Plan Review Notes For Permit 05070837
Permit Number 05070837
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-03 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE FIRE PUMP INFORMATION
 IS CURRENTLY BEING REVIEWED UNDER
 GENERATOR PERMIT, HOWEVER FIRE PUMP WILL
 BE REQUIRED TO BE PERMITTED SEPARATELY.
 PLEASE SEE THIS MAY BE SUBMITTED ALONG
 WITH GENERATOR PERMIT SO IT MAY BE
 REVIEWED AND PERMITTED AT THE SAME TIME.
 PLANS, SPECS WILL BE REQUIRED FOR EACH
 AS EACH WILL BE FILED UNDER SEPRATE
 FILES.
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP, FIRE PUMP CONTROLLER.
 PLEASE SEE OTHER COMMENTS FOR FPC, AS
 SOME INFORMATION CAN NOT VERIFIED AT
 THIS TIME.
 215.5
  
 3)NOTE: PLEASE SEE CONDUCTORS FROM FPL,
 GENERATOR TO FIRE PUMP, FIRE PUMP CONT,
 SHALL BE BASED ON 125%.
 PLEASE SEE 695.6(C)(2) ETC.
 PLEASE SEE PLANS INDICATE EXSITING
 "NAMEPLATE @ 100HP, 250 FLA'S. THIS IS
 ONLY A NOTE FOR VERIFICATION. NO
 CORRECTION NEEDED.
  
 4)NOTE: PLEASE SEE SPECS/CUT SHEETS FOR
 FPC WERE SUBMITTED, HOWEVER PLEASE NOTE
 THE MANUAL MEANS OF DISCONNECT LOCATED
 ON OUTSIDE OF EQUIPMENT, RATED FOR THE
 LAOD SERVED SHALL BE PART OF THE FPC.
 PLEASE SEE 230.76,230.79,NFPA-20 CHAPTER
 7-4.
 5)NOTE:PLEASESEE THE LOCATION OF FIRE
 PUMP CONTROLLER SHALL BE ARRANGED TO
 PREVENT ANY DAMAGE TO FPC EQUIPMENT IN
 THE EVENT OF FIRE/EXPLOSION ETC.
 PLEASE KNOW,IT IS KNOWN THIS IS AN
 EXSITING ROOM AND THERE ARE SOME
 EXISTING CONDITIONS WHICH CAN NOT BE
 AVOIDED. HOWEVER,A STEEL REINFORCED
 CONCRETE WALL WILL BE REQUIRED TO HELP
 IN SHIELDING ANY SUCH FIRE /EXPLOSION
 FROM MAIN SERVICE EQUIPMENT.
 PLEASE SEE 695.3, NFPA-20 6-2.1.ETC
  
 6)NOTE: PLEASE SEE THE LOCATION OF FIRE
 PUMP CONTROLLER SHALL BE SUCH THE
 LEAKING OF ANY WATERFROM FIRE PUMP ,
 FIRE SPRINKLERS ETC WILL NOT AFFECT THE
 FPC, PLEASE SEE NFPA-20 7-2,7-3.3.1, FOR
 ENCLOSURE TYPE ETC.
 PLEASE SEE NOTE ON PLANS MENTIONS FOR
 FEEDERS FROM GEN TO ENTER BLDG AS LOW AS
 POSSIBLE INTO REAR OF FIRE PUMP
 CONTROLLER, HOWEVER PLEASE SEE
 7-2.2,695.12, WHICH REQUIRES FPC TO BE
 MOUNTED A MIN OF 12" ABOVE FLR.
  
 7)NOTE: PLEASE PROVIDE NOTE FOR SIGNAGE
 FOR ALL ELECTRICAL EQUIPMENT.
 695.4B3,4 ETC.
  
 8)NOTE: PLEASE SEE PROTECTIVE BOLLARDS
 WILL BE REQUIRED OUTSIDE TO PROTECT GEN
 ENCLOSURE FROM PARKING LOT AREA.
 PLEASE SEE ANY ZONING COMMENTS.
  
 9)NOTE: PLEASE SEE PLANS MENTIONS PIPING
 IN ROOM SHALL BE EMT, PLEASE SEE
 695.6(2)(E).
  
 10)NOTE: PLEASE SEE 701.11(B)(2)(3) FOR
 SOURCES OF FUEL.
 PLEASE SEE IT IS KNOWNTO OUR OFFICE
 THE LOCAL UTILITY COMAPNY SUPPLYING
 NATURAL GAS SEEMS TO BE AT OVER 500%
 CAPACITY. PLEASE SEE AN ALTERANTE FUEL
 SOURCE WILL BE REQUIRED FOR MIN REQUIRED
 RUN TIME.
  
 11)NOTE: PLEASE SEE SITE PLAN / SURVEY
 WILL BE REQUIRED TO INDICATE THE BASE
 FLOOD ELEVATION (BFE). GEN SLAB SHALL BE
 A MIN OF 6" ABOVE BFE. PLEASE SEE BLDG
 REVIEW COMMENTS.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 BOLT/TIE DOWN CONNECTIONS REQUIRED.
  
 12)NOTE: PLEASE SEE FBC LOCAL
 ADMINISTRATIVE SECTION 104.6.5, PERMIT
 VALUATION IS BASED ON ALL LABOR AND
 MATERIALS, EVEN IF EQUIPMENT IS OWNER
 SUPPLIED. PLEASE ADJUST.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  