Plan Review Notes
Plan Review Notes For Permit 05070977
Permit Number 05070977
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-03 00:00:00REDLINED
  
 SHOW WINDOW LENGTH TO BE VERIFIED IN
 FEILD. 210.62
  
 LOAD ON PANEL STILL SHOWN AS 6KW, DEMAND
 LOAD WAS CORRECTED.
  
 GFI CIRCUITS IN KITCHEN ONLY REQUIRED
 PER 210.8B3 WHICH REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.