2005-08-23 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1. SHT 1.0A EQUIPMENT SCHEDULE ITEM #5 |
| DOES NOT SHOW WATER SUPPLY OR DRAINAGE. |
| PLEASE CLARIFY. SECTION 104.2.1. |
| 2. SHT 1.0A EQUIPMENT PLAN INDICATES |
| EXISTING GREASE INTECEPTOR. THIS IS A |
| NEW RESTURANT AND AS INDICATED BY |
| ENVIRONMENTAL COMPLIANCE THERE IS NO |
| GREASE INTECEPTOR AND THE REQUIREMENT |
| HAS BEEN WAIVED. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 3. SHT 1.0A INDICATE THE FOLLOWING |
| ACCESSIBLITY REQUIREMENTS ON THE |
| DETAILS: |
| A. 11-4.16.5 FLUSH CONTROLS |
| B. 11-4.18.4 FLUSH CONTROLS |
| C. 11-4.19.5 FAUCETS |
| 4. SHT 3.0P WATER RISER DIAGRAM WATER |
| HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| IN THE CEILING AS SHOWN. PDI-WH 201. - |
| PLUMBING NOTES: |
| #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE |
| PER TABLE 704.1. |
| #11 "L" OR "K" COPPER REQUIRED |
| UNDERGROUND. "M" COPPER NOT MANUF. IN |
| ROLL COPPER AND JOINTS FOR COPPER NOT |
| APPROVE UNDER THE SLAB. |
| #12 AIR CHAMBERS NOT APPROVED. DELETE |
| FROM REFERENCE. SECTION 604.9 |
| 5. THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE GAS PERMIT: |
| A. TYPE OF GAS, (LP OR NATURAL) |
| B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| C. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| D. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| F. GAS RISER DIAGRAM INDICATES 2PSI |
| PRESSURE FROM THE METER. INDICATE |
| LOCATION OF 2LB TO 1/2LB REGULATOR IN |
| GAS SYSTEM AND SUBMIT MANUF. |
| SPECIFICATION SHEETS FOR REGULATOR. |
| 6. SHT 1.0A WITH DBPR STAMPS SHALL BE |
| SIGNED, SEALED AND DATED PER SECTION |
| 104.2.2. - TWO PAGE "WORKSHEETS" SHALL |
| BE ATTACHED TO EACH SET OF PLANS BEING |
| SUBMITTED FOR REVIEW. SECTION 101.4.7. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |