2005-07-23 00:00:00PLUMBING PLANREVIEW FBC 2001 DENIED.
 PROVIDE INFORMATION ON CLOTHES DRYER
 EXHAUST, PER THE FOLLOWING MECHANICAL
 CODE SECTIONS, SEPERATE MECHANICAL
 PERMIT REQUIRED.
  
 ?M504.4 EXHAUST INSTALLATION. DRYER
 EXHAUST DUCTS FOR CLOTHES DRYERS
 SHALL TERMINATE ON THE OUTSIDE OF THE
 BUILDING AND SHALL BE EQUIPPED WITH A
 BACKDRAFT DAMPER.SCREENS SHALL NOT BE
 INSTALLED AT THE DUCT TERMINATION.
 DUCTS SHALL NOT BE CONNECTED OR
 INSTALLED WITH SHEET METAL SCREWS OR
 OTHER
 FASTENERS THAT WILL OBSTRUCT THE FLOW.
 CLOTHES DRYER EXHAUST DUCTS SHALL
 NOT BE CONNECTED TO A GAS VENT
 CONNECTOR, GAS VENT OR CHIMNEY.CLOTHES
 DRYER EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR THROUGH DUCTS OR PLENUMS.
  
 ?M504.5 MAKEUP AIR. INSTALLATIONS
 EXHAUSTING MORE THAN 200 CFM (0.09
 M^3/S) SHALL BE PROVIDED WITH MAKEUP
 AIR.WHERE A CLOSET IS DESIGNED FOR
 THE INSTALLATION OF A CLOTHES DRYER, AN
 OPENING HAVING AN AREA OF NOT LESS
 THAN 100 SQUARE INCHES (0.0645 M^2)
 SHALL BE PROVIDED IN THE CLOSET
 ENCLOSURE.
 QUESTIONS: 561-805-6692