2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PUT THE GEC SYSTEM ON THE
 RISER PER 250.53.
  
 2} INDICATE THE EQUIPMENT GROUND TO THE
 GENERATOR PER 250.122.
  
 3} PLEASE NOTE THAT A DISCONNECT IS
 REQUIRED ON THE BUILDING PER 225.31,
 GROUPED PER 230.71. THE ATS MUST BE
 SERVICE RATED PER 225.36 TO COMPLY WITH
 THIS REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  