2005-08-31 00:00:00IN ELEC FOR REVIEW
 ******* UNSAT ********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS AND
 SOME NEW NOTES DUE TO CHANGES IN PLANS.
  
 1)NOTE: PLEASE SEE LOAD CALCUALTIONS FOR
 POOL SUB PANEL WERE REVISED, HOWEVER OCP
 FOR FEED TO PANEL WAS NOT INCREASED?
 PLEASE SEE PANEL "B" STILL SHOWS 2P60A
 BRKR.
 PLEASE ALSO CORRELATE RISER WITH PANEL
 SCHEDULES.
 PLEASE SEE RISER SHOWS POOL PANEL "C"
 BEING FED FROM MCB OUTSIDE PANEL,
 HOWEVER PANEL SCHEDULE FOR INSIDE PANEL
 INDICATES POOL SUB PANEL BEING FED FROM
 INSIDE?
 PLEASE SEE RISER NOW SHOWS #3'S FOR
 INCREASED FEEDERS.
 PLEASE SEE NO PANEL SCHEDULE FOR EITHER
 OUTSIDE 8/16 CIRCUIT PANELS WERE
 SUBMITTED.
 PLEASE SEE RISER ONLY INDICATES THE 150A
 MCB'S.
 PLEASE ADJUST.
 215.5
  
 2)NOTE: PLEASE SEE IRRIGATION PUMP ON
 PLANS, NOT ON PANEL SCHEDULE OR LOADS.
 215.5
  
 3)NOTE: PLEASE SEE PREVIOUS NOTE # 10
 REQUESTED LTR FROM ARCHITECT. PLEASE SEE
 LTR SUBMITTED IS REQUIRED TO BE SEALED
 AND DATED. FS 481.221
 PLEASE ALSO SEE LETTER IS REQUIRED TO BE
 CORRECTLY NOTORIZED AS SET-FORTH UNDER
 FS 117.05 FOR NOTORIES.
 PLEASE SEE MIN INFORMATION REQUIRED.
 THE STAMP AND SIGNATURE IS INSUFFICENT.
  
 4)NOTE: PLEASE SEE RISER SHOWS 3-1/0'S
 AND #6 CONDUCTORS IN A 1" CONDUIT?
 PLEASE SEE TABLE 9 FOR PIPE FILL.
 PLEASE ADJUST.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  