Plan Review Notes For Permit 05070533 |
Permit Number |
05070533 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- MULE-HIDE BITUMEN ROOF SYSTEM | | SUBMITTED DOESN'T WORK. IT'S LIMITED BY | | LIMITATION #9 WHICH DOESN'T ALLOW | | ENHANCED FASTENING TO INCREASE THE | | UPLIFT VALUE AT CORNERS AND PERIMETER | | ZONES. PROVIDE ANOTHER SYSTEM THAT IS | | NOT LIMITED BY LIMITATION #9. (SEE TABLE | | 1606.2B FBC 2001 FOR DESIGN PRESSURES AT | | CORNERS AND PERIMETER AREAS) | | | | 2- CLEARLY SPECIFY ROOF TILE FASTENING. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | 2001. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|