Plan Review Notes
Plan Review Notes For Permit 05070720
Permit Number 05070720
Review Stop E
Sequence Number 3
Notes
Date Text
2006-02-23 00:00:00 
 AFTER SPEAKING WITH SHARON WITH RHR
 POOLS I DETERMINED AN ELECTRICAL REVIEW
 WAS NOT REQUIRED FOR THIS REVISION WHICH
 WAS FOR A BARRIER./WRT.
2006-01-30 00:00:00 
 FAILED
 ~~~~~~
  
  
 1} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 INDICATE IF THE PANEL IS NEW OR
 EXISTING,
 IF EXISTING DISREGARD THE PREVIOUS
 COMMENT, BUT INDICATE SAME ON PLAN.
  
 2} THE DATE ON THE PLAN IS THE SAME DATE
 AS THE PREVIOUS PLAN. "THE DATE THE SEAL
 AND SIGNATURE IS AFFIXED ... SHALL BE
 ENTERED ON SAID PLANS..." FAC
 61G15-23.002(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW