2005-10-08 00:00:00 | ************ UNSAT 2ND REVIEW ******** |
| |
| PLEASE SEE SAME COMMENTS FROM PREVIOUS |
| REVIEW AND SEE COMMENTS BELOW. |
| |
| 1)NOTE: PLEASE SEE NOTE #1 FROM FIRST |
| REVIEW, MOST OF THESE ITEMS REQUESTED |
| WERE NOT DONE. |
| SOME OF THE OTHERS WERE HAND DRAWN ON |
| PLANS WHICH ARE SIGNED,DATED AND SEALED |
| BY AN ENGINEER.THIS IS NOT PERMITTED |
| UNDER FS 471.025 |
| PLEASE HAVE ENGINEER OF RECORD MAKE ALL |
| CHANGES AND CORRECTIONS WITH INFORMATION |
| NEEDED. PLEASE HAVE ENGINEER RE-PRINT |
| SHEETS AND , SIGN, DATEAND SEAL ALL |
| SHEETS AS PREVIOUSLY MENTIONED. |
| |
| 2)NOTE: IF THERE IS NO "NIGHT TIME" |
| AFTER DUSK" SWIMMING, THIS WILL BE |
| REQUIRED TO BE REVISED BY ENGINEER. |
| PLANS WILL STILL NEED TO BE STAMPED BY |
| THE PALM BEACH COUNTY HEALTH DEPT AFTER |
| SUCH CORRECTIONS/CHANGES ARE MADE TO |
| PLANS. |
| |
| 3)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONAL AND PLANS BEING REVIEW WITH |
| REPEAT COMMENTS. |
| THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| *** PLEASE SEE PLANS SUBMITTED WHICH ARE |
| COPIES OF PLANS FOR MAIN BLDG, NEED NOT |
| BE SUBMITTED FOR ELECTRICAL. |
| PLEASE SEE NUMEROUS SHEETS SUBMITTED |
| WHICH HAVE NOTHING TO DO WITH ELECTRCAL |
| FOR POOL. *CONDO UNITS ETC?? |
| |
| NO REVIEW FOR CODE COMPLIANCE CAN BE |
| DONE AT THIS TIME FOR CHANGESWHICH |
| STILL NEED TO BE DONE PER ABOVE AND |
| PREVIOUS REVIEW. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |