2005-08-01 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE LOAD CALCULATIONS ON |
| THE RIGHT SIDE OF PANEL SCHEDULE. PLEASE |
| SEE LOAD ADDS UP TO 6KW, HOWEVER, LOADS |
| LISTED ON PANEL SCHEDULE ADDS UP TO MORE |
| THAN TOTAL OF 6KVA.? |
| PLEASE SEE 220,215.5 |
| |
| 2)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| KITCHENS IN OTHER THAN DWELLING UNITS |
| WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| KITCHENS TO BE GFCI PROTECTED. THIS |
| REQUIREMENT APPLIES TO EACH AND EVERY |
| 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| RECEPTACLE, WHETHER OR NOT THE |
| RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| |
| |
| 3)NOTE: PLEASE SEE CIRCUITING FOR |
| "SHOW/DISPLAY WINDOW" RECEPTS, PLEASE |
| ALSO SEE # OF RECEPTS FOR EACH12 |
| LINEAR FT, OR POSTION THERE-OF. |
| 210.62,220.12 |
| |
| 4)NOTE: PLEASE SHOW THE "EXISTING" SIGN |
| CIRCUIT J-BOX LOCATION ETC ON PLANS. |
| |
| PLEASE ANY POSSIBLE COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| SHEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |