2005-08-09 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT SPECIFICATIONS FOR THE HEATER | | SHOWN. | | | | 2} THE ELECRICAL SCHEMATIC SHOWS POOL | | WIRING, NOT SPA WIRING INDICATED ON THE | | APPLICATION.THE ENGINEER OF RECORD NEEDS | | TO EXPAND THE WIRING SCHEMATIC TO | | INCLUDE ALL WORK. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|