Plan Review Notes For Permit 05070511 |
Permit Number |
05070511 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-30 00:00:00 | DENIED; | | 1.VALVESSHALL BE READILY ACCESSIBLE FOR | | MAINT. AND REMOVAL. VAVES SHALL BE FULL | | WAY. WHERE CHECK VAVES ARE INSTALLED | | THEY SHALL BE OF THE SWING OR VERTICAL | | CHECK PATTERN. (ADD TO NOTES) | | 2.LOCAL ORD. #2853-95 BACKFLOW REQUIRED | | ON WATER SERVICE. ADD TO NOTES | | 3.JOINTS AND CONNECTIONS FBC PLUMBING | | SEC. 605.21 PURPLE PRIMER REQUIRED ON | | PVC PIPING. ADD TO NOTES | | 4GAS PIPING SHALL COMPLY WITH FBC FUEL | | GAS. SEPARATE PLANS AND PERMIT REQUIRED. | | ADD TO NOTES. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|