Plan Review Notes
Plan Review Notes For Permit 05070873
Permit Number 05070873
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT PLANS WHICH
 CORRELATE FOR POOL BEING INSTALLED.
 PLEASE SEE PLANS ON ONE SHEETS SHOWS ONE
 SIZE AND OTHER SHEETS SHOWS A POOL LESS
 THAN HALF THE SIZE?
 PLEASE CORRRELATE ALL LIGHTING FIXTURES,
 POOL , SPA PUMP ETS.
 PLEASE INCLUDE THE WIRING DIAGRAM FOR
 ALL ELECTRICAL EQUIPMENT BEING
 INSTALLED.
 PLEASE SEE WIRING DIAGRAMS SHOWS A NEW
 PANEL BEING INSTALLED, HOWEVER NO
 CONDUCTORS,CONDUIT ETC TO WHERE PANEL IS
 BEING FED, WHAT SIZE, OCP ETC.
 215.5
  
 2)NOTE: PLEASE SUBMIT A COMPLETE SIGNED,
 SEALED, DATED PHOTOMETRIC STUDY FOR POOL
 AREA.
 PLEASE BE SURE PHOTOMETRICS ARE STAMPED
 BY THE PALM BEACH COUNTY HEALTH DEPT.FOR
 ANY "NIGHT-TIME" AFTER DUSK" SWIMMING.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]