2006-02-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/26/05:
  
 2) FBC 424.1.1SIZING.IT IS NOTED
 THAT THE 21'-6" PLAN DIMENSION, TO MATCH
 THAT ON THE LOGITUDINAL POOL SECTION (ON
 SHEET 3), HAS BEEN HANDWRITTEN ON SHEET
 1.CHANGES TO THE SIGNED AND SEALED
 PLANS ARE ONLY ACCEPTABLE IF EACH CHANGE
 IS SIGNED AND DATED BY THE ENGINEER OF
 RECORD.
  
 IT IS NOTED THAT THE COMMENT 1 HAS BEEN
 ADDRESSED ALREADY.IF THE RESPONSE TO
 COMMENT 2 REQUIRES NEW SHEETS, PLEASE
 ENSURE THAT THE CERTIFICATE OF
 AUTHORIZATION NUMBER IS ON THE TITLE
 BLOCK OF THE NEW SHEETS.COMMENT 1 IS
 REPEATED BELOW ONLY FOR EASE OF
 REFERENCE:
  
 1) 471.023 F.S.ADD THE CERTIFICATE OF
 AUTHORIZATION NUMBER (6141) FOR YKA
 CONSULTING ENGINEER'S INC TO EACH SHEET.
 THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  