Plan Review Notes
Plan Review Notes For Permit 05070837
Permit Number 05070837
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-24 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED
 FOR REQUIRED GAS PERMIT:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 7. INDICATE THE BTU LOAD OF EXISTING
 GENERATOR. IF NEW GENERTATOR IS A
 SUBSTANTIAL ADDITION TO SYSTEM, TOTAL
 BTU OF SYSTEM MAY BE REQUIRED TO CHECK
 PIPE SIZING OUT OF THE METER. (BTU LOAD
 OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2001
 FUEL GAS CODE SECS. 401.8 THRU 402.5.2
 AND TABLES 402(1) THRU 402(34)).
 8. PLANS INDICATE THAT THE UNDERGROUND
 PIPING SHALL HAVE A MINIMUM OF 12"
 COVER. SECTION 404.9 REQUIRES MINIMUM
 18" COVER, BUT MAY BE REDUCED TO 12"
 WHERE EXTERNAL DAMAGE IS NOT LIKELY TO
 RESULT. PLEASE INDICATE HOW THIS
 EXCEPTION WILL BE APPROVED.
  