2006-01-19 00:00:00BUILDING PROVISO:
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A "A5"
 FLOOD ZONE MINIMUM ELEVATION IS 7'-6".
 ***NOTICE THE FLOOD ELEVATION
 CERTIFICATE IS CERTIFYING THE ELEVATION
 OF THE GENERATOR SLAB. THE SURVEYOR CAN
 NOT CERTIFY SOMETHING THAT IS NOT THERE.
 ALSO NOTE THAT THE MINIMUM FLOOD
 ELEVATION FOR THE CITY IS 7'-6" FOR A
 "A5" FLOOD ZONE. THIS CERTIFICATE IS
 DUE AFTER THE SLAB IS POURED AND THE
 SURVEYOR CAN TAKE THE ACTUAL FINISH
 ELEVATION OF THE SLAB. DUE BEFORE FINAL
 INSPECTION.