Plan Review Notes For Permit 05070720 |
Permit Number |
05070720 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-16 00:00:00 | DENIED; | | | | 1) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 2)SCOPE OF WORK ISNOT CLEAR. THE PLAN | | SHOWS A PIPING DIAGRAM FOR THE SPA AND | | THE PIPING SCHMATIC SHOWS POOL ONLY. | | DOES REPIPING OF THE POOL INCLUDE NEW | | EQUIPMENT? IS ALL EQUIPMENT ON THE SAME | | PAD? IS THERE A PUMP FOR THE POOL AND A | | PUMP FOR THE SPA? WHAT IS THE HP OF THE | | BLOWER? | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|