Plan Review Notes For Permit 05070485 |
Permit Number |
05070485 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-06 00:00:00 | DENIED; | | 1.MASTER BATH L/T MUST BE DOWN STREAM OF | | THE BATHROOM GROUP. SEC 909.1. | | 2.L/T TO DISCHARGE ABOVE W/M AND | | CLEANOUT SHOULD BE AT 48" AFF. | | 3.BATH 2 SHOWER IS NOT VENTED. | | 4.BATH 3 SHOWER IS NOT VENTED. | | 5.SHOW PIPING FOR FUTURE TRAINING ROOM | | BATH ON RISER DIAGRAM. | | ONE SET OF PLANS MARKED IN RED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|