Plan Review Notes For Permit 05070853 |
Permit Number |
05070853 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-03 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PUT THE GEC SYSTEM ON THE | | RISER PER 250.53. | | | | 2} INDICATE THE EQUIPMENT GROUND TO THE | | GENERATOR PER 250.122. | | | | 3} PLEASE NOTE THAT A DISCONNECT IS | | REQUIRED ON THE BUILDING PER 225.31, | | GROUPED PER 230.71. THE ATS MUST BE | | SERVICE RATED PER 225.36 TO COMPLY WITH | | THIS REQUIREMENT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|