Plan Review Notes
Plan Review Notes For Permit 05070947
Permit Number 05070947
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070947
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: TROPICAL AWNING
 TEL: (561)276-7132
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) 3204.7 CONSTRUCTION REQUIREMENTS.
 MARQUEES, CANOPIES AND AWNINGS SHALL
 BE SO CONSTRUCTED AND ANCHORED TO THE
 BUILDING SO AS TO SUPPORT ALL LIVE
 AND DEAD LOADS AS SPECIFIED IN CHAPTER
 16.
  
 1606.1.6 BASIC WIND SPEED. THE BASIC
 WIND SPEED IN MILES PER HOUR, FOR THE
 DEVELOPMENT OF WIND LOADS, SHALL BE
 DETERMINED FROM FIGURE 1606.WEST PALM
 BEACH IS LOCATED IN A 140 MPH WIND ZONE.
  
  
 YOUR COMMENTS ABOUT THE LIVE AND DEAD
 LOADS ARE CORRECT, BUT AS TO WIND LOADS,
  
 1606 ARE COVERED IN CHAPTER 16. I CONCUR
 WITH YOU THAT THE COVERINGS SHOULD BE
 REMOVE FOR HIGH FORCE WINDS BUT THE
 CURENT CODE DOES NOT HAVE IT STATED IN
 THE BODY OF THE CODE. AS A DESIGN
 PROFESSIONAL YOU MAY WANT TO LOOKING
 INTO THE 2004 FL BLDG CODE, YOU DO GET
 LANGUAGE THAT WILL HELP IN YOUR DESIGN.
  
 THE STATE HAS GIVEN THE DESIGN
 PROFESSIONALS THE OPTION TO DESIGN UNDER
 EITHER CODE WHEN APPLICATION FOR PERMIT
 IS MADE BETWEEN JULY 1/2005 AND
 SEPTEMBER 30/ 2005.
  
 2004 FL BLD CODE 3105.4 SEE ATTACHMENT.
 3105.4.2.1 DOES PROVIDE RELEAF WHEN THE
 FABRIC IS DESIGNED WITH A QUICK REMOVAL
 OR BREAKAWAY FABRIC.TO THIS DATE THE
 BUILDING OFFICIAL HAS NOT INDICATED WHAT
 IS A QUICK RELEASE OR BREAK AWAY SYSTEM.
  
 BUILDING PLAN REVIW
 JIM WITMER
 TEL (561) 805-6715
  