2005-07-29 00:00:00 | *********** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| LOADS ON PANEL SCHEDULES ARE SHOWN AS |
| "BLANK". |
| PLEASE COMPLETE LOAD CALCS AND SHOW ALL |
| NEW AND EXSITNG LOADS. |
| 220.3,220.10,220.11,220.13 AND |
| CONTINUOUS @125%. 215.3,230.42 ETC |
| |
| 2)NOTE: PLEASE SEE NEW MAIN DISC'S |
| APPEAR OT BE SHOWN. PLEASE INDICATE THE |
| AIC RATING FOR NEW MAINS. AIC RATING IS |
| SHOWN FOR PANELS. |
| 110.9,215.5 |
| |
| 3)NOTE: PLEASE CLARIFY METHOD OF |
| EQUIPMENT GROUNDING FROM MAIN |
| DISCONNECTS TO SUB PANELS. |
| PLEASE SEE IF EMT, AN EQUIPMENT |
| GROUNDING CONDUCTOR WILL BE REQUIRED. |
| 250.110,,250.24,250.122 |
| |
| 4)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| REQUIRED SIGN CIRCUIT PER 600.5.EACH |
| COMMERCIAL BUILDING AND EACH COMMERCIAL |
| OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE |
| OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| OR OUTLINE LIGHTING SYSTEM USE. THE |
| OUTLET(S) SHALL BE SUPPLIED BY A BRANCH |
| CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. |
| |
| 5)NOTE: PLEASE SEE PANEL SCHEDULE |
| INDICATES A RTU #2, HOWEVER PLANS |
| INDICATE A RTU#1? IS THERE TWO UNITS? |
| PLEASE CORRELATE. |
| PLEASE ALSO SEE PANEL SCHEDULE DOES NOT |
| SHOW ANY INFORMATION FOR RTU#2, MOCP, |
| AWG, KW RATING ETC. |
| 215.5 |
| |
| 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| KITCHENS TO BE GFCI PROTECTED. THIS |
| REQUIREMENT APPLIES TO EACH AND EVERY |
| 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| RECEPTACLE, WHETHER OR NOT THE |
| RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| |
| |
| 7)NOTE: PLEASE SEE SIGNAGE SHALL BE |
| REQUIRED FOR BOTH MAIN FEEDING THE SAME |
| SPACE. 1 OF 2 AND 2OF 2. |
| 230.2E ETC. |
| |
| PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECTELECTRICAL |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| SETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| PLEASE SUBMIT ONE COPY OF ANY OLD SHEETS |
| MARKED OLD/VOIDED SHEEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
2005-07-28 00:00:00 | IN ELEC FOR REVIEW |