2005-07-29 00:00:00 | ********** UNSAT ************* |
| |
| 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED |
| WITH CONTRACT SCHEDULE AND ELECTRICAL |
| DETAIL SHEET SUBMITTED. |
| PLEASE SEE CONTRACT MENTIONS NEW 100W |
| FIXTURE, HOWEVER ELECTRICAL LISTS 75W? |
| PLEASE SEE CONTRACT MENTION NEW SALT |
| WATER CHORLINATOR SYSTEM BEING |
| INSTALLED, HOWEVER, PLEASE SEE THIS IS |
| NOT SHOWN IN ELECTRICAL WIRING DIAGRMA |
| NOR IS IT SHOWN ON PIPING SCHEDULE(SEE |
| PLUMBING NOTES). |
| PLEASE SEE ELECTRICAL SHEETS MENTISON A |
| NEW POOL PANEL BEING INSTALLED ALONG |
| WITH SEPARATE CIRCUITS FOR POOL |
| EQUIPMENT? PLEASE CORRELATE. |
| PLEASE SEE NEW POOL PANEL IS NOT SHOWN |
| ON ELECTRICAL WIRING DIAGRAM. |
| PLEASE ALSO SEE IF A NEW POOL PANEL IS |
| BEING INSTALLED? PLEASE CLARIFY WHY POOL |
| PUMP MOTOR, BLOWER AND LT IS ALSO BEING |
| FED WITH SEPARATE CIRCUITS? |
| PLEASE SHOW ALL CONTINUOUS LOADS AT 125% |
| 215.3,230.42 ETC. |
| PLEASE INDICATE LOAD ON EXISTING SERVICE |
| AND SIZE.220,215.5 |
| |
| 2)NOTE: PLEASE SEE FBC 104.2.1, ALL |
| PLANS/DRAWINGS MUST CONTAIN THE PRINTED |
| NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR PLANS/DESIGNS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW.IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |