
| THE ELEVATOR MACHINE ROOM? |
| |
| 35) A1.11SE THE SAME SITUATION APPEARS |
| WITH THE EXCEPTION OF CIRCULAR |
| STAIRS.PLEASE PROVIDE A FLOOR PLAN FOR |
| THIS LEVEL. |
| |
| 36) PROVIDE THE DRAFT WIND PRESSURE |
| REPORTCOMPLETED BY RWDI CONSULTING |
| ENGINEERS, IT APPEARS THE NEGATIVE |
| PRESSURES ARE LOW. |
| 1606.1.1 DETERMINATION OF WIND FORCES. |
| WIND FORCES ON EVERY BUILDING OR |
| STRUCTURE SHALL BE DETERMINED BY THE |
| PROVISIONS OF CHAPTER 6 OF ASCE 7-98. |
| THE SIMPLIFIED FORM WILL NOT WORK ON |
| THIS BUILDING BECAUSE OF HEIGHT AND THE |
| SHAPE OF THE BUILDING. |
| |
| |
| 37) A3.04A/ A3.05A INDICATES A |
| STRUCTURAL STEEL AND GLASS SKYLIGHT TO |
| BE USED SHOW COMPLIANCE WITH: |
| A)13-104.4.5 FENESTRATION ENERGY RATING |
| LABELS. ENERGY PERFORMANCE VALUES (I.E., |
| U-FACTOR, SOLAR HEAT GAIN COEFFICIENT) |
| OF FENESTRATION PRODUCTS (I.E., WINDOWS, |
| DOORS AND SKYLIGHTS) SHALL BE DETERMINED |
| BY AN ACCREDITED, INDEPENDENT LABORATORY |
| AND LABELED AND CERTIFIED BY THE |
| MANUFACTURER. |
| B) 1604.3 CONCENTRATED FLOOR LIVE LOADS |
| SKYLIGHT RIBS 200 LBS |
| C) MUST MEET SMALL MISSLE IMPACT |
| TESTING 30'-60' FROM THE GROUND. |
| D) 1707.4.2.1.1 TEST AND LABELING OF |
| SKYLIGHTS. EXTERIOR SKYLIGHTS SHALL BE |
| TESTED BY AN APPROVED INDEPENDENT |
| TESTING LABORATORY, AND SHALL BE LABELED |
| WITH AN APPROVED LABEL IDENTIFYING THE |
| MANUFACTURER, PERFORMANCE |
| CHARACTERISTICS AND APPROVED PRODUCT |
| EVALUATION ENTITY TO INDICATE COMPLIANCE |
| WITH THE REQUIREMENTS OF THE FOLLOWING |
| SPECIFICATION: AAMA/WDMA 1600/IS7, |
| VOLUNTARY SPECIFICATION FOR SKYLIGHTS OR |
| TAS 202 (HVHZ SHALL COMPLY WITH TAS 202) |
| E)2405.3.2 SLOPED GLAZING.GLASS SLOPED |
| MORE THAN 15 DEGREES (0.26 RAD) |
| FROM VERTICAL IN SKYLIGHTS, SUNSPACES, |
| SLOPED ROOFS AND OTHER EXTERIOR |
| APPLICATIONS SHALL BE CHOSEN TO RESIST |
| THE APPLICABLE LOADS FOR COMPONENTS |
| AND CLADDING.THE ALLOWABLE COMBINED |
| LOAD FOR THE GLASS SHALL BE DETERMINED |
| IN ACCORDANCE WITH ?2405.3.2.1 THROUGH |
| ?2405.3.2.3. |
| |
| 38) PROVIDE DETAILS FROM THE PRE-CAASST |
| SPECIALTY ENGINEER HOW SYSTEM ISTO BE |
| ASSEMBLED. WHAT TYPE MATERIAL IS TO BE |
| USED, FORCES TO BE RESISTED, UPLIFT, |
| LATERAL LOADS AND GRAVITY LOADS. |
| |
| 39) A3.09 DETAIL# 2FL BLD CODE |
| 104.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED, PROVIDE INFORMATION ON THE |
| TENSILE FABRIC & CANOPY STRUCTURE. |
| |
| 40)*******VERY IMPORTANT NOTE*********** |
| *************FOR CONTRACTOR************ |
| PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE |
| REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 41) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED, STOREFRONT, OPERTABLE |
