Plan Review Notes
Plan Review Notes For Permit 05070837
Permit Number 05070837
Review Stop B
Sequence Number 2
Notes
Date Text
2005-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070837
 ADD: 1801 S FLAGLER DR
 CONT: SULLIVAN
 TEL: (561)588-5886
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.THE
 NOC WAS RECORDED OVER 90 DAYS BEFORE
 COMMENCEMENT OF WORK, RQUIRING A
 RE-RECORDING OF NOTICE OF COMMENCEMENT.
 SEE 713.13(2)
  
 2)PROVISO:PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A "A5"
 FLOOD ZONE MINIMUM ELEVATION IS 7'-6".
 ***NOTICE THE FLOOD ELEVATION
 CERTIFICATE IS CERTIFYING THE ELEVATION
 OF THE GENERATOR SLAB. THE SURVEYOR CAN
 NOT CERTIFY SOMETHING THAT IS NOT THERE.
 ALSO NOTE THAT THE MINIMUM FLOOD
 ELEVATION FOR THE CITY IS 7'-6" FOR A
 "A5" FLOOD ZONE. THIS CERTIFICATE IS
 DUE AFTER THE SLAB IS POURED AND THE
 SURVEYOR CAN TAKE THE ACTUAL FINISH
 ELEVATION OF THE SLAB. DUE BEFORE FINAL
 INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026