Date |
Text |
2005-08-31 00:00:00 | IN ELEC FOR REVIEW |
| ******* UNSAT ******** |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS AND |
| SOME NEW NOTES DUE TO CHANGES IN PLANS. |
| |
| 1)NOTE: PLEASE SEE LOAD CALCUALTIONS FOR |
| POOL SUB PANEL WERE REVISED, HOWEVER OCP |
| FOR FEED TO PANEL WAS NOT INCREASED? |
| PLEASE SEE PANEL "B" STILL SHOWS 2P60A |
| BRKR. |
| PLEASE ALSO CORRELATE RISER WITH PANEL |
| SCHEDULES. |
| PLEASE SEE RISER SHOWS POOL PANEL "C" |
| BEING FED FROM MCB OUTSIDE PANEL, |
| HOWEVER PANEL SCHEDULE FOR INSIDE PANEL |
| INDICATES POOL SUB PANEL BEING FED FROM |
| INSIDE? |
| PLEASE SEE RISER NOW SHOWS #3'S FOR |
| INCREASED FEEDERS. |
| PLEASE SEE NO PANEL SCHEDULE FOR EITHER |
| OUTSIDE 8/16 CIRCUIT PANELS WERE |
| SUBMITTED. |
| PLEASE SEE RISER ONLY INDICATES THE 150A |
| MCB'S. |
| PLEASE ADJUST. |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE IRRIGATION PUMP ON |
| PLANS, NOT ON PANEL SCHEDULE OR LOADS. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE PREVIOUS NOTE # 10 |
| REQUESTED LTR FROM ARCHITECT. PLEASE SEE |
| LTR SUBMITTED IS REQUIRED TO BE SEALED |
| AND DATED. FS 481.221 |
| PLEASE ALSO SEE LETTER IS REQUIRED TO BE |
| CORRECTLY NOTORIZED AS SET-FORTH UNDER |
| FS 117.05 FOR NOTORIES. |
| PLEASE SEE MIN INFORMATION REQUIRED. |
| THE STAMP AND SIGNATURE IS INSUFFICENT. |
| |
| 4)NOTE: PLEASE SEE RISER SHOWS 3-1/0'S |
| AND #6 CONDUCTORS IN A 1" CONDUIT? |
| PLEASE SEE TABLE 9 FOR PIPE FILL. |
| PLEASE ADJUST. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |