Notes |
Date |
Text |
2005-09-10 00:00:00 | DENIED; | | 2ND REQUEST , CHANGES NOT ON | | DRAWINGS. | | 1) FBC-2001 424.2.8.1 VALVES SHALL BE | | MADE OF MATERIALS THAT ARE APPROVED IN | | THE FLA BLDG CODE, PLUMBING.THEY WILL | | BE READILY ACCESSIBLE FOR MAINT. AND | | REMOVAL.SEC 424.2.8.2 FULL WAY VALVES | | SHALL BE INSTALLED TO INSURE PROPER | | FUNCTION OF THE FILTRATION AND PIPING | | SYSTEMS.SEC 424.2.8.3 WHERE CHECK | | VALVES ARE INSTALLED THEY SHALL BE OF | | THE SWING OR VERTICAL CHECK PATTERNS. | | SEC 424.2.8.4 COMBINATION VALVES SHALL | | REQUIRE APPROVAL OF THE ADMINISTRATIVE | | AUTHORITY PRIOR TO THEIR INSTALLATION. | | 2) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3)424.2.9 WATER SUPPLY, LOCAL ORD. | | #2853-95 BACKFLOW REQUIRED ON WATER | | SEVICE. (ADD TO NOTES) | | 4.424.2.13.2 JOINTS AND CONNECTIONS, FBC | | PLUMBING SEC. 605.21,PURPLE PRIMER | | REQUIRED ON PVCPIPING. (ADD TO NOTES) | | 5)424.2.15 GAS PIPING SHALL COMPLY WITH | | FBC FUEL GAS. SEPARATE PLANS AND PERMIT | | REQUIRED. (ADD TO NOTES) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 | | | | |
|