Plan Review Notes
Plan Review Notes For Permit 05070977
Permit Number 05070977
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT 1.0A EQUIPMENT SCHEDULE ITEM #5
 DOES NOT SHOW WATER SUPPLY OR DRAINAGE.
 PLEASE CLARIFY. SECTION 104.2.1.
 2. SHT 1.0A EQUIPMENT PLAN INDICATES
 EXISTING GREASE INTECEPTOR. THIS IS A
 NEW RESTURANT AND AS INDICATED BY
 ENVIRONMENTAL COMPLIANCE THERE IS NO
 GREASE INTECEPTOR AND THE REQUIREMENT
 HAS BEEN WAIVED. PLEASE CLARIFY. SECTION
 104.2.1.
 3. SHT 1.0A INDICATE THE FOLLOWING
 ACCESSIBLITY REQUIREMENTS ON THE
 DETAILS:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.18.4 FLUSH CONTROLS
 C. 11-4.19.5 FAUCETS
 4. SHT 3.0P WATER RISER DIAGRAM WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. -
 PLUMBING NOTES:
 #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE
 PER TABLE 704.1.
 #11 "L" OR "K" COPPER REQUIRED
 UNDERGROUND. "M" COPPER NOT MANUF. IN
 ROLL COPPER AND JOINTS FOR COPPER NOT
 APPROVE UNDER THE SLAB.
 #12 AIR CHAMBERS NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9
 5. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
 A. TYPE OF GAS, (LP OR NATURAL)
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 C. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 D. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 F. GAS RISER DIAGRAM INDICATES 2PSI
 PRESSURE FROM THE METER. INDICATE
 LOCATION OF 2LB TO 1/2LB REGULATOR IN
 GAS SYSTEM AND SUBMIT MANUF.
 SPECIFICATION SHEETS FOR REGULATOR.
 6. SHT 1.0A WITH DBPR STAMPS SHALL BE
 SIGNED, SEALED AND DATED PER SECTION
 104.2.2. - TWO PAGE "WORKSHEETS" SHALL
 BE ATTACHED TO EACH SET OF PLANS BEING
 SUBMITTED FOR REVIEW. SECTION 101.4.7.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]