Plan Review Notes For Permit 05070507 |
Permit Number |
05070507 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-22 00:00:00 | ********** PROVISO/RELDINED *********** | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE | | INDICATES A WHIRLPOOL TUB, HOWEVER PLANS | | DO NOT SHOW THIS. | | PLEASE ALSO SEE 680.71 FOR REQUIRED GFI | | PROTECTION TO BE INDICATED. | | | | 2)NOTE: PLEASE SEE ALL RECEPTS WITH AREA | | OF LAUNDRY RM SINK SHALL BE GFI/ GFI | | PROTECTED.210.8 | | | | 3)NOTE: PLEASE SEE KITCHEN APPEARS TO BE | | SHOWING AN "ISLAND", IF SO, PLEASE SEE | | 210.52C2, 210.8A6 FOR REQUIRED GFI | | RECEPT(S). | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULES | | INDICATE 80 RECESSED LTS, HOWEVER 80 | | COULD NOT BE LOCATED ON PLANS. | | PLEASE ADJUST WHEN FINAL # IS INSTALLED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | ALONG WITH ANY OTHER REVISIONS BEFORE | | ROUGH ELECTRICAL INSPECTION IS CALLED | | IN. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|