2005-07-23 00:00:00 | ---------------PROVISO------------------ | | 1)AUXILIARY DRAIN PAN REQUIRED PER FBC,M | | 307.2.3 | | | | 2)BALANCED RETURN REQUIRED FROM BACK | | BEDROOM PER FBC,M 601.4 | | | | 3)DRYER EXHAUST REQUIRED PER FBC,M 504 | | | | 4)AHU IN ATTIC REQUIRES NOTIFICATION AT | | C.B. PANEL PER FBC CH.13 SEC | | 610.1.ABC.3.5.2 | | | | 5)AHU IN ATTIC TO HAVE MIN 30X20 ACCESS | | PANEL WITHIN 6' OF SERVICE PANEL PER FBC | | CH.13 SEC 610.1.ABC.3.5.2 | | | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|