| PASS THROUGHS OR GLASS BLOCK |
| B)EXTERIOR DOORS, SOLID, SWING, GLAZED |
| SLIDERS ROLL UP |
| C) MULLIONS BOTH VERTICAL & HORIZONTAL |
| D) SKYLIGHTS |
| E) EXTERIOR VENTS OR LOUVERS |
| F) EXTERIOR GUARDRAILS |
| G) PANEL WALL SYSTEMS: SOFFITS, EFIS |
| SYSTEMS, DENSEGLASS |
| H) LOUVERS |
| I) ROOFING PRODUCTS/ ASSEMBLIES |
| |
| 42)1707.4.4.1 ANCHOR REQUIREMENTS: |
| WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| ED IN ACCORDANCE WITH THE PUBLISHED |
| MANUFACTURER'S RECOMMENDATIONS TO |
| ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| SUBSTITUTE ANCHORING SYSTEM USED FOR |
| THE SUBSTRATE NOT SPECIFIED BY THE |
| FENESTRATION MANUFACTURER SHALL PROVIDE |
| EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| TED BY ACCEPTED ENGINEERING PRACTICES. |
| |
| 43)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 44) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED STATE TESTING |
| LABORATORY OR BE ENGINEERED. IF TO BE |
| USED IN CONJUNCTION WITH GLAZED UNITS |
| WITH LARGE MISSLE TESTING THE MULLION |
| ALSO REQUIRES LARGE MISSLE TESTING. |
| |
| 45) A3.10 DETAIL# 2 INDICATES ATTACHMENT |
| OF LIMESTONE VENEER, PROVIDE THE WEIGHT |
| PSF, METHOD OF ATTACHMENT, SPACING OF |
| FASTENERS SEE SECTION 1403 FOR VENEER |
| WALLS . |
| |
| 46) A4.00 DETAIL# 3 PROVIDES A DETAIL |
| FOR SOFITS AND DROPPED CEILING. THE PLAN |
| DOES NOT INDICATE HOW OFTEN THE TOP |
| PLATE IS TO BE SECURED TO THE CONCRETE |
| DECK NOR DOES THE DETAIL INDICATE WHAT |
| THE LIMITATION IS FOR BRACING AT THE MID |
| SPAN. THE PLAN DOESN'T INDICATE WHAT |
| CENTERS THE FRAMING IS TO BE PLACED OR |
| SCREW ATTACHMENT. |
| |
| 47) A4.00 DETAIL # 5 INDICATES THE USE |
| OF WOOD BUCKS. 609.2.1 TYPE I AND TYPE |
| II CONSTRUCTION. PARTITIONS SHALL BE |
| CONSTRUCTEDOF NONCOMBUSTIBLE |
| MATERIALS.EXCEPTIONS: 1. FRAMING MEMBERS |
| MAY BE OF FIRE RETARDANT TREATED WOOD. |
| |
| 48) DETAIL# 2 INDICATES THE USE OF EFIS |
| TRIM, SEE 1404.1.1 TYPE I BUILDINGS THAT |
| ARE NOT OVER 3 STORIES OR 40' MAY HAVE |
| TYPE VI TRIM. |
| |
| 49) A6.01 RAILING DETAIL INDICATES TWO |
| INCHES CLEAR FROM THE BOTTOM RAIL TO THE |
| DECK.1015.3 OPENINGS. A BOTTOM RAIL OR |
| CURB SHALL BE PROVIDED THAT WILL REJECT |
| THE PASSAGE OF 2-INCH (51 MM) DIAMETER |
| SPHERE. |
| |
| 50) A6.06 MAIN GLASS CANOPY, PROVIDE |
| INFORMATION ON THE CANOPY SYSTEM. ALSO |
| PROVIDE INFORMATION ON THE GLAZING |
| SYSTEM INDICATING COMPLIANCE WITH |
| 2407.2.1 ALLOWABLE GLAZING MATERIALS. |
| |
| 51) A6.08 DETAI# 19 MAIN LOBBY |
| HORIZONTAL SLIDING DOORS, PROVIDE THE |
| MANUFACTURER SPECS FOR CODE COMPLIANCE |
| WITH 1012.4 (1-9) |
| |
| 52)SHEET AC-02: |
| 52A) THERE APPEARS TO BE A DESCREPANCY |
| BETWEEN AC-02 NORTH END OF BUILDING |
| WHERE THE INTAKE LOUVERS ARE INDICATES |
| THIS TO BE AN ELECTRICAL ROOM VS A1.03 |
| WHICH CALLS FOR OPEN STORAGE. OCCUPANCY |
| SEPERATION FROM THE PARKING GARAGE. |
| 52B) THE SAME SITUATION IS ON THE SOUTH |
| END OF THE PARKING GARAGE WITH THE EF |
| 23,24,& 25. PROVIDE A SECTION THROUGH |
| THIS AREA AND THE OPEN AREA TO THE |
| SOUTH. |
| |
| 53) THE SAME ISSUES AS 52 BUT ON AC-03. |
| |
| 54) P-2 INDICATES PLUMBING IN THE EXIT |
| TOWERS, TOWER 5 STAIR A, TOWER8 STAIR A. |
| 1006.1.3.1 PENETRATIONS INTO OPENINGS |
| THROUGH A STAIRWAY ENCLOSURE ASSEMBLY |
| ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, DUCTWORK AND EQUIPMENT NECESSARY |
| FOR INDEPENDENT STAIR PRESSURIZATION, |
| SPRINKLER PIPING, STANDPIPES AND |
| ELECTRICAL CONDUIT SERVING THE |
| STAIRWAY AND TERMINATING AT A STEEL BOX |
| NOT EXCEEDING 16 SQ IN. (0.010 M^2). |
| SUCH PENETRATIONS SHALL BE PROTECTED IN |
| ACCORDANCE WITH ?705.4.THERE SHALL BE NO |
| PENETRATIONS OR COMMUNICATING OPENINGS, |
| WHETHER PROTECTED OR NOT, BETWEEN |
| ADJACENT STAIR ENCLOSURES. |
| |
| 55)P-13 INDICATES A 4" RAIN WATER LITER |
| IN EXIT NOTE "TO BUILD 2HR SOFFIT W/ |
| ACCESS PANEL". 1006.1.4 THERE SHALL BE |
| NO USABLE SPACE WITHIN AN EXIT ENCLOSURE |
| |
| 56) 1016.4 STAIR IDENTIFICATION. AN |
| APPROVED SIGN SHALL BE LOCATED AT EACH |
| FLOOR LEVEL LANDING IN ALL ENCLOSED |
| STAIRWAYS OF BUILDINGS FOUR OR MORE |
| STORIES IN HEIGHT.THE SIGN SHALL |
| INDICATE THE FLOOR LEVEL AND THE |
| AVAILABILITY OF ROOF ACCESS FROM THAT |
| STAIRWAY AND AN IDENTIFICATION OF THE |
| STAIRWAY.THE SIGN SHALL ALSO STATE THE |
| FLOOR LEVEL OF AND DIRECTION TO |
| EXIT DISCHARGE.THE SIGN SHALL BE |
| LOCATED APPROXIMATELY 5 FT (1524 MM) |
| ABOVE THE FLOOR LANDING IN A POSITION |
| WHICH IS READILY VISIBLE WHEN THE |
| DOOR IS IN THE OPEN OR CLOSED POSITION. |
| |
| 57) 412.8.1 ALL STAIRWAY DOORS WHICH ARE |
| TO BE LOCKED FROM THE STAIRWAY SIDE |
| SHALL HAVE THE CAPABILITY OF BEING |
| UNLOCKED SIMULTANEOUSLY WITHOUT |
| UNLATCHING UPON A SIGNAL FROM THE |
| CENTRAL CONTROL STATION.THE DOORS |
| SHALL BE SIMILARLY UNLOCKED UPON |
| ACTIVATION OF THE SPRINKLER SYSTEM OR |
| UPON POWER FAILURE. |
| |
| 412.8.2 TELEPHONE OR OTHER TWO-WAY |
| COMMUNICATIONS SYSTEMS CONNECTED TO AN |
| APPROVED EMERGENCY SERVICE WHICH |
| OPERATES CONTINUOUSLY SHALL BE |
| PROVIDED AT NOT LESS THAN EVERY FIFTH |
| FLOOR IN EACH REQUIRED STAIRWAYWHERE |
| OTHER PROVISIONS OF THIS CODE PERMIT THE |
| DOORS TO BE LOCKED. |
| |
| 58) PROVIDE SIGNAGE AS REQUIRED BY |
| 11-4.30 OF FL ACCESSIBILITYAS WELL AS |
| FAIRHOUSING ANSI 117.1 703 FOR STAIRS |
| AND OTHER REQUIRED ELEMENTS. |
| |
| 59) **STRUCTURAL WIND DESIGN LOADS** |
| SHEET S0.02 INDICATE THE WIND DESIGN IS |
| TAKEN FROM ASCE7-98 WITH A "EXPOSURE "C" |
| THE PRESSURES ARE LOW FOR A BUILDING OF |
| OVER 185'. TABLES FROM ASCE 7-88 FOR |
| 180' BUILDING FOR END ZONES INDICATE |
| 139.1 FOR END ZONES ON A TRIBUTARY AREA |
| OF 20', WHY ARE THE PRESSURES SO LOW |
| PROVIDE CALCULATIONS. WE LOOK FOR WINDOW |
| AND DOOR PRESSURES +/- FOR OPENINGS IN |
| BOTH, END ZONES AS WELL AS THE INTERIOR |
| ZONES & THEIR TRIBUTARY AREA. THIS IS |
| CRUCIAL INFORMATION REQUIRED FOR THE |
| CONTRACTORS TO PROVIDE THE CORRECT |
| WINDOW OR DOOR FOR THE REQUIRED |
| PRESSURES. |
| |
| 60) SHEET S0.02 INDICATES WORK NOT |
| COVERED BY THE ENGINEER OF RECORD WITH |
| NOTE 7825 SPECIALTY ENGINERED ITEMS, |
| THE ITEMS THAT COMPOSE COMPONENTS AND |
| CLADDING TO ENCLOSE THE BUILDING WILL |
| NEED TO SUPPLY TECHNICAL DATA FOR THE |
| BUILDING TO BE PERMITTED.ADDITIOAL |
| INFORMATION REQUIRED. FL BLD CODE |
| 104.2.1.2*OTHER SPECIALTIES AS THE POOL |
| WILL BE PERMITTED SEPERATELY. |
| |
| 61) STRUCTURAL SHEET S4.05 HAS A NOTE |
| ABOUT HDS SEE NOTES, WHERE? CONCERNS |
| ABOUT 707.1 CONCEALED SPACES IN TYPES I, |
| II AND IV CONSTRUCTION.COMBUSTIBLES |
| SHALL NOT BE PERMITTED IN CONCEALED |
| SPACES OF TYPES I, II OR IV |
| CONSTRUCTION. |
| |
| 62) DEALS WITH THE REQUIEMENTS FOR FIRE |
| RESISTANCY IN TABLE 600 FOR A TYPE I |
| BLDG. COLUMNS SUPPORTING MORE THAN 1 |
| FLOOR REQUIRE A 4 HR RATING. SUPPORTING |
| 1FLOOR ONLY A 3 HR RATING. TABLE 709.2.4 |
| |
| PROVIDES THE MINIMUM DIMENSION FOR THE |
| FIRE RATED COLUMNS PROVIDE THE TYPE OF |
| CONCRETE TO BE USED, THEN MINIMUM FIRE |
| RESISTANCY OF COLUMNS CAN BE VERIFIED. |
| PLEASE NOTE ON S6.01, S6.02 & S6.03. |
| |
| 63) S6.02 IDENTIFIES THE DIFFERENT TYPES |
| OF HOOPS TO BE USED BY CONFIGURATION. |
| PLEASE PROVIDE THE DIMENSIONS FOR THE |
| MINIMUM REQUIRED COVERAGE OF STEEL IN |
| 709.2.4.2. |
| |
| 64) A5.07-A5.13 SSTAIR TOWERS STAIRS TO |
| COMPLY WITH1007.1.2 STAIRWAYS LOCATED |
| IN A REQUIRED FIRE RESISTANT ENCLOSURE |
| SHALL HAVE CLOSED RISERS. |
| |
| 65) PLANS TO INDICATE COMPLIANCE WITH: |
| 1015.3 OPENINGS. OPEN GUARDRAILS SHALL |
| HAVE INTERMEDIATE RAILS OR ORNAMENTAL |
| PATTERN SUCH THAT A 4-INCH (102 MM) |
| DIAMETER SPHERE CANNOT PASS THROUGH ANY |
| OPENING UP TO A HEIGHT OF 34 INCHES.A |
| BOTTOM RAIL OR CURB SHALL BE PROVIDED |
| THAT WILL REJECT THE PASSAGE OF 2-INCH |
| (51 MM) DIAMETER SPHERE. |
| EXCEPTIONS: |
| 1. A 6 INCH (152 MM) SPHERE SHALL NOT |
| PASS THROUGH THE TRIANGULAR OPENING |
| FORMED BY A TREAD, RISER AND BOTTOM OF A |
| GUARDRAIL. |
| |
| |
| THE ANSWERS TO THE LISTED QUESTIONS |
| ABOVE MAY RESULT IN MORE QUESTIONS IN |
| THE NEXT REVIEW. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |