2006-02-06 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05070720 |
| ADD: 8583 EGRET MEADOW LANE |
| CONT:RHR POOLS |
| TEL: (772)263-9132 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| POOL REVIEW |
| ACTION: REVIEWD |
| BUILDING PROVISO: |
| |
| TO BE IN PLACE AT TIME OF C. O.: |
| |
| 1)424.2.17.1.8 ACCESS GATES, WHEN |
| PROVIDED, SHALL BE SELF-CLOSING AND |
| SHALL COMPLY WITH THE REQUIREMENTS OF |
| ?424.2.17.1.1 THROUGH 424.2.17.1.7 AND |
| SHALL BE EQUIPPED WITH A SELF-LATCHING |
| LOCKING DEVICE LOCATED ON THE POOL SIDE |
| OF THE GATE.WHERE THE DEVICE RELEASE |
| IS LOCATED NO LESS THAN 54 INCHES FROM |
| THE BOTTOM OF THE GATE, THE DEVICE |
| RELEASE MECHANISM MAY BE LOCATED ON |
| EITHER SIDE OF THE GATE AND SO PLACED |
| THAT IT CANNOT BE REACHED BY A YOUNG |
| CHILD OVER THE TOP OR THROUGH ANY |
| OPENING OR GAP FROM THE OUTSIDE.GATES |
| THAT PROVIDE ACCESS TO THE SWIMMING POOL |
| MUST OPEN OUTWARD AWAY FROM THE POOL. |
| THE GATES AND BARRIER SHALL HAVE NO |
| OPENING GREATER THAN 1/2 INCH WITHIN 18 |
| INCHES OF THE RELEASE MECHANISM. |
| |
| 2) 424.2.17.1.9 ALL DOORS AND WINDOWS |
| PROVIDING DIRECT ACCESS FROM THE HOME TO |
| THE POOL SHALL BE EQUIPPED WITH AN EXIT |
| ALARM COMPLYING WITH UL 2017 THAT HAS A |
| MINIMUM SOUND PRESSURE RATING OF 85 DB A |
| AT 10 FEET AND IS EITHER HARDWIRED OR OF |
| THE PLUG-IN TYPE.THE EXIT ALARM SHALL |
| PRO-DUCE A CONTINUOUS AUDIBLE WARNING |
| WHEN THE DOOR AND ITS SCREEN ARE OPENED. |
| THE ALARM SHALL SOUND IMMEDIATELY |
| AFTER THE DOOR IS OPENED AND BE CAPABLE |
| OF BEING HEARD THROUGHOUT THE HOUSE |
| DURING NORMAL HOUSEHOLD ACTIVITIES.THE |
| ALARM SHALL BE EQUIPPED WITH A MANUAL |
| MEANS TO TEMPORARILY DEACTIVATE THE |
| ALARM FOR A SINGLE OPENING.SUCH |
| DEACTIVATION SHALL LAST NO MORE THAN 15 |
| SECONDS.THE DEACTIVATION SWITCH SHALL |
| BE LOCATED AT LEAST 54 INCHES ABOVE THE |
| THRESH-OLD OF THE DOOR.SEPARATE ALARMS |
| ARE NOT REQUIRED FOR EACH DOOR OR WINDOW |
| IF SENSORS WIRED TO A CENTRAL ALARM |
| SOUND WHEN CONTACT IS BROKEN AT ANY |
| OPENING. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |