2005-08-24 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| |
| A. THE FOLLOWING INFORMATION IS REQUIRED |
| FOR REQUIRED GAS PERMIT: |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| 2. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 5. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2. |
| 7. INDICATE THE BTU LOAD OF EXISTING |
| GENERATOR. IF NEW GENERTATOR IS A |
| SUBSTANTIAL ADDITION TO SYSTEM, TOTAL |
| BTU OF SYSTEM MAY BE REQUIRED TO CHECK |
| PIPE SIZING OUT OF THE METER. (BTU LOAD |
| OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE FBC-2001 |
| FUEL GAS CODE SECS. 401.8 THRU 402.5.2 |
| AND TABLES 402(1) THRU 402(34)). |
| 8. PLANS INDICATE THAT THE UNDERGROUND |
| PIPING SHALL HAVE A MINIMUM OF 12" |
| COVER. SECTION 404.9 REQUIRES MINIMUM |
| 18" COVER, BUT MAY BE REDUCED TO 12" |
| WHERE EXTERNAL DAMAGE IS NOT LIKELY TO |
| RESULT. PLEASE INDICATE HOW THIS |
| EXCEPTION WILL BE APPROVED. |
| |